TYPE<br />
Single-phase transformer for single-phase networks.<br />
Cast in resin, corrosion resistant, water-tight, plug-in<br />
connection designed for directly buried installation.<br />
Protection degree : IP 68<br />
Primary voltage : 3200 V (1)<br />
Primary winding insulation level : 7,2 kV<br />
Secondary no-load voltage : 237 V (2)<br />
Secondary winding insulation level : 1,1 kV<br />
Coupling : single-phase<br />
Dielectric : oil<br />
Power rating : 400, 630, 1000, 2000, 3000,<br />
5000, 10000 VA<br />
Nominal power depending on public lighting standards<br />
320, 504, 800, 1600, 2400, 4000, 8000 VA<br />
<strong>Transformers</strong> comply with NFC 52 410 standards.<br />
CONDITIONS of USE:<br />
Environmental class AD7 : can be partly or completely<br />
immersed in water for a limited time period.<br />
MV INLET<br />
A -Two -pole plug-in concentric, universal terminals for<br />
3.6/6 kV concentric two -pole cable 2 x 6, 10, 16, or<br />
25 mm² cross-section conforming to NF C33-221 standards.<br />
B - «Lead-through» connection in transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
No adjustment.<br />
MV PROTECTION<br />
By means of HRC fuse, rupturing capacity 15 kVA.<br />
MV POTENTIAL CONDITION<br />
The winding is not connected to earth potential.<br />
On request: Earthed end of the winding connected to<br />
outer conductor (neutral) of the cable.<br />
(1) On request: other voltages compatible with primary winding<br />
insulation level.<br />
(2) On request: other voltages compatible with secondary<br />
winding insulation level.<br />
TED MMX - 0.4 to 10 kVA<br />
LV OUTLET<br />
Two-pole 6 metre-long H.07.RN.F cable<br />
< to 1 kVA : cross-section 2 x 2.5 mm²<br />
1 to 5 kVA : cross-section 2 x 6 mm²<br />
10 kVA : cross-section 2 x 10 mm²<br />
On request : two-pole plug-in terminal for H.07.RN.F.<br />
cable with maximum 2 x 25 mm² cross-section.<br />
LV PROTECTION<br />
Without LV protection<br />
On request:<br />
The cut-out device ensures direct magnetic protection<br />
and thermal protection by means of a probe incorporated<br />
in the windings; breaking capacity: 6 kA.<br />
*Single-pole + neutral, curve B, for the TED ≤ 6 kVA<br />
*Two-pole, curve B, for the TED > 6 kVA<br />
By HRC fuses.<br />
LV POTENTIAL CONDITION<br />
One end of the LV winding is connected to the earthing terminal<br />
(blue lead).<br />
On request: centre tap of the LV winding connected to the<br />
earthing terminal. In this case, possible LV protection must<br />
be two-pole.<br />
EARTHING TERMINAL<br />
By means of a M10 threaded rod, connected internally to<br />
magnetic circuit.<br />
DIELECTRIC TESTS<br />
Impulse withstands : 45 kV - Wave 1 / 50<br />
Power frequency withstands voltage : 16 kV - 50 Hz -<br />
1 minute.<br />
USER INFORMATION WRITTEN ON COVER<br />
Terminals assembly instructions:<br />
manuals available on request.<br />
EQUIPMENTS<br />
The transformers are delivered with :<br />
Two HV preparation leaflets.<br />
Two non-waterproof transport plugs.<br />
The BIP is delivered separately.<br />
Handling ropes.<br />
Technical leaflet for the assembly of the plug-in<br />
terminals.<br />
6