TEH TTT - 50, 63, 80, 100, 125, 160 kVA<br />
TYPE<br />
Outdoor, watertight, metal tank specially treated against<br />
corrosion, buriable in a visible in concrete pit.<br />
Protection level : IP 68<br />
Primary voltage : 5500 V (1)<br />
Primary winding insulation : 7.2 kV<br />
Secondary no-load voltage : 410 V (2)<br />
Secondary winding insulation : 1.1 kV<br />
Vector group : 50 kVA : Yzn 11<br />
80 - 100 kVA : Dyn 11<br />
Dielectric : oil<br />
Rated power : 50 - 80 - 100 - 125 - 160 kVA<br />
Nominal power depending on public lighting standards :<br />
40 - 50.4 - 64 - 80 - 100 - 128 kVA<br />
The transformers conform to NFC 52 410 standards.<br />
CONDITIONS OF USE<br />
Environment class AD7 : can be partially or wholly<br />
immersed in water for limited time period.<br />
MV CONNECTION<br />
a- Right three p-hase, plug-in terminals with shield for<br />
three- phase, 6 kV, belt or radial field type cable (see<br />
leaflet ). 60 10472)<br />
Maximum current : 80 A<br />
Maximum cable diameter : 44,5 mm (maximum<br />
allowance included)<br />
Optional : bent plug-in terminals.<br />
b- «Lead-through» connection of the network to the<br />
Transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
By switch, only to be operated off-load<br />
Off-load adjustment plugs : + 5, + 7,5 % (3)<br />
MV PROTECTION<br />
By three H.R.C. fuses with breaking capacity 15 kA<br />
(1) Other voltage values on request ; must be compatible with<br />
insulation level of primary winding (7,2 kV)<br />
(2) Other voltage values on request ; must be compatible with<br />
insulation level of secondary winding (1,1 kV)<br />
(3) Other percentages on request<br />
LV OUTPUT<br />
Four single-pole 6 metre-long H.07.RN.F cable<br />
50 - 63 - 80 kVA : 1 x 35 mm² cross section<br />
100 kVA : 1 x 50 mm² cross section<br />
125 kVA : 1 x 70 mm² cross section<br />
160 kVA : 1 x 70 mm² cross section<br />
LV PROTECTION<br />
Without low voltage protection. Three- thermal probes<br />
incorporated in the windings are opened on the H 07 RNF<br />
2 x 2,5 mm² cable and ensure thermal protection of<br />
equipment.<br />
LV ELECTRICAL POSITION<br />
LV neutral is connected to earth terminal inside the<br />
transformer.<br />
Optional : neutral not connected inside the transformer<br />
EARTH CONNECTION<br />
The rods are welded onto the cover and tank.<br />
DIELECTRIC TESTS<br />
Impulse withstand voltage : 60 kV - wave 1 / 50<br />
Power frequency withstand : 22 kV - 50 Hz - 1 minute<br />
USER INSTRUCTIONS WRITTEN<br />
CLEARLY ON COVER<br />
MV cable terminal assembly instructions :<br />
technical leaflets available on request, according to cable<br />
type.<br />
EQUIPMENTS<br />
The transformers are delivered with:<br />
Two HV preparation leaflets.<br />
Non-waterproof transport plugs.<br />
BIP delivered separately.<br />
Handling ropes.<br />
One technical leaflet for assembing MV plug-in<br />
terminals.<br />