SENS (sensor monitoring)<br />
W.E.<strong>ST</strong>. <strong>Elektronik</strong> <strong>GmbH</strong><br />
Kommando Parameter Vorgabe Einheit<br />
sens x x= ON|OFF ON -<br />
The sensor monitoring can be activated. The output current to the solenoids and the input signal (in case<br />
of 4… 20 mA) are monitored.<br />
SOLENOIDS (number of solenoids)<br />
Commands Parameter Defaults Units<br />
solenoids x<br />
x= 1|2 2 -<br />
If this module is used with a throttle or pressure valve solenoid A should be used only.<br />
This command is used to switch off the internal monitoring of solenoid B.<br />
Solenoids = 1 - throttle or pressure valve<br />
Solenoids = 2 - directional valves<br />
CURRENT (range of the output current)<br />
Kommando Parameter Vorgabe Einheit<br />
current x x= 0, 1, 2 0 -<br />
Selection of the output current range: 0 = 1,0 A range, 1 = 1,6 A range and 2 = 2,6 A range.<br />
If modus “RCURR” = ON, then this command is not active.<br />
The current range select done automatically.<br />
DFREQ / DAMPL (dither frequency, dither amplitude)<br />
Kommando Parameter Vorgabe Einheit<br />
dfreq x<br />
dampl x<br />
x= 60… 400<br />
x= 0… 1800<br />
120<br />
400<br />
Hz<br />
0,01%<br />
Dither amplitude. Typical values between 500 and 1200 (good experience were made with 700) 2 .<br />
Dither frequency. Typical values are between 60 and 200 (good experience were made with 125).<br />
The dither amplitude and the dither frequency are adjustable. With the dither setting the valve hysteresis<br />
can be reduced clearly. The dates for the dither setting can often be taken from the valve dates.<br />
The dither amplitude should be as high as possible, but the drive should not vibrate.<br />
Caution: Too high dither amplitude can lead to an increased attrition (the friction in the<br />
valve reduces a short start phase).<br />
Caution: If the PWM frequency is lower than 500 Hz, the dither amplitude should be set to<br />
zero. In this case the low PWM frequency is used to reduce the valve hysteresis<br />
2<br />
The current loop compensator is improved in software version 14. The amplitude has to be reduced again older versions.<br />
Seite 19 von 22 12.03.2008