uilt together and holiday homes. Apartment buildings are multi-storey block of flats. Industrial buildings and warehouses, and hospitals and health institutions, are self-explanatory. Office and enterprise buildings include e.g. hotels and congress buildings, shopping centres and military buildings. Culture and research buildings are defined as schools and other educational establishments, laboratories, museums, libraries, churches, indoor swimming pools, sports buildings, kindergartens, community centres and castles. Other types of buildings are e.g. prisons. Figure 3 presents an overview of building defects distributed by localisation of defects. Defects related to the building envelope constitute 66% of the investigated cases. Technical installations are here defined as e.g. electric, heating, cooling, ventilation and sanitation installations. Defects incurred to technical installations do not in any way reflect the actual level of defects to such installations in Norway. It rather expresses that this is an area of expertise in which the institute traditionally have had few assignments. The term “other building components and assemblies” are used to categorise elements not to be studied in this investigation, namely all elements not forming part of a buildings envelope (e.g. inner walls, stairs and other internal components). These cases should of course be subject to further inquiries, but then as part of research aiming at solving challenges in the pursuit of enhanced indoor quality in the built environment. In Figure 4 an overview of sources of defects is given. This investigation focuses on defects related to moisture, which reply for as much as 76% of all cases. In recent years, more attention has been paid to the negative implications moist materials have on indoor air quality and health. The link between dampness and health has been scientifically demonstrated by numerous epidemiological surveys. Such surveys have been summarised in a Nordic research project (Bornehag et al. 2001). The categorisation of defect sources is chosen to allow for a simple classification of the main impact responsible for the defect. This again enables fast registration, while at the same time providing an overall illustration of the cause of defects. A more thorough analysis of defect causes calls for in-depth studies of each assignment report. Precipitation, often in combination with wind, is a self-explanatory climatic impact. Indoor activity, humans, animals and plants produce indoor moisture. Built-in moisture is moisture in both materials and constructions. Defects related to water in soil are due to insufficient draining and circumstances related to the outside terrain. 9% of the cases are related to moisture in combination with other sources. These other sources are often reinforcement corrosion and sulphate attack. 24% of the investigated cases are not moisture related at all. Unkown 0 % Combination or others 3 % Insurance industry 3 % Building owners 58 % Material manufacturers and suppliers 5 % Building contractors 16 % Engineers and architects 9 % Lawyers 6 % Figure 1. Process induced building defect cases for the 10-year period 1993-2002 (a total of 2,423 building defect cases), distributed by type of client. Culture and research buildings (e.g. schools) 11 % Office and enterprise buildings 16 % Industrial buildings and warehouses 8 % Hospitals and health institutions 3 % Other types of buildings 1 % Apartment buildings (block of flats) 27 % Domestic buildings 34 % Figure 2. Process induced building defect cases for the 10-year period 1993-2002 (a total of 2,423 building defect cases), distributed by building type. Technical installations 3 % Other building components and assemblies (not related to the building enclosure) 31 % Slab-on-ground floors 8 % External walls under terrain 7 % Roofs 22 % External walls above terrain 29 % Figure 3. Process induced building defect cases for the 10-year period 1993-2002 (a total of 2,423 building defect cases), distributed by localization of defects. Damage source moisture in combination with other sources 9 % Other sources (not moisture related) 24 % Combination of moisture sources 9 % Leakage water (from e.g. sanitary installations) 5 % Water in soil 8 % Precipitation 24 % Built-in moisture 6 % Indoor moisture 15 % Figure 4. Process induced building defect cases for the 10-year period 1993-2002 (a total of 2,423 building defect cases), distributed by source of defects.

Concrete walls 32 % LECA masonry 10 % Other 3 % Brick cavity or veneer walls 17 % Timber framework 30 % Metal framework 7 % Sandwichelements 1 % Figure 5. Defect cases for the 10-year period 1993-2002 concerning external walls above terrain, distributed by type of wall (587 cases, 29% of the total amount of building defects). Other 6 % Element walls under terrain 7 % Concrete walls 66 % Brick walls 1 % LECA masonry 20 % Figure 6. Defect cases for the 10-year period 1993-2002 concerning external walls under terrain, distributed by type of wall (145 cases, 7% of the total amount of building defects). Pitched wooden roof with cold attic 12 % Raised wooden roof structure on a underlay of concrete or ligthweight concrete 2 % Insulated pitched wooden roof with combined wind barrier and sheathing (watertight breather membrane) 7 % Insulated pitched wooden roof with separate wind barrier and sheathing (venting (air gap) between wind barrier and sheathing) 7 % Other 11 % Pitched wooden roof with heated rooms in parts of the attic 14 % Insulated terrace with wooden floor joists 2 % Compact roof 19 % Terrace on concrete floors 26 % Figure 7. Defect cases for the 10-year period 1993-2002 concerning roofs, distributed by type of roof (465 cases, 22% of the total amount of building defects). In Figures 5–7 building defects concerning external walls above terrain (i.e. ground level), external walls under terrain and roofs respectively are broken down into distributions by type of structure. Only 30% of the building defect cases related to external walls above terrain is related to timber frame walls. The bulk of defects related to walls above terrain are found on walls made out of porous mineral building materials – with defects on rendered facades by far being the most common exterior surface problem. Approximately 20% of the building defects are reported within the first year, and about 48% of the defects are reported within 5 years after completion of the building (Fig. 8). No. of building defect cases 300 250 200 150 100 50 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 No. of years from completion until defects are being reported Figure 8. Process induced building defect cases for the 10-year period 1993-2002, distributed by number of years from completion until defects are being reported. A bulk of the defects is related to moisture, and many types of building defect cases are recurring items, which indicate a general lack of knowledge concerning fundamental principles of building physics. A wide range of classical problems has been recorded, as for example unfortunate design and use of materials, inaccurate craftsmanship, structure and composition of rendering layers and paint on porous, mineral building materials, inappropriate rendering layers on facade systems with rendering directly on thermal insulation, insufficient efforts to protect against precipitation and insufficient efforts to protect against moisture in general. These findings are supporting earlier investigations concluding that the construction industry is not able to learn from past experience and that the exchange of knowledge in construction projects is not satisfactory (e.g. Lisø et al. 2000). The building defects archive reveals serious deficiencies in the construction industry with regard to knowledge about correct design and construction of buildings in Norway. These findings are also supported by earlier case studies of building defect assignments carried out by the institute. Lisø et al. (2005c) present a review of typical problem areas associated with weather-protective flashing. A total of 175 assignment reports associated with defective or damaged flashing from the period 1963 - 2001 were analysed. The investigation clearly showed that certain faults and deficiencies are recurring items. Windowsill/weatherboard flashings comprised as much as 41% of the building defect cases associated with weather-protective flashing. Defects in connection with parapet flashing comprised 27% of all cases included in this investigation. With few exceptions, instances of flashing defects are located in Norway’s coastal areas. A review of the archives regarding process induced masonry defects showed that inappropriate

Concrete walls<br />

32 %<br />

LECA masonry<br />

10 %<br />

Other<br />

3 %<br />

Brick cavity or veneer<br />

walls<br />

17 %<br />

Timber framework<br />

30 %<br />

Metal framework<br />

7 %<br />

Sandwichelements<br />

1 %<br />

Figure 5. Defect cases for the 10-year period 1993-2002 concerning<br />

external walls above terrain, distributed by type of wall<br />

(587 cases, 29% of the total amount of building defects).<br />

Other<br />

6 %<br />

Element walls under<br />

terrain<br />

7 %<br />

Concrete walls<br />

66 %<br />

Brick walls<br />

1 %<br />

LECA masonry<br />

20 %<br />

Figure 6. Defect cases for the 10-year period 1993-2002 concerning<br />

external walls under terrain, distributed by type of wall<br />

(145 cases, 7% of the total amount of building defects).<br />

Pitched wooden roof with<br />

cold attic<br />

12 %<br />

Raised wooden roof structure<br />

on a underlay of concrete or<br />

ligthweight concrete<br />

2 %<br />

Insulated pitched wooden<br />

roof with combined wind<br />

barrier and sheathing<br />

(watertight breather<br />

membrane)<br />

7 %<br />

Insulated pitched wooden<br />

roof with separate wind<br />

barrier and sheathing<br />

(venting (air gap) between<br />

wind barrier and sheathing)<br />

7 %<br />

Other<br />

11 %<br />

Pitched wooden roof with<br />

heated rooms in parts of the<br />

attic<br />

14 %<br />

Insulated terrace with<br />

wooden floor joists<br />

2 %<br />

Compact roof<br />

19 %<br />

Terrace on concrete floors<br />

26 %<br />

Figure 7. Defect cases for the 10-year period 1993-2002 concerning<br />

roofs, distributed by type of roof (465 cases, 22% of<br />

the total amount of building defects).<br />

In Figures 5–7 building defects concerning external<br />

walls above terrain (i.e. ground level), external<br />

walls under terrain and roofs respectively are broken<br />

down into distributions by type of structure. Only<br />

30% of the building defect cases related to external<br />

walls above terrain is related to timber frame walls.<br />

The bulk of defects related to walls above terrain are<br />

found on walls made out of porous mineral building<br />

materials – with defects on rendered facades by far<br />

being the most common exterior surface problem.<br />

Approximately 20% of the building defects are<br />

reported within the first year, and about 48% of the<br />

defects are reported within 5 years after completion<br />

of the building (Fig. 8).<br />

No. of building defect cases<br />

300<br />

250<br />

200<br />

150<br />

100<br />

50<br />

0<br />

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30<br />

No. of years from completion until defects are being reported<br />

Figure 8. Process induced building defect cases for the 10-year<br />

period 1993-2002, distributed by number of years from completion<br />

until defects are being reported.<br />

A bulk of the defects is related to moisture, and<br />

many types of building defect cases are recurring<br />

items, which indicate a general lack of knowledge<br />

concerning fundamental principles of building physics.<br />

A wide range of classical problems has been recorded,<br />

as for example unfortunate design and use of<br />

materials, inaccurate craftsmanship, structure and<br />

composition of rendering layers and paint on porous,<br />

mineral building materials, inappropriate rendering<br />

layers on facade systems with rendering directly on<br />

thermal insulation, insufficient efforts to protect<br />

against precipitation and insufficient efforts to protect<br />

against moisture in general. These findings are<br />

supporting earlier investigations concluding that the<br />

construction industry is not able to learn from past<br />

experience and that the exchange of knowledge in<br />

construction projects is not satisfactory (e.g. <strong>Lisø</strong> et<br />

al. 2000).<br />

The building defects archive reveals serious deficiencies<br />

in the construction industry with regard to<br />

knowledge about correct design and construction of<br />

buildings in Norway. These findings are also supported<br />

by earlier case studies of building defect assignments<br />

carried out by the institute. <strong>Lisø</strong> et al.<br />

(2005c) present a review of typical problem areas associated<br />

with weather-protective flashing. A total of<br />

175 assignment reports associated with defective or<br />

damaged flashing from the period 1963 - 2001 were<br />

analysed. The investigation clearly showed that certain<br />

faults and deficiencies are recurring items. Windowsill/weatherboard<br />

flashings comprised as much<br />

as 41% of the building defect cases associated with<br />

weather-protective flashing. Defects in connection<br />

with parapet flashing comprised 27% of all cases included<br />

in this investigation. With few exceptions, instances<br />

of flashing defects are located in Norway’s<br />

coastal areas.<br />

A review of the archives regarding process induced<br />

masonry defects showed that inappropriate