TYPE<br />

Single-phase transformer for three -phase networks. Cast<br />

in resin, corrosion resistant, water-tight, plug-in<br />

connection designed for directly buried installation.<br />

Protection degree : IP 68<br />

Primary voltage : 5500 V (1)<br />

Primary winding insulation level : 7.2 kV<br />

Secondary no-load voltage : 237 V (2)<br />

Secondary winding insulation level : 1.1 kV<br />

Coupling : single-phase<br />

Dielectric : oil<br />

Power rating : 2 - 3 - 5 - 10 kVA<br />

Nominal power depending on public lighting<br />

standards : 1.6 - 2.4 - 4 - 8 kVA<br />

<strong>Transformers</strong> comply with NFC 52410 standards.<br />

OPERATING CONDITIONS<br />

Environmental condition AD7: can be partly or completely<br />

immersed in water, for a limited time period.<br />

MV INLET<br />

a- Three-phase plug-in connection for three-phase cable,<br />

6 kV, belt or radial field type (see description 60 10472)<br />

Maximum current: 80 A<br />

Maximum overall diameter of cable: 44,5 mm, maximum<br />

allowance included.<br />

b- «Lead-through» connection in transformer.<br />

TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />

No voltage adjustment provided.<br />

MV PROTECTION<br />

By means of two HRC fuses, rupturing capacity 10 kA.<br />

PHASE SELECTOR<br />

Medium Voltage fuses allows even load distribution<br />

among the three- phases of supply network.<br />

(1) On request : other voltages compatible to the primary<br />

winding insulation level.<br />

(2) On request : other voltages compatible to the secondary<br />

winding insulation level.<br />

TED MTT - 2, 3, 5, 10 kVA<br />

LV OUTLET<br />

Two-pole 6 m. H.07 cable :<br />

2 to 5 kVA: cross-section 6 mm²<br />

10 kVA: cross-section 10 mm²<br />

On request: Two-pole plug-in terminal for H.07.RN.F<br />

cable with maximum cross-section 25 mm².<br />

LV PROTECTION<br />

Without Low Voltage protection<br />

On request:<br />

The cut-out device ensures direct magnetic and thermal<br />

protection by means of a probe incorporated in the<br />

windings, breaking capacity: 6 kA<br />

*single-pole + neutral, curve B, for TED ≤ 6 kVA:<br />

*two-pole, curve B for TED > 6 kVA<br />

By HRC fuses.<br />

LV ELECTRICAL POSITION<br />

The end of the LV winding is linked to earthing terminal<br />

(blue conductor).<br />

On request: Centre tap of LV winding connected to the<br />

earthing terminal. In this case, possible LV protection<br />

must be two-pole.<br />

EARTHING TERMINAL<br />

By means of a M10 threaded rod, connected internally to<br />

magnetic circuit.<br />

DIELECTRIC TESTS<br />

Impulse withstand: 60 kV - Wave shape 1 / 50<br />

Power frequency<br />

withstand voltage: 22 kV - 50 Hz -1 minute<br />

USER INFORMATION WRITTEN ON COVER<br />

MV cable terminal assembly instructions : manual<br />

available on request for different cable types.<br />

EQUIPMENTS<br />

<strong>Transformers</strong> are delivered with:<br />

Two MV plug-in terminals for assembly.<br />

Two non-waterproof transport only taps.<br />

BIP delivered separately.<br />

Handling ropes.<br />

One technical leaflet for assembling MV plug-in<br />

terminals.<br />