SENS (sensor monitoring)<br />

W.E.<strong>ST</strong>. <strong>Elektronik</strong> <strong>GmbH</strong><br />

Kommando Parameter Vorgabe Einheit<br />

sens x x= ON|OFF ON -<br />

The sensor monitoring can be activated. The output current to the solenoids and the input signal (in case<br />

of 4… 20 mA) are monitored.<br />

SOLENOIDS (number of solenoids)<br />

Commands Parameter Defaults Units<br />

solenoids x<br />

x= 1|2 2 -<br />

If this module is used with a throttle or pressure valve solenoid A should be used only.<br />

This command is used to switch off the internal monitoring of solenoid B.<br />

Solenoids = 1 - throttle or pressure valve<br />

Solenoids = 2 - directional valves<br />

CURRENT (range of the output current)<br />

Kommando Parameter Vorgabe Einheit<br />

current x x= 0, 1, 2 0 -<br />

Selection of the output current range: 0 = 1,0 A range, 1 = 1,6 A range and 2 = 2,6 A range.<br />

If modus “RCURR” = ON, then this command is not active.<br />

The current range select done automatically.<br />

DFREQ / DAMPL (dither frequency, dither amplitude)<br />

Kommando Parameter Vorgabe Einheit<br />

dfreq x<br />

dampl x<br />

x= 60… 400<br />

x= 0… 1800<br />

120<br />

400<br />

Hz<br />

0,01%<br />

Dither amplitude. Typical values between 500 and 1200 (good experience were made with 700) 2 .<br />

Dither frequency. Typical values are between 60 and 200 (good experience were made with 125).<br />

The dither amplitude and the dither frequency are adjustable. With the dither setting the valve hysteresis<br />

can be reduced clearly. The dates for the dither setting can often be taken from the valve dates.<br />

The dither amplitude should be as high as possible, but the drive should not vibrate.<br />

Caution: Too high dither amplitude can lead to an increased attrition (the friction in the<br />

valve reduces a short start phase).<br />

Caution: If the PWM frequency is lower than 500 Hz, the dither amplitude should be set to<br />

zero. In this case the low PWM frequency is used to reduce the valve hysteresis<br />

2<br />

The current loop compensator is improved in software version 14. The amplitude has to be reduced again older versions.<br />