10.04.2013 Views

Lisø PhD Dissertation Manuscript - NTNU

Lisø PhD Dissertation Manuscript - NTNU

Lisø PhD Dissertation Manuscript - NTNU

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Figure 7 Example showing the recommended construction of<br />

welted parapet £ashing<br />

the flashing (on the facade side) resulting in leakage<br />

behind the wind barrier. A recommended solution is<br />

shown in Figure 7. Fastening at the inward edge of<br />

the parapet must be positioned a minimum 150 mm<br />

above the roofing material in order to prevent<br />

leakage due to static water on the roof. This in turn<br />

necessitates a parapet that is not too low.<br />

When the turndown along the facade is finished off<br />

against the wall waist, rain striking the parapet is led<br />

directly in towards the facade. Depending on the<br />

facade material, this moistening can lead to staining<br />

and frost damage (Figure 8). Norwegian Standard<br />

3420 stipulates finishing off a minimum 20 mm away<br />

from the wall waist. Among other factors, the necessary<br />

distance from wall waist depends on the height,<br />

form and location of the building.<br />

The parapet should always have a minimum 1:5 slope<br />

inwards towards the roof surface. An inwards incline<br />

reduces the danger of ice and/or snow sliding off the<br />

parapet. In addition, the slope is an important safeguard<br />

against static water, snow and/or ice and<br />

thereby water pressure on joints in the parapet flashing.<br />

High-performance weather-protective £ashings<br />

Figure 8 Finishing-off of the parapet £ashing against the<br />

wall face has led to wetting/moistening of the facade with<br />

consequent organic growth. Source: Norwegian Building<br />

Research Institute,Oslo<br />

Wall £ashing details<br />

The junction between the roof and adjacent, upper<br />

outer wall is a vulnerable point. For wood frame<br />

walls, the transition must be designed by finishing<br />

the roofing underneath the wind-barrier layer<br />

within the wall (Figure 9a). Leaks can easily arise<br />

whenever the wind-barrier/roofing material overlap is<br />

missing, even when the flashing is installed as a rain<br />

shield. The most frequent cases of registered damage<br />

are for masonry and concrete walls. A typical fault is<br />

flashing not being inserted in the mortar joint<br />

(notch), or where the insertion joint has become so<br />

jagged and uneven that water can run in behind the<br />

flashing. In the case of cavity walls, one must always<br />

expect water penetration through the external face of<br />

the wall. Drainage water must therefore be drained<br />

away as shown in Figure 9b. Connection of flashing<br />

to concrete walls is shown in Figure 9c.<br />

Ridge and bevel ¢nishing<br />

The type of ridge flashing should be selected according<br />

to the type of roofing material and the local climatic<br />

Figure 9a Recommended design of roo¢ng against a wood<br />

frame wall<br />

49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!