TED TTT - 5, 10, 16, 25, 32 kVA<br />

TYPE<br />

Three-phase transformer for three-phase networks. Caste in<br />

resin, corrosion resistant, water-tight, plugin connection<br />

designed for directly buried installation.<br />

Protection degree : IP 68<br />

Primary voltage : 5500 V (1)<br />

Primary winding insulation level : 7.2 kV<br />

Secondary no-load voltage : 410 V (2)<br />

Secondary winding insulation level : 1.1 kV<br />

Coupling : Yzn 11<br />

Dielectric : oil<br />

Power rating : 5 - 10 - 16 - 25 - 32 kVA<br />

Nominal power depending on public<br />

lighting standards : 4 - 8 - 12.8 - 20 - 25.6 kVA<br />

<strong>Transformers</strong> comply with NFC 52 410 standards.<br />

OPERATING CONDITIONS<br />

Environmental condition AD7 : can be partly or completely<br />

immersed in water for a limited time period.<br />

MV INLET<br />

a- Three-phase plug-in connection for three-phase cable,<br />

6 kV, belt or radial field type (see leaflet n°60 10471).<br />

Maximum current : 80 A<br />

Maximum overall cable diameter : 44.5 mm,<br />

maximum allowance included.<br />

On request : elbow bent terminals.<br />

b- «Lead-through» connection in transformer.<br />

TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />

Adjustment by strips off voltage, Taps + 5, + 7,5 % (3).<br />

MV PROTECTION<br />

By means of three HRC fuses, rupturing capacity 15 kA.<br />

(1) On request : other voltages compatible with primary<br />

winding insulation level.<br />

(2) On request: other voltagescompatible with secondary<br />

winding insulation level.<br />

(3) Other percentagevalueson request.<br />

LV OUTLET<br />

Five- pole 6 meter-long H.07.RN.F cable,<br />

5 - 10 kVA : cross-section 6 mm²<br />

16 kVA : cross-section 16 mm²<br />

25 - 32 kVA : cross-section 25 mm²<br />

On request : four-pole plug-in terminal for H.07.RN.F.<br />

cable with maximum overall diameter of 44.5 mm.<br />

LV PROTECTION<br />

Without low voltage protection.<br />

On request:<br />

The cut-out device ensures that direct magnetic<br />

protection and thermal protection by means of a probe<br />

incorporated in the windings, breaking capacity :<br />

10 kA.<br />

Protection by HRC fuse.<br />

LV POTENTIAL CONDITION<br />

LV neutral conductor is connected to the earthing<br />

terminal inside the transformer.<br />

On request : LV neutral conductor is not connected to<br />

earthing terminal inside the transformer.<br />

EARTHING TERMINAL<br />

By means of a M10 threaded rod, connected internally to<br />

the transformer.<br />

DIELECTRIC TESTS<br />

Impulse withstand : 60 kV - wave 1 / 50<br />

Power frequency withstand voltage : 22 kV - 50 Hz<br />

- 1 minute.<br />

USER INFORMATION WRITTEN ON COVER<br />

MV cable terminal assembly instructions :<br />

manual available on request for different cable types .<br />

EQUIPMENTS<br />

The transformers are delivered with :<br />

Two HV preparation leaflets.<br />

Two non-waterproof transport plugs.<br />

BIP delivered separately.<br />

Handling ropes.<br />

One technical leaflet for assembling MV plug-in<br />

terminals.<br />

18