Operation<br />

Frequency Range<br />

Voltage/current type sensor: 0.25 to 2.0 kHz<br />

Contact closure type sensor: 0.25 to 30 Hz<br />

Low threshold: +1.0 VDC min<br />

High threshold: +3.2 VDC max<br />

Low or High Pulse Duration<br />

Voltage/current type sensor: 200 us min<br />

Contact closure type sensor: 15 ms min<br />

Hysteresis<br />

0.5 VDC minimum<br />

Input impedance<br />

10 k-ohm typical, 500 ohm minimum<br />

Input source current<br />

-2 mA nom. at 0 VDC<br />

Max. non-destructive Input voltage<br />

±50 peak, continuous<br />

Current Output<br />

1 current output<br />

Output range: User selectable 0 – 20 mA or 4-20 mA, representing 0 to<br />

100% variable.<br />

Resistive load: 800 ohm max. Loop<br />

Capacitive load: No limit<br />

Standard Communication<br />

Serial Interface<br />

Type: Conforms to RS-232C, RS-485/422, and 20 mA<br />

standards; supports 2 and 4 wire multi-drop in RS-<br />

485. 20 mA loop is passive ONLY.<br />

Interfacing: RS-485 supports 2-wire or 4-wire multi-drop<br />

networking; RS 232 C provides support for modem.<br />

Data rate: 300 to 19200, operator selectable from the<br />

keyboard.<br />

Data Format: Asynchronous, bit-serial, selectable parity, data<br />

length, and stop bits.<br />

Optical Isolation: 250 VRMS max.<br />

Input Voltage: ±30 Vdc max. (RS-232C)<br />

±15/-10 Vdc max. (RS-485)<br />

Cable Length: 50 feet max. (RS-232C)<br />

4000 feet max (Rs-485 and 20 mA)<br />

1-10Installation<br />

<strong>Thermo</strong> Fisher Scientific<br />

REC 4175 Rev B