Profibus-<strong>DP</strong> Model 3102<br />

2-2<br />

2. When electrically isolated bus segments are required, or<br />

3. When the maximum cable length of a segment (standard LAN cable)<br />

is exceeded (see Table 2-1).<br />

TABLE 2-1<br />

MAXIMUM CABLE LENGTH OF A SEGMENT (STANDARD LAN CABLE)<br />

Transmission Rate<br />

9.6 to 93.75 Kbps<br />

187.50 Kbps<br />

500.00 Kbps<br />

1.50 Mbps<br />

3.0 to 12.00 Mbps<br />

Maximum Cable Length of a<br />

Segment (in m)<br />

1000<br />

Rules<br />

If you want to install the bus with RS 485 repeaters, the following rules apply:<br />

1. A maximum of 9 RS 485 repeaters can be connected in series.<br />

2. The maximum cable length between two nodes must not exceed the<br />

values in Table 2-2.<br />

TABLE 2-2<br />

MAXIMUM CABLE LENGTH BETWEEN TWO NODES (STANDARD LAN<br />

CABLES)<br />

9.6 to 93.75 Kbps<br />

187.50 Kbps<br />

500.00 Kbps<br />

1.50 Mbps<br />

3.0 to 12.00 Mbps<br />

Transmission Rate<br />

2.3 Profibus-<strong>DP</strong> Connector<br />

800<br />

400<br />

200<br />

100<br />

Maximum Cable Length Between<br />

Two Nodes (in m) With RS 485<br />

Repeaters<br />

10000<br />

8000<br />

4000<br />

2000<br />

1000<br />

The bus connector should be rated for 12 Mbaud and contain a termination<br />

resistor that can be switched on or off. Siemens bus connector 6ES7 972-OBA20-<br />

OXAO is available from Thermo <strong>Ramsey</strong>, part number 057416.<br />