TYPE<br />
Single-phase transformer for single-phase networks.<br />
Cast in resin, corrosion resistant, water-tight, plug-in<br />
connection designed for directly buried installation.<br />
Protection degree : IP 68<br />
Primary voltage : 3200 V (1)<br />
Primary winding insulation level : 7.2 kV<br />
Secondary no-load voltage : 237 V (2)<br />
Secondary winding insulation level : 1.1 kV<br />
Coupling : single phase<br />
Dielectric : oil<br />
Power rating : 16 - 25 - 32 - 50 kVA<br />
Nominal power depending on public lighting standards<br />
12.8 - 20 - 25.6 - 40 kVA<br />
<strong>Transformers</strong> comply with NFC 52 410 standards.<br />
OPERATING CONDITIONS<br />
Environmental condition AD7 : can be partly or<br />
completely immersed in water for a limited time period.<br />
MV INLET<br />
A- Two-pole plug-in concentric, universal terminals for<br />
3.6/6 kV concentric two-pole cable 2 x 6, 10, 16, or<br />
25 mm² cross-section according to NF C33-221 standards.<br />
B- «Lead-through» connection in transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
Adjustment by strips off voltage, taps + 5, + 7.5 % (3)<br />
MV PROTECTION<br />
By means of HRC fuse, rupturing capacity 50 kA.<br />
MV POTENTIAL CONDITION<br />
The winding is not connected to earth potential.<br />
On request: Earthed end of the windin connected to the<br />
outer conductor (neutral) of the cable.<br />
(1) On request: other voltages compatible with primary winding<br />
insulation level.<br />
(2) On request: other voltages compatible with secondary<br />
winding insulation level.<br />
(3) Other percentage values on request.<br />
TED MMX - 16, 25, 32, 50 kVA<br />
LV OUTLET<br />
Two-pole 6 metre-long H.07.RN.F cable , cross-section:<br />
16 kVA: 25 mm² for 230 V. Two single-pole 6 metre-long<br />
H.07.RNF cable, cross-section:<br />
25 kVA: 35 mm² for 230 V.<br />
32 kVA : 50 mm² for 230 V<br />
50 kVA : 95 mm² for 230 V.<br />
On request for the 16 kVA : two-pole plug-in<br />
terminal for H.07.RN.F. cable with a maximum<br />
cross-section of 2 x 25 mm².<br />
LV PROTECTION<br />
Without LV protection<br />
On request:<br />
The cut-out device ensures magnetic protection and<br />
thermal protection by means a probe incorporated in<br />
the winding (only for the 16 and 25 kVA)<br />
Breaking capacity: 16 kVA : 85 kA - 25 kVA : 85 kA<br />
Protection by means of one HRC fuse<br />
LV POTENTIAL CONDITION<br />
One end of the LV winding is connected to the earthing<br />
terminal (blue lead).<br />
On request: centre tap of the LV winding connected to<br />
the earthing terminal.<br />
EARTHING TERMINAL<br />
By means of a M10 threaded rod, connected internally to<br />
the transformer core.<br />
DIELECTRIC TESTS<br />
Impulse withstands: 45 kV - wave 1/ 50<br />
Power frequency withstands voltage:<br />
16 kV - 50 Hz - 1 minute<br />
USER INFORMATION WRITTEN ON<br />
THE COVER<br />
Terminals assembly instructions:<br />
Manual available on request.<br />
EQUIPMENTS<br />
The transformers are delivered with:<br />
Two MV plug-in terminals for assembly.<br />
Two non-waterproof blanking off taps.<br />
The BIP is delivered separately.<br />
Handling ropes.<br />
One technical leaflet for the assembly of the MV<br />
plug-in terminals.<br />