TEH TTT TECHNICAL DATA - 50, 63, 80, 100, 125, 160 kVA<br />

Power rating (kVA) 50 63 80 100 125 160<br />

Power output (kVA) 40 50.4 64 80 100 128<br />

Iron losses (W) 200 280 295 320 375 395<br />

Copper losses (W) 780 850 1080 1330 1700 2350<br />

Short-circuit impedance (%) 3.5 3.5 3.5 4 4 4<br />

Vector group Yzn11 Dyn11 Dyn11 Dyn11 Dyn11 Dyn11<br />

Magnetising current (%) 2.8 2.6 2.6 2.4 2.2 2.1<br />

Length (mm) 1042 1090 1090 1090 1122 1122<br />

Width (mm) 545 585 595 595 627 627<br />

Height (mm) 837 937 937 937 937 1037<br />

Total weight (kg) 650 770 805 845 970 1010<br />

Oil weight (kg) 110 150<br />

160 160 210 210<br />