GENERAL INFORMATION<br />
THREE-POLE TERMINAL : 5500 V - 80 A<br />
This terminal can receive a large number of medium<br />
voltage cables:<br />
Belt cable,<br />
Radial field cable,<br />
Twisted three-pole cable.<br />
It is made up of two parts:<br />
1- A point entirely moulded to transformer with female<br />
contacts (3 phases and 1 screen)<br />
2- The plug to be made on cable, which comprises body of<br />
plug, male pins & watertight parts.<br />
PROTECTION AGAINST WATER PENETRATION<br />
Carried out at four levels:<br />
1- Between watertight sheath and sealing ring (4) by a<br />
thermoretractable sheath (1).<br />
2- Between e plug and point by a a O-ring seal (11).<br />
3- Between phase conductor and phase contactor (6) by<br />
thermo retractable sheath (10).<br />
4- Extra insulation is provided by insulating liquid BIP<br />
inside the terminal compartment. It acts as a density dielectric<br />
allowing water to be kept on the surface, which<br />
might otherwise get into terminal in the event of cable<br />
damage.<br />
ELECTRICAL CHARACTERISTICS<br />
This terminal allows the transporting of maximum 80 A<br />
intensity.<br />
The three -pole terminal is designed with sufficient leak<br />
lines to keep to the 7.2 kV class and support all UTE tests<br />
planned.<br />
MECHANICAL CHARACTERISTICS<br />
The sealing ring lets in cables with maximum sheath diametre<br />
44.5 mm.<br />
CONNECTORS<br />
Made of brass with sheaths set in copper.<br />
THREE-POLE PLUG MODEL<br />
There are two types of three- pole plugs:<br />
1- a right three- pole plug, standard model<br />
2- An elbow -bent type three- pole plug (optional).<br />
This plug reduces the size of set and facilitates transformer<br />
installation. The design of the terminal allows greater<br />
latitude orientation.<br />
IMPORTANT<br />
Essential requirements to be communicated on order:<br />
Cable type<br />
Cable cross section<br />
Terminal model (right or elbow-bent)<br />
Supply of a cable sample, if it is specially designed.<br />
22