TED MTT - 16, 25, 32, 50 kVA<br />
TYPE<br />
Single-phase transformer for three-phase networks. Cast in<br />
resin, corrosion resistant, water-tight, plug-in<br />
connection designed for directly buried installation.<br />
Protection degree : IP 68<br />
Primary voltage : 5500 V (1)<br />
Primary winding insulation level : 7.2 kV<br />
Secondary no-load voltage : 237 V (2)<br />
Secondary winding insulation level : 1.1 kV<br />
Coupling : single phase<br />
Delectric : oil<br />
Power rating : 16 - 25 - 32 - 50 kVA<br />
Nominal power depending on public<br />
lighting standards : 12.8 - 20 - 25.6 - 40 kVA<br />
<strong>Transformers</strong> comply with NFC 52410 standards.<br />
OPERATING CONDITIONS<br />
Environmental condition AD7: can be partly or completely<br />
immersed in water for a limited time period.<br />
MV INLET<br />
a- Three-phase plug-in connection for three-phase cable, 6<br />
kV, belt or radial field type (see leaflet 60 10472)<br />
Maximum current : 80 A<br />
Maximum overall cable diametre : 44.5 mm, maximum<br />
allowance included.<br />
On request : elbow bent terminals.<br />
b- «Lead-through» connection in transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
Adjustment by strips off voltage, taps + 5, + 7,5 % (3)<br />
MV PROTECTION<br />
By means of two HRC fuses, rupturing capacity 15 kA.<br />
PHASE SELECTOR<br />
By means of a switching device, allowing even load<br />
distribution among the three phases of supply network.<br />
(1) On request : other voltages compatible with primary winding<br />
insulation level.<br />
(2) On request : other voltages compatible with secondary<br />
winding insulation level.<br />
(3) Other percentage values on request.<br />
LV OUTLET<br />
Two-pole 6 meter-long H.07.RN.F cable<br />
16 kVA : cross-section 25 mm²<br />
Two single-pole 6 meter-long H.07.RN.F cable<br />
25 kVA : cross-section 50 mm²<br />
32 kVA : cross-section 50 mm²<br />
50 kVA : cross-section 95 mm²<br />
On request for the 16 kVA : two-pole plug-in terminal<br />
for H.07.RN.F cable with 25 mm² maximum cross-section.<br />
LV PROTECTION<br />
Without low voltage protection. On request, the cut-out<br />
device ensures direct magnetic protection and thermal<br />
protection by means of a probe incorporated in the<br />
windings (only for the 16 and 25 kVA).<br />
Breaking capacity : 16 kVA : 85 kA - 25 kVA : 85 kA<br />
Protection by HRC fuses.<br />
LV POTENTIAL CONDITION<br />
One end of the LV winding is connected to the earthing<br />
terminal (blue lead).<br />
On request: Centre tap of the LV winding connected to<br />
earthing terminal.<br />
EARTHING TERMINAL<br />
By means of a M10 threaded rod, connected internally to<br />
magnetic circuit.<br />
DIELECTRIC TESTS<br />
Impulse withstand : 60 kV - Wave 1 / 50<br />
Power frequency withstand voltage : 22 kV - 50 Hz -<br />
1 minute.<br />
USE INFORMATION WRITTEN ON COVER<br />
MV cable terminal assembly instructions :<br />
manual available on request for different cable types.<br />
EQUIPMENTS<br />
The transformers are delivered with:<br />
Two MV plug-in terminals for assembly.<br />
Two non-waterproof blanking off taps.<br />
BIP is delivered separately.<br />
Handling ropes.<br />
One technical leaflet for assembling MV plug-in<br />
terminals.<br />