Trade Program 2011/2012 inTelligenT swiTching ... - Graesslin.de
Trade Program 2011/2012 inTelligenT swiTching ... - Graesslin.de
Trade Program 2011/2012 inTelligenT swiTching ... - Graesslin.de
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Technical data<br />
Dimensions H x W x D (mm) 87 x 154 x 27<br />
Weight (g) approx. 200<br />
Operating voltage Battery 2 x 1,5V AA LR6 alkaline<br />
Battery lifetime 2 years<br />
(<strong>de</strong>p. on switching frequency)<br />
Battery back-up 10 min.<br />
(programs retained in EPROM)<br />
Switching output 1 changeover contact (potential-free)<br />
Resistive load 6 (2) A 250 V AC<br />
Connection type max. 1,5 mm 2<br />
Regulation cycles (selectable) 2 points, PID<br />
Sensing element 100 K (at 25°C) NTC<br />
Ambient temperature resolution 0,1ºC<br />
Time setting resolution<br />
– program<br />
– frost protection<br />
+5°C … +32°C (0,5°C steps)<br />
+5°C (adjustable +3°C … +7°C)<br />
Time display 24 h or 12 h AM/PM Format<br />
Time setting resolution<br />
– time of day<br />
– program<br />
1 minute<br />
30 minutes<br />
Temperature control accuracy 0,5°C (20°C 3 K/hour)<br />
Thermal gradient (heating system) 3 K/hour<br />
Room temperature display range 0ºC … +50ºC<br />
<strong>Program</strong>ming weekly program with up to 48 time<br />
and temperature level changes<br />
Pre-set programs 4 + 1 user <strong>de</strong>fined<br />
Operating temperature range Max. 45ºC<br />
Operating humidity range 10% to 90% relative humidity,<br />
not con<strong>de</strong>nsing<br />
Storing temperature limits -20ºC to +55ºC<br />
Protection class II<br />
Protection type IP40<br />
According to EN 60730-1, EN 60730-2-7<br />
EN 60730-2-9, EN 55014-1<br />
EN 55014-2, EN 61000-6-2<br />
dimensional drawings /<br />
circuit diagrams:<br />
feeling D 101<br />
feeling D 101<br />
87<br />
28<br />
wiring diagram<br />
for boiler / heater<br />
1<br />
C<br />
2<br />
154<br />
NC<br />
NO<br />
3<br />
boiler / heater<br />
wiring diagram<br />
for motorized valves<br />
N L<br />
1<br />
C<br />
NC<br />
NO<br />
2<br />
M<br />
3<br />
valve<br />
feeling<br />
69<br />
Room thermostat<br />
clocks