TED MMX 400, 630 VA<br />

TED MMX 10 kVA<br />

TED MMX 1 to 5 kVA<br />

TED MMX TECHNICAL DATA - 0.4 to 10 kVA<br />

1 - MV fuses<br />

2 - MV Input terminal<br />

3 - Output terminal<br />

4 - Rating plate<br />

5 - Earth terminal<br />

6 - LV protection (optional)<br />

7 - Two-pole LV output<br />

Power rating (kVA) 400 630 1000 2000 3000 5000 10000<br />

Power output (kVA) 320 504 800 1600 2400 4000 8000<br />

Iron losses (W) 10 15 20 30 45 60 110<br />

Copper losses (W) 13 20 26 38 45 75 130<br />

Short-circuit impedance (%) 3.4 3.4 2.9 2.5 2.5 2.5 3.0<br />

Voltage drop (%) cos φ = 1 3.2 3.17 2.6 1.91 1.52 1.52 1.34<br />

Voltage drop (%) cos φ = 0,8 3.16 3.28 2.84 2.49 2.4 2.4 2.66<br />

Magnetising current (%) 12 10 9 8.5 8 8 5<br />

Length (mm) 361 361 400 400 400 400 Ø500<br />

Width (mm) 256 256 374 374 374 374 Ø500<br />

Height (mm) 430 430 435 435 435 435 565<br />

Total weight (kg) 33 35 55 60 65 77 145<br />