TYPE<br />

Single-phase transformer for single-phase networks.<br />

Cast in resin, corrosion resistant, water-tight, plug-in<br />

connection designed for directly buried installation.<br />

Protection degree : IP 68<br />

Primary voltage : 3200 V (1)<br />

Primary winding insulation level : 7.2 kV<br />

Secondary no-load voltage : 237 V (2)<br />

Secondary winding insulation level : 1.1 kV<br />

Coupling : single phase<br />

Dielectric : oil<br />

Power rating : 16 - 25 - 32 - 50 kVA<br />

Nominal power depending on public lighting standards<br />

12.8 - 20 - 25.6 - 40 kVA<br />

<strong>Transformers</strong> comply with NFC 52 410 standards.<br />

OPERATING CONDITIONS<br />

Environmental condition AD7 : can be partly or<br />

completely immersed in water for a limited time period.<br />

MV INLET<br />

A- Two-pole plug-in concentric, universal terminals for<br />

3.6/6 kV concentric two-pole cable 2 x 6, 10, 16, or<br />

25 mm² cross-section according to NF C33-221 standards.<br />

B- «Lead-through» connection in transformer.<br />

TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />

Adjustment by strips off voltage, taps + 5, + 7.5 % (3)<br />

MV PROTECTION<br />

By means of HRC fuse, rupturing capacity 50 kA.<br />

MV POTENTIAL CONDITION<br />

The winding is not connected to earth potential.<br />

On request: Earthed end of the windin connected to the<br />

outer conductor (neutral) of the cable.<br />

(1) On request: other voltages compatible with primary winding<br />

insulation level.<br />

(2) On request: other voltages compatible with secondary<br />

winding insulation level.<br />

(3) Other percentage values on request.<br />

TED MMX - 16, 25, 32, 50 kVA<br />

LV OUTLET<br />

Two-pole 6 metre-long H.07.RN.F cable , cross-section:<br />

16 kVA: 25 mm² for 230 V. Two single-pole 6 metre-long<br />

H.07.RNF cable, cross-section:<br />

25 kVA: 35 mm² for 230 V.<br />

32 kVA : 50 mm² for 230 V<br />

50 kVA : 95 mm² for 230 V.<br />

On request for the 16 kVA : two-pole plug-in<br />

terminal for H.07.RN.F. cable with a maximum<br />

cross-section of 2 x 25 mm².<br />

LV PROTECTION<br />

Without LV protection<br />

On request:<br />

The cut-out device ensures magnetic protection and<br />

thermal protection by means a probe incorporated in<br />

the winding (only for the 16 and 25 kVA)<br />

Breaking capacity: 16 kVA : 85 kA - 25 kVA : 85 kA<br />

Protection by means of one HRC fuse<br />

LV POTENTIAL CONDITION<br />

One end of the LV winding is connected to the earthing<br />

terminal (blue lead).<br />

On request: centre tap of the LV winding connected to<br />

the earthing terminal.<br />

EARTHING TERMINAL<br />

By means of a M10 threaded rod, connected internally to<br />

the transformer core.<br />

DIELECTRIC TESTS<br />

Impulse withstands: 45 kV - wave 1/ 50<br />

Power frequency withstands voltage:<br />

16 kV - 50 Hz - 1 minute<br />

USER INFORMATION WRITTEN ON<br />

THE COVER<br />

Terminals assembly instructions:<br />

Manual available on request.<br />

EQUIPMENTS<br />

The transformers are delivered with:<br />

Two MV plug-in terminals for assembly.<br />

Two non-waterproof blanking off taps.<br />

The BIP is delivered separately.<br />

Handling ropes.<br />

One technical leaflet for the assembly of the MV<br />

plug-in terminals.<br />