TED TTT - 5, 10, 16, 25, 32 kVA<br />
TYPE<br />
Three-phase transformer for three-phase networks. Caste in<br />
resin, corrosion resistant, water-tight, plugin connection<br />
designed for directly buried installation.<br />
Protection degree : IP 68<br />
Primary voltage : 5500 V (1)<br />
Primary winding insulation level : 7.2 kV<br />
Secondary no-load voltage : 410 V (2)<br />
Secondary winding insulation level : 1.1 kV<br />
Coupling : Yzn 11<br />
Dielectric : oil<br />
Power rating : 5 - 10 - 16 - 25 - 32 kVA<br />
Nominal power depending on public<br />
lighting standards : 4 - 8 - 12.8 - 20 - 25.6 kVA<br />
<strong>Transformers</strong> comply with NFC 52 410 standards.<br />
OPERATING CONDITIONS<br />
Environmental condition AD7 : can be partly or completely<br />
immersed in water for a limited time period.<br />
MV INLET<br />
a- Three-phase plug-in connection for three-phase cable,<br />
6 kV, belt or radial field type (see leaflet n°60 10471).<br />
Maximum current : 80 A<br />
Maximum overall cable diameter : 44.5 mm,<br />
maximum allowance included.<br />
On request : elbow bent terminals.<br />
b- «Lead-through» connection in transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
Adjustment by strips off voltage, Taps + 5, + 7,5 % (3).<br />
MV PROTECTION<br />
By means of three HRC fuses, rupturing capacity 15 kA.<br />
(1) On request : other voltages compatible with primary<br />
winding insulation level.<br />
(2) On request: other voltagescompatible with secondary<br />
winding insulation level.<br />
(3) Other percentagevalueson request.<br />
LV OUTLET<br />
Five- pole 6 meter-long H.07.RN.F cable,<br />
5 - 10 kVA : cross-section 6 mm²<br />
16 kVA : cross-section 16 mm²<br />
25 - 32 kVA : cross-section 25 mm²<br />
On request : four-pole plug-in terminal for H.07.RN.F.<br />
cable with maximum overall diameter of 44.5 mm.<br />
LV PROTECTION<br />
Without low voltage protection.<br />
On request:<br />
The cut-out device ensures that direct magnetic<br />
protection and thermal protection by means of a probe<br />
incorporated in the windings, breaking capacity :<br />
10 kA.<br />
Protection by HRC fuse.<br />
LV POTENTIAL CONDITION<br />
LV neutral conductor is connected to the earthing<br />
terminal inside the transformer.<br />
On request : LV neutral conductor is not connected to<br />
earthing terminal inside the transformer.<br />
EARTHING TERMINAL<br />
By means of a M10 threaded rod, connected internally to<br />
the transformer.<br />
DIELECTRIC TESTS<br />
Impulse withstand : 60 kV - wave 1 / 50<br />
Power frequency withstand voltage : 22 kV - 50 Hz<br />
- 1 minute.<br />
USER INFORMATION WRITTEN ON COVER<br />
MV cable terminal assembly instructions :<br />
manual available on request for different cable types .<br />
EQUIPMENTS<br />
The transformers are delivered with :<br />
Two HV preparation leaflets.<br />
Two non-waterproof transport plugs.<br />
BIP delivered separately.<br />
Handling ropes.<br />
One technical leaflet for assembling MV plug-in<br />
terminals.<br />
18