INPOS (in positioning window)<br />

W.E.ST. Elektronik GmbH<br />

Commands Parameter Defaults Units<br />

inpos x x= 2… 2000 200 0,01%<br />

This parameter is used in 0,01% units.<br />

The INPOS command defines the window where the INPOS message is indicated. The positioning<br />

process is not influenced by this message. The controller remains active.<br />

In NC-mode this message has to be interpreted alternatively as following error.<br />

OFFSET (zero point adjustment)<br />

Commands Parameter Defaults Units<br />

offset x<br />

x= -2000… 2000 0 0,01%<br />

This parameter is entered in 0,01% units.<br />

The corresponding OFFSET will be added to the control error (demand value - actual value + offset). With<br />

this parameter the zero point failure can be compensated.<br />

POL (output polarity)<br />

Commands Parameter Defaults Units<br />

pol x x= +|- + -<br />

The output polarity of the controller can be switched over.<br />

SENS (sensor monitoring)<br />

Commands Parameter Defaults Units<br />

sens x x= ON|OFF ON -<br />

The sensor monitoring can be activated (with 4… 20 mA sensors).<br />

SAVE (data storing in EEPROM)<br />

Commands Parameter Defaults Units<br />

save - - -<br />

Every parameter change is immediately active but only saved in RAM. For permanent storing in<br />

EEPROM the command SAVE is used to copy the parameter from RAM into EEPROM memory.<br />