Network Transformers - Augier
Network Transformers - Augier
Network Transformers - Augier
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
TYPE<br />
NETWORK ACCESSORIES<br />
Dead end box, junction boxes and derivation<br />
Cast in resin, corrosion resistant, watertight, for<br />
directly buried installations with plug-in terminals.<br />
Isolation voltage : 7.2 kV<br />
Operation voltage : 5.5 kV<br />
Maximum current : 80 A<br />
WORKING CONDITIONS<br />
Environment class: AD7: can be partially or totally<br />
immersed in water temporarily.<br />
Box 1A<br />
(Dead end box)<br />
Box 1A / 1D<br />
(Junction box)<br />
CONNECTION<br />
These different boxes made up of unpluggable<br />
three- pole terminals can receive either a three -pole 6/6<br />
kV cable, a radial field 3.6/6 kV cable, or a bent type<br />
three-pole cable (see notice n°60 10472).<br />
Maximum cable diameter: 44.5 mm, maximum<br />
tolerance included.<br />
They are delivered with the necessary cable end<br />
pre-paration equipment, as well as disposable blanking<br />
off taps.<br />
On request:<br />
Bent plug-in terminals.<br />
Watertight blanking off taps.<br />
Box 1A / 2D<br />
(T-junction box)<br />
Length Width Height Weight<br />
1A Ø 135<br />
374 9 kg<br />
1A / 1D 270 130 375 15 kg<br />
1A / 2D 270 270 375 22 kg<br />
1A / 3D 270 270 375 31 kg<br />
Box 1A / 3D<br />
(Cross type junction)<br />
25