TEH TTT - 50, 63, 80, 100, 125, 160 kVA<br />

TYPE<br />

Outdoor, watertight, metal tank specially treated against<br />

corrosion, buriable in a visible in concrete pit.<br />

Protection level : IP 68<br />

Primary voltage : 5500 V (1)<br />

Primary winding insulation : 7.2 kV<br />

Secondary no-load voltage : 410 V (2)<br />

Secondary winding insulation : 1.1 kV<br />

Vector group : 50 kVA : Yzn 11<br />

80 - 100 kVA : Dyn 11<br />

Dielectric : oil<br />

Rated power : 50 - 80 - 100 - 125 - 160 kVA<br />

Nominal power depending on public lighting standards :<br />

40 - 50.4 - 64 - 80 - 100 - 128 kVA<br />

The transformers conform to NFC 52 410 standards.<br />

CONDITIONS OF USE<br />

Environment class AD7 : can be partially or wholly<br />

immersed in water for limited time period.<br />

MV CONNECTION<br />

a- Right three p-hase, plug-in terminals with shield for<br />

three- phase, 6 kV, belt or radial field type cable (see<br />

leaflet ). 60 10472)<br />

Maximum current : 80 A<br />

Maximum cable diameter : 44,5 mm (maximum<br />

allowance included)<br />

Optional : bent plug-in terminals.<br />

b- «Lead-through» connection of the network to the<br />

Transformer.<br />

TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />

By switch, only to be operated off-load<br />

Off-load adjustment plugs : + 5, + 7,5 % (3)<br />

MV PROTECTION<br />

By three H.R.C. fuses with breaking capacity 15 kA<br />

(1) Other voltage values on request ; must be compatible with<br />

insulation level of primary winding (7,2 kV)<br />

(2) Other voltage values on request ; must be compatible with<br />

insulation level of secondary winding (1,1 kV)<br />

(3) Other percentages on request<br />

LV OUTPUT<br />

Four single-pole 6 metre-long H.07.RN.F cable<br />

50 - 63 - 80 kVA : 1 x 35 mm² cross section<br />

100 kVA : 1 x 50 mm² cross section<br />

125 kVA : 1 x 70 mm² cross section<br />

160 kVA : 1 x 70 mm² cross section<br />

LV PROTECTION<br />

Without low voltage protection. Three- thermal probes<br />

incorporated in the windings are opened on the H 07 RNF<br />

2 x 2,5 mm² cable and ensure thermal protection of<br />

equipment.<br />

LV ELECTRICAL POSITION<br />

LV neutral is connected to earth terminal inside the<br />

transformer.<br />

Optional : neutral not connected inside the transformer<br />

EARTH CONNECTION<br />

The rods are welded onto the cover and tank.<br />

DIELECTRIC TESTS<br />

Impulse withstand voltage : 60 kV - wave 1 / 50<br />

Power frequency withstand : 22 kV - 50 Hz - 1 minute<br />

USER INSTRUCTIONS WRITTEN<br />

CLEARLY ON COVER<br />

MV cable terminal assembly instructions :<br />

technical leaflets available on request, according to cable<br />

type.<br />

EQUIPMENTS<br />

The transformers are delivered with:<br />

Two HV preparation leaflets.<br />

Non-waterproof transport plugs.<br />

BIP delivered separately.<br />

Handling ropes.<br />

One technical leaflet for assembing MV plug-in<br />

terminals.<br />