TERMINAL INSULATION LIQUID :<br />
BLUE BIP<br />
INSTRUCTION FOR INJECTING BIP IN<br />
TRANSFORMER TAPS<br />
1- Preheat the BIP to about 35°C to facilitate<br />
pouring.<br />
2- Use a syringe to obtain the necessary quantity of BIP<br />
(see table below).<br />
3- Inject the BIP into tap.<br />
4- Repeat the operation for the other taps.<br />
WARNING : do not exceed the quantity of BIP,<br />
otherwise the excess liquid will automatically leak outside<br />
the terminal when the plug is inserted.<br />
Note: BIP is a dielectric which is denser than water.<br />
Therefore if water penetrates the terminal as a result of<br />
incorrect plugging in or damage to the cable, it remains on<br />
the surface.<br />
All our equipment with plug-in terminals is supplied with<br />
BIP (TED, boxes, ...). The BIP is delivered separately.<br />
WARNING : removal of a plug results in a loss of BIP<br />
and the BIP level in the terminal should therefore be topped<br />
up (added) (10cl for the three phase terminal).<br />
BIP topping up method: see diagram.<br />
NOTE : please contact us for your BIP purchases.<br />
Necessary « BIP » quantity for a tap<br />
Quantity Tap type<br />
10 ml Two-pole MV concentric plug-in terminal 6² - 10² Model « B »<br />
25 ml Two-pole MV concentric plug-in terminal 16² - 25² Model « B »<br />
25 ml Two-pole MV concentric plug-in terminal Model « X »<br />
10 ml Two-pole LV concentric plug-in terminal<br />
300 ml MV three-pole terminal<br />
BIP<br />
Tap on the TED lip<br />
(TED MMX 400 / 630<br />
kVA)<br />
125 ml MV three-pole terminal, without plug (on last transformer)<br />
Syringue<br />
27