TED MTT 2 to 10 kVA<br />
1- MV fuses and phase-selector<br />
2- MV three-pole terminal<br />
3- MV inlet<br />
4- MV outlet<br />
5- Rating plate<br />
6- Earthing terminal M 10 x 20<br />
7- LV protection (optional)<br />
8- LV output<br />
TED MTT TECHNICAL DATA - 2, 3, 5, 10 kVA<br />
Power rating (kVA) 2 3 5 10<br />
Power output (kVA) 1.6 2.4 4 8<br />
Iron losses (W) 30 45 60 110<br />
Copper losses (W) 38 45 75 130<br />
Short-circuit impedance (%) 2.5 2.5 2.5 3<br />
Voltage drop (%) cos φ = 1 1.91 1.52 1.52 1.34<br />
Voltage drop (%) cos φ = 0,8 2.49 2.4 2.4 2.66<br />
Magnetising current (%) 8.5 8 8 5<br />
Diameter (mm) Ø500 Ø500 Ø500 Ø500<br />
Height (mm) 485 485 485 485<br />
Total weight (kg) 100 110 115 170<br />
Weight of oil filling (kg) 20 18 14 23<br />
15