The <strong>Coadis</strong> Slim :<br />
Ductable units<br />
<strong>Coadis</strong> <strong>SLIM</strong><br />
high pressure, thin,<br />
ductable unit<br />
- a terminal unit with high available static pressure (90 Pa)<br />
- reduced thickness (230mm), and a false ceiling occupancy surface less important<br />
- easy maintenance, without dismantling the unit, thanks to an easy access to the fan motor, air filter, electric heaters, as well<br />
as to the hydraulic coil assembly.<br />
- very low acoustic level<br />
- Large diameter impellers (Ø160mm) satisfying the high available static pressure requirements and capable of keeping correct<br />
performances in spite of filter fouling<br />
Refer to our residential offer with RESIDENCIAT system<br />
USE<br />
<strong>Coadis</strong> Slim is an independent air conditioning terminal unit to be installed in false ceiling. It is especially designed to meet<br />
the requirements of tertiary premises with very reduced space between ceiling and false ceiling.<br />
Range<br />
Available in 2-pipe, 2-pipe + 2- wire and 4-pipe systems; 2 models of COADIS Slim are available :<br />
● Model I : The unit recovers the bulk air at the rear and discharges it through a rectangular sleeve :<br />
- Air recovery grille (optional) with possibility of a filter on the unit or on the recovery grille (consult us)<br />
- Air diffusion kit with grille and counter-frame to be sealed for soffit installation (optional - consult us). For more information,<br />
refer to COADIS COMFORT brochure<br />
● Modèle Y : This unit recovers the bulk air at the rear and discharges it through circular shells :<br />
- Air return plenum (optional) for ducted air intake<br />
- Complete kit of air diffusion with grille, duct and plenum for soffit installation (optional, consult us). For more information see<br />
COADIS Comfort brochure.<br />
Reduced thickness unit, <strong>Coadis</strong> Slim comes in 3 sizes :<br />
235/11, 235/22 and 235/33<br />
Easy access to the fan motor , filter, electric heaters and coil + condensates drain pan assembly simplifies and reduces the<br />
costs of the maintenance operations.<br />
The Ciat company participates to the EUROVENT certification programme for fan coil units. See performances in Eurovent mode, on last page<br />
of the range. The list of certified products and characteristics is listed in the EUROVENT manual, also available on the internet site<br />
www.eurovent-certification.com<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
COADIS <strong>SLIM</strong><br />
1
2<br />
Ductable units<br />
Hydraulical<br />
pipings<br />
Condensates<br />
evacuation<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
<strong>SLIM</strong><br />
<strong>Coadis</strong> Slim is easy to install on four threaded rods, preferably with resilient mounts.<br />
Hydraulic connections can be made from pipes in suspended ceiling of the corridor adjacent to the room.<br />
The condensates drain pan is designed so as to avoid water retention. "Dry" drain pan prevents bacteria proliferation and<br />
interior corrosion.<br />
<strong>Coadis</strong> Slim has been designed for offices in great need of available static pressure (90 Pa nominal output flow).<br />
Large diameter (160mm) impellers ensure a correct output flow in spite of filter clogging. Long lasting performances of the<br />
unit . <strong>Coadis</strong> Slim meets perfectly the constraints of the new thermal regulations.<br />
Its very low latent power allows to save energy and to optimize the selection of water chillers.<br />
Fresh air supply is possible (consult us).<br />
COADIS <strong>SLIM</strong> IS THE IDEAL SOLUTION FOR OPEN-PLAN OFFICES.<br />
<strong>Coadis</strong> Slim<br />
Traditional ductable<br />
COADIS <strong>SLIM</strong><br />
Condensates draining<br />
to 208 mm<br />
h<br />
<strong>Coadis</strong> Slim has a condensates drainage height (h) superior to the one of the majority of ductable units. The condensates<br />
can be drained on a long piping distance by keeping a satisfactory draining slope. Therefore, in most cases, <strong>Coadis</strong> Slim can<br />
function without condensates drain pump. <strong>Coadis</strong> Slim is the ideal solution for open-plan offices.
Ductable units<br />
TECHNICAL DESCRIPTION<br />
Water coil, 2 or 4-pipe system<br />
- Galvanised sheet metal<br />
- Copper pipes, continuous aluminium fins<br />
- Monoblock connector with 40 mm between axis for direct<br />
control valve mounting<br />
- Air bleed and draining<br />
- Nominal pressure 16 bar (20°C)<br />
- Test pressure 24 bar<br />
- Max water temperature : 110°C (PN 10)<br />
- Water coil connectors on the left or right side of the unit<br />
facing the air discharge (to be mentioned on order)<br />
Electric heater, 2-pipe<br />
+ 2 wires system<br />
- Single-tube electric heating element(s) 230/1/50 integrated<br />
in the aluminium block.<br />
- Manually-reset capillary temperature limiter.<br />
Condensates drain pan<br />
- Polymer drain pan<br />
- Without water retention, condensates draining at the level of<br />
the reclined drain pan bottom.<br />
- Drainage connectors reversible manually to the front or rear.<br />
- 4 drainage diameters : 15, 16, 22 or 28 mm in standard.<br />
Fan motor assembly<br />
● Motor<br />
- 7 speeds, 3 are pre-wired in factory (this wiring can be<br />
modified on site).<br />
- Sealed, tropicalised, class B with protected shaft.<br />
- Permanent condenser.<br />
- Automatic normally closed overload protection on coil<br />
- Resilient mounts.<br />
- Power supply 230/1/5.<br />
- Reduced power consumption.<br />
● Fan(s)<br />
- Galvanised sheet metal scroll(s).<br />
- Direct drive aluminium impeller(s) Ø160mm, dynamically<br />
balanced double inlets.<br />
Air filter<br />
- Positioned on the air return, the filter is easily accessible<br />
- Flexible filtering media in polyester fibers, cleanable<br />
- EN 779 : G3 efficiency<br />
- Fire rating M1<br />
- Rigid metal frame<br />
Frame<br />
- Galvanised sheet metal<br />
- Thermal and acoustic insulation in melamine resin on<br />
discharge side, open cells soft foam, with aluminium film,fire<br />
rating M1.<br />
● Y Model :<br />
- air discharge through Ø200mm circular shells for the<br />
standard version (1 for 235/11, 2 235/22 and 3 for 235/33).<br />
Optional, air discharge through Ø160mm circular shells for<br />
CIAT diffusion kit below.<br />
● I Model :<br />
Air discharge through rectangular sleeve<br />
Electrical box<br />
- on hydraulic connection side<br />
- Entirely sealed.<br />
- DIN railing in accordance with EN 50022, 7.5 mm.depth<br />
- Cable stops for customer's connection<br />
Air return plenum (optional)<br />
- 150 mm thick air return plenum with filter (possibility of fresh<br />
air nozzles, consult us)<br />
- 30 mm thick air return plenum without filter (the filter will<br />
have to be planned on the air return grille by the installer)<br />
Diffusion kit for soffit air discharge<br />
(optional, consult us), see <strong>Coadis</strong><br />
Comfort :<br />
I Model :<br />
● Air diffusion grille<br />
- WHITE RAL 9010 plain colour<br />
- Double deflection dampers allowing air jet to adhere to the<br />
ceiling by Coanda effect.<br />
- Simplified assembly with quarter of a turn locks<br />
● Counter frame<br />
Y Model :<br />
● Air discharge grille<br />
- WHITE RAL 9010 plain colour<br />
- Double deflection damper allowing air jet to adhere to the<br />
ceiling by Coanda effect.<br />
- simplified assembly with quarter of a turn locks<br />
● Discharge plenum<br />
- Galvanised steel sheet with grille fixation<br />
- Thermal insulation avoiding condensation<br />
- Ø 160mm circular nozzle (1 for 235/11, 2 for 235/22 and 3<br />
for 2335/33)<br />
● Telescopic sleeve<br />
- Allows the connection between grille and plenum<br />
- Can be integrated in a 120 mm max. thickness wall.<br />
● Circular isophonic flexible duct<br />
- Sold separately per standard length, to be cut on site<br />
Note : Refer to user's installation brochure for further<br />
information<br />
CONTROLS<br />
Wall-mounted electronic thermostat range<br />
V20 electronic range.<br />
V200 electronic range.<br />
V2000 ® electronic range.<br />
LON control, consult us.<br />
ACCESSORIES<br />
Resilient fixation mounts.<br />
Ø100 mm smooth sleeve for possible treated fresh air inlet.<br />
Ø100 mm smooth sleeve with gasket and self adjusting<br />
module for possible treated fresh air inlet.<br />
Ø 125 mm sleeve with or without self adjusting module,<br />
consult us.<br />
OPTIONAL (CONSULT US)<br />
- 60Hz operation (230V)<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
COADIS <strong>SLIM</strong><br />
3
4<br />
Ductable units<br />
MODEL I DIMENSIONS<br />
230 Overall<br />
dimensions<br />
20<br />
Attachment holes C<br />
20<br />
1) 1) Air vent<br />
2) Coil drain<br />
A<br />
3) Monoblock connectors with a fixed<br />
40 mm between axis<br />
4) 2 piece flat surface male/female<br />
hydraulic connectors 3/8" -> 1/2"<br />
5) Mounting example of a 2 or 4-way<br />
flat surface valve mounting<br />
(integrated with water regulation<br />
loop)<br />
6) O-ring<br />
Air filter<br />
25<br />
Electric box<br />
e : Water coil inlet<br />
s : Water coil outlet<br />
Overall dimensions 609<br />
570<br />
Cold water coil G3/8”<br />
520<br />
MODELS I AND Y HYDRAULIC CONNECTIONS<br />
40<br />
Hot water coil G3/8”<br />
∅16<br />
100 108<br />
5<br />
20<br />
150<br />
Oblong slots 12 x 30<br />
Condensate<br />
drain pan<br />
AB<br />
2<br />
s<br />
e<br />
B<br />
1<br />
6<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
A<br />
G1/2" G1/2"<br />
B<br />
4<br />
80 35<br />
G3/8" G3/8"<br />
Rectangular air<br />
diffusion grille kit<br />
(consult us)<br />
3<br />
Overall dimensions A<br />
39 B<br />
140<br />
AB<br />
A<br />
G 1/2"<br />
5<br />
1<br />
208.5<br />
Condensates outlet<br />
. Dry drain pan, without water retention,<br />
avoiding bacteria proliferation<br />
. Polymer material smooth drain pan<br />
. Reversible connections with<br />
4 diameters : 15, 16, 22 or 28mm.<br />
G 3/8"<br />
<strong>SLIM</strong><br />
A B C<br />
235/11 604 425 460<br />
235/22 904 725 760<br />
235/33 1204 1025 1060
230 Overall<br />
dimensions<br />
Ductable units<br />
Y MODEL DIMENSIONS<br />
Air<br />
filter<br />
20<br />
20 Attachment holes C<br />
Cold water coil G3/8”<br />
25<br />
Electric box<br />
632 Overall dimensions<br />
570<br />
520<br />
Detail A<br />
A<br />
40<br />
77<br />
55.5 129<br />
∅16<br />
100 108<br />
. Dry drain pan, without water retention,<br />
avoiding bacteria proliferation<br />
. Polymer material smooth drain pan<br />
. Reversible connections with<br />
4 diameters : 15, 16, 22 or 28mm.<br />
43<br />
∅200<br />
Hot water coil G3/8”<br />
35<br />
Condensate<br />
drain pan<br />
Oblong slots 12 x 30<br />
Views facing the<br />
discharge<br />
Overall dimensions A<br />
39 B<br />
140<br />
A B C D<br />
235/11 604 425 460 212.5<br />
235/22 904 725 760 232.5<br />
235/33 1204 1025 1060 262.5<br />
Ø200mm discharge nozzles for standard version and Ø160mm when using the Ciat diffusion kit (optional)<br />
Refer to user's brochure for aeraulic balance<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
235/22<br />
235/33<br />
235/11<br />
Diffusion kit for soffit air discharge (optional, consult us)<br />
D D<br />
D 260 D<br />
D 250 250 D<br />
208.5<br />
Condensates outlet<br />
COADIS <strong>SLIM</strong><br />
5
6<br />
Ductable units<br />
MODEL Y ACCESSORIES DIMENSIONS<br />
Sheet metal air return plenum<br />
Thickness = 30mm without filter<br />
50 30<br />
230 Overall dimensions<br />
∅200<br />
20<br />
Attachment holes C<br />
20<br />
Without filter<br />
- The air return plenum has Ø200mm nozzles in the standard version with :<br />
1 nozzle for 235/11 size<br />
2 nozzles for 235/22 size<br />
3 nozzles for 235/33 size<br />
- it is possible to plan, on request, pre-punched holes for fresh air inlet.<br />
Sheet metal air return plenum<br />
Thickness = 150mm with filter<br />
50 170<br />
<strong>Coadis</strong> slim C<br />
235/11 460<br />
235/22 760<br />
235/33 1060<br />
- In case of an air return plenum without filter, the installer will have to supply its own filter on the air return grille<br />
AIR DIFFUSION KIT FOR SOFFIT INSTALLATION (SEE COADIS COMFORT)<br />
I Model + air diffusion kit<br />
Rectangular plenum supplied by customer<br />
Wall<br />
Air diffusion<br />
grille<br />
Counter<br />
frame to<br />
be sealed<br />
DIFFUSION KIT<br />
230 Overall<br />
dimensionst<br />
Air filter<br />
Y Model + Diffusion Kit<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
20<br />
Attachment holes C<br />
20<br />
∅200<br />
Pre-cut hole for possible<br />
treated fresh air inlet<br />
25<br />
Isophonic circular duct<br />
Diffusion plenum<br />
Telescopic sleeve<br />
Air diffusion grille<br />
DIFFUSION KIT<br />
<strong>SLIM</strong><br />
Wall
COADIS<br />
<strong>SLIM</strong><br />
Motor<br />
reference<br />
Ductable units<br />
THERMAL PERFORMANCES<br />
235/11<br />
235/22<br />
235/33<br />
Air flow<br />
m 3 /h<br />
Available<br />
static<br />
pressure Pa<br />
(1)<br />
2-pipe<br />
system W<br />
coil heating<br />
capacity<br />
Cooling capacity<br />
4-pipe W<br />
type coil<br />
heating<br />
capacity<br />
ISO or NR<br />
comfort<br />
level<br />
Air temperature mean rise in K (2)<br />
Auxillary electric heater 230/1/50<br />
Total Sensible 1R 1R 2R<br />
600 1200<br />
R1 355 40 5 390 1 730 1 430 1 920 38 5,0 10,0<br />
R2 325 5 050 1 630 1 330 1 850 35 5,5 11,0<br />
R3 290 4 620 1 500 1 200 1 760 32 6,1 12,3<br />
R4 250 4 120 1 350 1 060 1 660 28 7,1 14,3<br />
R5 200 3 480 1 150 887 1 500 23 8,9 17,8<br />
R6 145 2 670 903 683 1 290 17 12,3 24,6<br />
R7 105 1 940 673 501 1 060
8<br />
<strong>Coadis</strong> Slim<br />
Ductable units<br />
PRICE WITHOUT VAT<br />
I Model<br />
Y Model<br />
235/11<br />
235/22<br />
235/33*<br />
235/11<br />
235/22<br />
235/33*<br />
* Extra price for special<br />
motor size 235/33<br />
(consult us for<br />
characteristics).<br />
Water coil only<br />
Standard unit<br />
Water coil + electric element (2-pipe + 2 wires system)<br />
Connectors on left Connectors on right Connectors on left Prise à droite<br />
2-pipe<br />
system<br />
4-pipe<br />
system<br />
2-pipe<br />
system<br />
4-pipe<br />
system<br />
Code 7062213 7086872 7086876 7086880<br />
1 heating element<br />
600W<br />
7086885<br />
2 heating<br />
elements<br />
1200W<br />
7086886<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -<br />
1 heating element<br />
600W<br />
7086896<br />
<strong>SLIM</strong><br />
2 heating<br />
elements<br />
1200W<br />
7086897<br />
€ ● ● ● ● ● ● ● ●<br />
Code 7062220 7086873 7086877 7086881<br />
900W<br />
7086888<br />
1800W<br />
7086889<br />
900W<br />
7086899<br />
€ ● ● ● ● ● ● ● ●<br />
Code 7062221 7086874 7086878 7086882<br />
1200W<br />
7086890<br />
1800W<br />
7086891<br />
2400W<br />
7086892<br />
1200W<br />
7086901<br />
1800W<br />
7086902<br />
€ ● ● ● ● ● ● ● ● ● ●<br />
Code 7062222 7086909 7086914 7086918<br />
600W<br />
7086922<br />
1200W<br />
7086923<br />
600W<br />
7086933<br />
€ ● ● ● ● ● ● ● ●<br />
Code 7062223 7086910 7086915 7086919<br />
900W<br />
7086924<br />
1800W<br />
7086925<br />
900W<br />
7086936<br />
€ ● ● ● ● ● ● ● ●<br />
Code 7062225 7086912 7086916 7086920<br />
1200W<br />
7086926<br />
1800W<br />
7086928<br />
2400W<br />
7086929<br />
1200W<br />
7086938<br />
1800W<br />
7086940<br />
€ ● ● ● ● ● ● ● ● ● ●<br />
Code E040290<br />
€ ●<br />
See pages on controls for a complete offer : terminal unit + control<br />
COADIS <strong>SLIM</strong> OPTIONS (FITTED ON THE UNIT)<br />
Designation 235/11 235/22 235/33<br />
Sheet metal air return plenum with circular Ø200mm nozzles and filter housing<br />
€<br />
●<br />
€<br />
●<br />
€<br />
●<br />
Air intake plenum with Ø200mm nozzles, without filter<br />
€<br />
●<br />
€<br />
●<br />
€<br />
●<br />
Designation<br />
Condensates draining pump mounted on the unit with overflow<br />
safety device. 8/h max. flow for a 1 m draining height.<br />
Draining : 6mm internal diameter flexible tube, 8mm diameter<br />
nozzle. This accessory must be completed with a valve type<br />
regulation allowing slaving of the high safety device to the valve<br />
closing (condensates stopped).<br />
Approximate calculation of the condensate water flow :<br />
Qv (l/h) = (P totale - P sensible) (W)/ 680<br />
Price<br />
Code €<br />
E045004 ●<br />
NN AA 00 66 .. 66 11 88 CC<br />
1800W<br />
7086900<br />
2400W<br />
7086903<br />
1200W<br />
7086935<br />
1800W<br />
7086937<br />
2400W<br />
7086941
Ductable units<br />
ACCESSORIES (SUPPLIED SEPARATELY)<br />
Designation<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
Price<br />
Code €<br />
Resilient mounts supplied separately (4 required per unit) 0219453 ●<br />
Smooth sleeve alone, ext. Ø 100 mm with screws. 7013442 ●<br />
Shell assembly, ext. Ø100mm (2) with self adjusting module<br />
equipped with a gasket.<br />
Packed with screws and assembly drawing.<br />
The air flow rate controller is designed to supply a determined flow<br />
(1) with a differential pressure between 50 and 100 Pa.<br />
(1) 3 air flows are available by using wedges. The minimum air flow<br />
is by default.<br />
(2) Ø125mm, consult us<br />
2 piece male / female connectors<br />
15(1)/30/45<br />
m 3 /h<br />
60(1)/75/90<br />
m 3 /h<br />
Condensates draining pump Kit to be mounted on the unit with overflow safety device. 8/h max. flow for a 1 m draining height.<br />
Draining : 6mm internal diameter flexible tube, 8mm diameter nozzle. This accessory must be completed with a valve type<br />
regulation allowing slaving of the high safety device to the valve closing (condensates stopped).<br />
Approximate calculation of the condensate water flow : Qv (l/h) = (P totale - P sensible) (W)/ 680<br />
* In case of fresh air intake only<br />
*<br />
*<br />
All-or-nothing 230/1/50 motorised damper, voltage absence closing,<br />
for use with ResidenCiat system (SUPPLIED SEPARATELY)<br />
7013440 ●<br />
7013544 ●<br />
5202314 ●<br />
7023316 ●<br />
Ø200 5202619 ●<br />
Ø160 5202618 ●<br />
COADIS <strong>SLIM</strong><br />
9
10<br />
Ductable units<br />
EUVOVENT PERFORMANCES - 2-PIPE SYSTEM<br />
CIAT takes part in the EUROVENT fan coil unit certification program.In order to profit from the last<br />
updates, we advise you to consult Internet site EUROVENT www.eurovent-certification.com<br />
EUROVENT mode, 2-pipe system :<br />
- Summer : cold water 7/12°C, air 27°C BH 19°C<br />
- Winter : hot water inlet 50°C for determined in summer mode, air 20°C<br />
For ductable units, the air flows are determined by a available static pressure of 50Pa in medium speed.<br />
2-pipe<br />
COADIS<br />
<strong>SLIM</strong><br />
235/11<br />
235/22<br />
235/33<br />
Motor<br />
reference<br />
Dp : pressure drop<br />
Lw : acoustic dBA power<br />
Air flow<br />
Available<br />
static<br />
pressure<br />
Sensible<br />
cooling<br />
capacity<br />
Total<br />
cooling<br />
capacity<br />
Total<br />
heating<br />
capacit<br />
Dp cold Dp hot Lw Diffusion<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
<strong>SLIM</strong><br />
Lw air intake<br />
+<br />
radiated<br />
m3 /h Pa kW kW kW kPa kPa dBA dBA<br />
R1 255 71 1,06 1,18 1,68 11,2 9,6 56 59<br />
R2 240 62 1 1,11 1,59 10,1 8,7 54 57<br />
R3 215 50 0,91 1,02 1,47 8,6 7,4 52 55<br />
R4 190 39 0,81 0,92 1,33 7,1 6,2 49 51<br />
R5 160 27 0,7 0,8 1,14 5,5 4,8 44 47<br />
R6 120 15 0,55 0,65 0,9 3,7 3,3 38 41<br />
R7 85 8 0,41 0,48 0,66 2,2 2 28 33<br />
R1 465 77 1,98 2,31 3,11 12,1 10,5 59 62<br />
R2 425 64 1,82 2,17 2,91 10,7 9,4 56 60<br />
R3 375 50 1,63 1,99 2,65 9,1 8,1 53 56<br />
R4 325 37 1,44 1,78 2,34 7,4 6,6 50 52<br />
R5 280 27 1,26 1,57 2,08 5,9 5,3 46 48<br />
R6 230 18 1,06 1,32 1,75 4,3 3,9 41 43<br />
R7 175 11 0,83 1,03 1,37 2,7 2,5 35 37<br />
R1 615 68 2,86 3,43 4,34 31,5 27 57 60<br />
R2 525 50 2,52 3,07 3,83 25,7 22,1 53 56<br />
R3 455 37 2,21 2,74 3,4 21 18 49 52<br />
R4 385 26 1,9 2,39 2,94 16,4 14,1 45 47<br />
R5 310 17 1,58 2,02 2,47 12 10,5 40 42<br />
R6 250 11 1,29 1,67 2 8,5 7,4 35 37<br />
R7 185 6 0,97 1,27 1,54 5,1 4,6 28 29
Ductable units<br />
EUVOVENT PERFORMANCES - 4-PIPE SYSTEM<br />
CIAT takes part in the EUROVENT fan coil unit certification program.In order to profit from the last<br />
updates, we advise you to consult Internet site EUROVENT www.eurovent-certification.com<br />
EUROVENT mode, 2-pipe system :<br />
- Summer: cold water 7/12°C, air 27°C BH 19°C<br />
- Winter: hot water 70°C/60°, air 20°C<br />
For ductable units, the air flows are determined by a available static pressure of 50Pa in medium speed.<br />
4-pipe<br />
COADIS<br />
<strong>SLIM</strong><br />
235/11<br />
235/22<br />
235/33<br />
Motor<br />
reference<br />
Dp : pressure drop<br />
Lw : acoustic dBA power<br />
Air flow<br />
Available<br />
static<br />
pressure<br />
Sensible<br />
cooling<br />
capacity<br />
Total<br />
cooling<br />
capacity<br />
Total<br />
heating<br />
capacit<br />
Dp cold Dp hot Lw Diffusion<br />
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E - NN AA 00 66 .. 66 11 88 CC<br />
Lw air intake<br />
+<br />
radiated<br />
m3 /h Pa kW kW kW kPa kPa dBA dBA<br />
R1 255 71 1,06 1,18 1,26 11,2 1,6 56 59<br />
R2 240 62 1 1,11 1,23 10,1 1,5 54 57<br />
R3 215 50 0,91 1,02 1,17 8,6 1,4 52 55<br />
R4 190 39 0,81 0,92 1,1 7,1 1,3 49 51<br />
R5 160 27 0,7 0,8 1 5,5 1,1 44 47<br />
R6 120 15 0,55 0,65 0,86 3,7 0,8 38 41<br />
R7 85 8 0,41 0,48 0,69 2,2 0,6 28 33<br />
R1 465 77 1,98 2,31 2,57 12,1 8 59 62<br />
R2 425 64 1,82 2,17 2,45 10,7 7,4 56 60<br />
R3 375 50 1,63 1,99 2,3 9,1 6,6 53 56<br />
R4 325 37 1,44 1,78 2,12 7,4 5,7 50 52<br />
R5 280 27 1,26 1,57 1,96 5,9 5 46 48<br />
R6 230 18 1,06 1,32 1,74 4,3 4,1 41 43<br />
R7 175 11 0,83 1,03 1,47 2,7 3 35 37<br />
R1 615 68 2,86 3,43 3,93 31,5 20,5 57 60<br />
R2 525 50 2,52 3,07 3,62 25,7 17,8 53 56<br />
R3 455 37 2,21 2,74 3,34 21 15,5 49 52<br />
R4 385 26 1,9 2,39 3,03 16,4 13 45 47<br />
R5 310 17 1,58 2,02 2,68 12 10,5 40 42<br />
R6 250 11 1,29 1,67 2,31 8,5 8,1 35 37<br />
R7 185 6 0,97 1,27 1,89 5,1 5,7 28 29<br />
Non contractual document. With the thought of material improvement always in mind, CIAT reserves the right,without notice, to proceed with any technical modification.<br />
Head office & Factories<br />
Avenue Jean Falconnier - B.P. 14<br />
01350 - Culoz - France<br />
Tel.: 33 4 79 42 42 42 - Fax: 33 4 79 42 42 10<br />
e-mail: info@ciat.fr - http:\\www.ciat.com<br />
CIAT Service<br />
Tél. : 33 4 79 42 42 90 - Fax : 33 4 79 42 42 13<br />
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 000 000 € - R.C.S. Belley B 545 620 114<br />
COADIS <strong>SLIM</strong><br />
11