Network Transformers - Augier
Network Transformers - Augier
Network Transformers - Augier
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TYPE<br />
Single-phase transformer for three -phase networks. Cast<br />
in resin, corrosion resistant, water-tight, plug-in<br />
connection designed for directly buried installation.<br />
Protection degree : IP 68<br />
Primary voltage : 5500 V (1)<br />
Primary winding insulation level : 7.2 kV<br />
Secondary no-load voltage : 237 V (2)<br />
Secondary winding insulation level : 1.1 kV<br />
Coupling : single-phase<br />
Dielectric : oil<br />
Power rating : 2 - 3 - 5 - 10 kVA<br />
Nominal power depending on public lighting<br />
standards : 1.6 - 2.4 - 4 - 8 kVA<br />
<strong>Transformers</strong> comply with NFC 52410 standards.<br />
OPERATING CONDITIONS<br />
Environmental condition AD7: can be partly or completely<br />
immersed in water, for a limited time period.<br />
MV INLET<br />
a- Three-phase plug-in connection for three-phase cable,<br />
6 kV, belt or radial field type (see description 60 10472)<br />
Maximum current: 80 A<br />
Maximum overall diameter of cable: 44,5 mm, maximum<br />
allowance included.<br />
b- «Lead-through» connection in transformer.<br />
TAP CHANGER FOR VOLTAGE ADJUSTMENT<br />
No voltage adjustment provided.<br />
MV PROTECTION<br />
By means of two HRC fuses, rupturing capacity 10 kA.<br />
PHASE SELECTOR<br />
Medium Voltage fuses allows even load distribution<br />
among the three- phases of supply network.<br />
(1) On request : other voltages compatible to the primary<br />
winding insulation level.<br />
(2) On request : other voltages compatible to the secondary<br />
winding insulation level.<br />
TED MTT - 2, 3, 5, 10 kVA<br />
LV OUTLET<br />
Two-pole 6 m. H.07 cable :<br />
2 to 5 kVA: cross-section 6 mm²<br />
10 kVA: cross-section 10 mm²<br />
On request: Two-pole plug-in terminal for H.07.RN.F<br />
cable with maximum cross-section 25 mm².<br />
LV PROTECTION<br />
Without Low Voltage protection<br />
On request:<br />
The cut-out device ensures direct magnetic and thermal<br />
protection by means of a probe incorporated in the<br />
windings, breaking capacity: 6 kA<br />
*single-pole + neutral, curve B, for TED ≤ 6 kVA:<br />
*two-pole, curve B for TED > 6 kVA<br />
By HRC fuses.<br />
LV ELECTRICAL POSITION<br />
The end of the LV winding is linked to earthing terminal<br />
(blue conductor).<br />
On request: Centre tap of LV winding connected to the<br />
earthing terminal. In this case, possible LV protection<br />
must be two-pole.<br />
EARTHING TERMINAL<br />
By means of a M10 threaded rod, connected internally to<br />
magnetic circuit.<br />
DIELECTRIC TESTS<br />
Impulse withstand: 60 kV - Wave shape 1 / 50<br />
Power frequency<br />
withstand voltage: 22 kV - 50 Hz -1 minute<br />
USER INFORMATION WRITTEN ON COVER<br />
MV cable terminal assembly instructions : manual<br />
available on request for different cable types.<br />
EQUIPMENTS<br />
<strong>Transformers</strong> are delivered with:<br />
Two MV plug-in terminals for assembly.<br />
Two non-waterproof transport only taps.<br />
BIP delivered separately.<br />
Handling ropes.<br />
One technical leaflet for assembling MV plug-in<br />
terminals.<br />
14