Menus<br />

A.12. MAIN MENU 5<br />

Main Menu 5 is dedicated to the serial option. COMM A is used to set up the<br />

serial line and PRINT is used for setting up the printer output. Main Menu 5<br />

does not appear unless an optional COMM A is installed.<br />

A.12.1. Communication A Scroll<br />

The MT 3101 has one serial channel, which can be configured using jumpers as<br />

an RS232 or an RS485 channel. The serial channel can be used for printing or<br />

for a serial communication with an intelligent device such as a PLC or a PC. An<br />

additional COMM A board can be installed and programmed, typically one for<br />

the printer and one for networking.<br />

The following screens define the communication parameters for the first and the<br />

second channel.<br />

COMM A SCROLL<br />

Baud Rate port #1<br />

Password: Service<br />

> 9600 <<br />

CHOICE ENTER<br />

Default: 9600<br />

Selections: 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200<br />

- COMM. A SCROLL 2 -<br />

Set parity port #1<br />

> No parity <<br />

CHOICE ENTER<br />

Default: NO PARITY<br />

Selections: EVEN PARITY, ODD PARITY, NO PARITY<br />

- COMM. A SCROLL 3 -<br />

Stop bits port #1<br />

> 1 stop bit <<br />

CHOICE ENTER<br />

Default: 1 STOP BIT<br />

Selections: 1 STOP BIT, 2 STOP BITS<br />

Password: Service<br />

Password: Service<br />

A-66 Weighbridge Physical Parameters <strong>Thermo</strong> Fisher Scientific<br />

REC 4175 Rev B