A.5.9. Displayed Damping Factors<br />

The process variable when displayed on the screen can be damped by a<br />

programmable factor to filter out variations that can be introduced by<br />

mechanical vibrations.<br />

To tune a damping filter, enter the number of seconds corresponding to the<br />

desired time constant.<br />

Example: 10 seconds is entered for a damping factor. Following a step change,<br />

the process variable reaches 60% of the final value in 10 seconds. This damping<br />

factor only affects the display, not the current output variable, which has a<br />

separate damping factor.<br />

Default: 2 sec<br />

Min: 0 sec<br />

Max: 400 sec<br />

Damping Display Load<br />

Display Scroll 11 is only visible if the Run display line 3 is set to Load (refer to<br />

Section A.5.8).<br />

Default: 2 sec<br />

Min: 0 sec<br />

Max: 400 sec<br />

Damping Display Speed<br />

Display Scroll 12 is only visible if the Run display line 3 is set to speed (refer to<br />

Section A.5.8).<br />

Default: 2 sec<br />

Min: 0 sec<br />

Max: 400 sec<br />

-- DISPLAY SCROLL 10 --<br />

Damping Display RATE<br />

Damping = 2 sec<br />

ENTER<br />

-- DISPLAY SCROLL 11 --<br />

Damping Display LOAD<br />

Damping = 2 sec<br />

ENTER<br />

-- DISPLAY SCROLL 12 --<br />

Damping Displ SPEED<br />

Damping = 2 sec<br />

ENTER<br />

Password:<br />

Operator<br />

<strong>Thermo</strong> Fisher Scientific Weighbridge Physical Parameters A-19<br />

REC 4175 Rev B