GENERAL INFORMATION<br />
TWO-POLE TERMINAL MODEL X<br />
This terminal consists of two parts :<br />
a- the plug is joined to the device and contains a central and periphical contact. It is designed to receive all plugs<br />
from 6 to 25mm².<br />
b- the plug is on the cable. The parts ensuring electric contacts must be adapted to cable cross-section.<br />
PROTECTION AGAINST WATER PENETRATION<br />
This is carried out in two stages :<br />
Between the sheath (3) and the envelope with the help of an o-ring seal (4). Toughness: 70° shore, +/- 5°.<br />
Between the cable and the sheath (3) with the help of a thermo-retractable sheath.<br />
NB: extra insulation is provided using an insulating liquid BIP inside the terminal compartment. This liquid acts as<br />
a density dielectric, thus allowing water to be kept on surface; otherwise this would get inside the terminal in the<br />
event of cable damage.<br />
IMPORTANT<br />
Essential infomation to be given on order:<br />
• Type and section of cable.<br />
• Provide sample of cable if it’s a special type.<br />
Example of protected cable<br />
Copper core<br />
Semi-conductor<br />
PR insulation<br />
Waterproof concentric<br />
conductor<br />
Redinsulation shaft<br />
Cable protection<br />
Redexterior shaft<br />
Cable cross<br />
section<br />
(mm²)<br />
RECOMMENDED CABLE<br />
Two-pole concentric cable 3,6 / 6 kV<br />
Maximum<br />
diameter on<br />
the insulation<br />
(mm)<br />
Approximate diameter<br />
on the exterior sleeve (mm)<br />
Non<br />
protected cable<br />
Acceptable<br />
current (A)<br />
Protected cable Buried<br />
6 + 6 16 18.6 19.6 63<br />
10 + 10 16.5 19.2 20.2 90<br />
16 + 16 18.3 21 22 115<br />
25 + 25 20.5 23.2 24.2 150<br />
Curved ribbon : 10 x diameter<br />
12