VELO (Internal velocity preset)<br />
W.E.ST. Elektronik GmbH<br />
Commands Parameter Defaults Units Description<br />
velo x x= 1000… 10000 10000 0,01%<br />
Here the maximum velocity can be limited internally. The limitation function corresponds to the external<br />
velocity preset if VS was parameterized with EXT.<br />
VS (internal or external velocity preset)<br />
Commands Parameter Defaults Units<br />
vs x x= EXT|INT INT<br />
Switch over between internal and external velocity preset.<br />
In case of external velocity preset external voltages at PIN 9 and PIN 10 are used. An input of 10V corresponds<br />
with 100% speed.<br />
VRAMP (ramp time for the external velocity)<br />
Commands Parameter Defaults Units<br />
vramp x x= 1… 2000 50 ms<br />
Here the ramp time for velocity changes will be set.<br />
Operating shocks can be reduced when changing the external velocity.<br />
VMODE (Activation of the NC mode)<br />
Commands Parameter Defaults Units<br />
vmode x x= ON|OFF OFF<br />
With this parameter the NC mode (almost closed loop controlled velocity) will be activated. In OFF state<br />
the stroke depended deceleration is active; the velocity preset limits the output signal.<br />
In ON state the positioning demand value is generated by a profile generator and the axis drives to the<br />
target position with the defined velocity. The stroke time is defined by the parameter th.<br />
Seite 18 von 24