TYPE<br />

Single-phase transformer for single-phase networks.<br />

Cast in resin, corrosion resistant, water-tight, plug-in<br />

connection designed for directly buried installation.<br />

Protection degree : IP 68<br />

Primary voltage : 3200 V (1)<br />

Primary winding insulation level : 7,2 kV<br />

Secondary no-load voltage : 237 V (2)<br />

Secondary winding insulation level : 1,1 kV<br />

Coupling : single-phase<br />

Dielectric : oil<br />

Power rating : 400, 630, 1000, 2000, 3000,<br />

5000, 10000 VA<br />

Nominal power depending on public lighting standards<br />

320, 504, 800, 1600, 2400, 4000, 8000 VA<br />

<strong>Transformers</strong> comply with NFC 52 410 standards.<br />

CONDITIONS of USE:<br />

Environmental class AD7 : can be partly or completely<br />

immersed in water for a limited time period.<br />

MV INLET<br />

A -Two -pole plug-in concentric, universal terminals for<br />

3.6/6 kV concentric two -pole cable 2 x 6, 10, 16, or<br />

25 mm² cross-section conforming to NF C33-221 standards.<br />

B - «Lead-through» connection in transformer.<br />

TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />

No adjustment.<br />

MV PROTECTION<br />

By means of HRC fuse, rupturing capacity 15 kVA.<br />

MV POTENTIAL CONDITION<br />

The winding is not connected to earth potential.<br />

On request: Earthed end of the winding connected to<br />

outer conductor (neutral) of the cable.<br />

(1) On request: other voltages compatible with primary winding<br />

insulation level.<br />

(2) On request: other voltages compatible with secondary<br />

winding insulation level.<br />

TED MMX - 0.4 to 10 kVA<br />

LV OUTLET<br />

Two-pole 6 metre-long H.07.RN.F cable<br />

< to 1 kVA : cross-section 2 x 2.5 mm²<br />

1 to 5 kVA : cross-section 2 x 6 mm²<br />

10 kVA : cross-section 2 x 10 mm²<br />

On request : two-pole plug-in terminal for H.07.RN.F.<br />

cable with maximum 2 x 25 mm² cross-section.<br />

LV PROTECTION<br />

Without LV protection<br />

On request:<br />

The cut-out device ensures direct magnetic protection<br />

and thermal protection by means of a probe incorporated<br />

in the windings; breaking capacity: 6 kA.<br />

*Single-pole + neutral, curve B, for the TED ≤ 6 kVA<br />

*Two-pole, curve B, for the TED > 6 kVA<br />

By HRC fuses.<br />

LV POTENTIAL CONDITION<br />

One end of the LV winding is connected to the earthing terminal<br />

(blue lead).<br />

On request: centre tap of the LV winding connected to the<br />

earthing terminal. In this case, possible LV protection must<br />

be two-pole.<br />

EARTHING TERMINAL<br />

By means of a M10 threaded rod, connected internally to<br />

magnetic circuit.<br />

DIELECTRIC TESTS<br />

Impulse withstands : 45 kV - Wave 1 / 50<br />

Power frequency withstands voltage : 16 kV - 50 Hz -<br />

1 minute.<br />

USER INFORMATION WRITTEN ON COVER<br />

Terminals assembly instructions:<br />

manuals available on request.<br />

EQUIPMENTS<br />

The transformers are delivered with :<br />

Two HV preparation leaflets.<br />

Two non-waterproof transport plugs.<br />

The BIP is delivered separately.<br />

Handling ropes.<br />

Technical leaflet for the assembly of the plug-in<br />

terminals.<br />

6