Centrifugal Fans AT belt driven - Nicotra Gebhardt
Centrifugal Fans AT belt driven - Nicotra Gebhardt Centrifugal Fans AT belt driven - Nicotra Gebhardt
Description Sound 240 L Wfc6 = L Wfc4 + L Wer Explosion protection according to ATEX Belt Driven Centrifugal Fans / Description For a free discharge situation i.e. without duct connected the sound level will be lower because of an end reflection. This is specially true for low frequencies. For this case a correction may be applied to L Wfc4 of the first 3 octave bands as follows: ADH / AT / RDH / RZR f c 63 125 250 Hz 0160/-0280 L Wer -14 -9 -4 dB 0315/-0800 L Wer -9 -4 -2 dB 0900/-1600 L Wer -4 -1 0 dB Fans for use in explosive atmospheres must comply with EC Directive 94/9/EG (ATEX 95). Equipment in Group II (all applications except mining) is categorised in accordance with the required degree of safety for designated use in equipment categories 1, 2 and 3. Depending on suitability, a distinction is in addition made between G (gas, vapours) and D (dust). Harmonised European standards and national guidelines must be observed. Equipment in class 2 and 3 is not subject to compulsory specifications nor to type testing. The manufacturer declares conformity with the EC directive. For the standard designs of our fans, the following ignition sources are essentially to be considered: A Hot surfaces, e.g. due to heat of friction or seizure of a bearing or due to blockage of an impeller A Rubbing-, grinding- or beating sparks, e.g. as a result of contact of the impeller with stationary components A Sparks resulting from discharge of electrostatically loaded, non-conducting omponents, e.g. of plasticpanels, surfaces with strong layer thickness. Preconditions for operating: A In the proximity of the motor, the temperature limits -20 °C and +40 °C must not be exceeded. A The temperature limits of -20 °C und +60 °C for the flow medium must not be exceeded. If the temperature of the flow medium should exceed +60 °C on the pressure side, then the fan must be switched off! A The fans may only be employed with a horizontal shaft. A The fans are to be protected against the falling-in or sucking-in of foreign objects. Protection guards must be ordered separately as an accessories. A On the machine plate the max. permitted fan speed is indicated. A Fans for operation in ex-hazardous areas are marked as such on the machine plate and they are accompanied by an EU conformity declaration and with operation and maintenance instructions. The operation and maintenance instructions have strictly to be observed. The conformity is always related to the fan system supplied. If the fan is completed with motor and belt drive by the customer the conformity of this fan set has to be declared at new. Fans of the series ADH / AT / RDH in ATEX-Execution on request.
Description Operating limits RZR ATEX Belt Driven Centrifugal Fans / Description Permissible fan speed Permissible shaft power Permissible nominal motor power RZR 1/min kW kW 11-0200-2G 6513 4.7 5.5 12-0200-2G 6513 4.7 5.5 19-0200-2G 6513 4.7 5.5 11-0225-2G 5774 4.7 5.5 12-0225-2G 5774 4.7 5.5 19-0225-2G 5774 4.7 5.5 11-0250-2G 4620 4.7 5.5 12-0250-2G 4620 4.7 5.5 19-0250-2G 5076 4.7 5.5 11-0280-2G 4582 6.5 7.5 12-0280-2G 4582 6.5 7.5 19-0280-2G 4582 9.7 11 11-0315-2G 3793 6.5 7.5 12-0315-2G 3793 6.5 7.5 19-0315-2G 4113 9.7 11 11-0355-2G 3110 6.5 7.5 12-0355-2G 3110 6.5 7.5 19-0355-2G 3555 9.7 11 11-0400-2G 2552 6.5 7.5 12-0400-2G 2552 6.5 7.5 13-0400-2G 3145 16.4 18.5 18-0400-2G 2913 9.7 11 11-0450-2G 2111 6.5 7.5 12-0450-2G 2111 6.5 7.5 13-0450-2G 2922 21.3 24 18-0450-2G 2410 9.7 11 11-0500-2G 1752 6.5 7.5 12-0500-2G 1752 6.5 7.5 13-0500-2G 2534 21.3 24 18-0500-2G 2000 9.7 11 11-0560-2G 1660 9.7 11 12-0560-2G 1660 9.7 11 13-0560-2G 2163 26.6 30 18-0560-2G 1660 9.7 11 11-0630-2G 1367 9.7 11 12-0630-2G 1367 9.7 11 13-0630-2G 2055 32.8 37 18-0630-2G 1367 9.7 11 11-0710-2G 1128 9.7 11 12-0710-2G 1128 9.7 11 13-0710-2G 1825 40.9 45 18-0710-2G 1128 9.7 11 11-0800-2G 927 9.7 11 18-0800-2G 927 9.7 11 13-0800-2G 1474 40.9 45 11-0900-2G 767 9.7 11 18-0900-2G 767 9.7 11 13-0900-2G 1339 68 75 11-0100-2G 650 9.7 11 18-1000-2G 650 9.7 11 13-1000-2G 1217 68 75 13-1120-2G 1026 83.6 92 13-1250-2G 957 122 135 13-1400-2G 870 145 160 13-1600-2G 748 181 200 241
- Page 53 and 54: AT G2C Dimensions in mm, subject to
- Page 55 and 56: Notes Notes Belt Driven Centrifugal
- Page 57 and 58: AT SC 7/7-18/18 AT C 7/7-18/18 Spec
- Page 59 and 60: AT TIC 20/15-30/28 Specifications F
- Page 61 and 62: AT SC2 7/7-18/18 Specifications Fan
- Page 63 and 64: AT SC2 7/7-18/18 Specifications Fan
- Page 65 and 66: Gebhardt fan systems - the "complet
- Page 67 and 68: Fittings / Accessories Corrosion Pr
- Page 69 and 70: Fittings / Accessories Volumeter p
- Page 71 and 72: Fittings / Accessories Anti Vibrati
- Page 73 and 74: Fan Sets Base Frame with Belt Tensi
- Page 75 and 76: RZR 11-0200/-0500 Fan set arrangeme
- Page 77 and 78: RZR 12-0200/-0710 Fan set arrangeme
- Page 79 and 80: RZR 13-0400/-1000 RZR 18-0400/-1000
- Page 81 and 82: AT 7/7-18/18 Fan set arrangement wi
- Page 83 and 84: RZR 12-0200/-0710 Fan set arrangeme
- Page 85 and 86: RZR 13-0400/-1000 RZR 18-0400/-1000
- Page 87 and 88: Fan Sets Min. Pulley-Diameter, Bear
- Page 89 and 90: Fan Sets Belt Driven Centrifugal Fa
- Page 91 and 92: Fan Sets Min. recommended Pulley Di
- Page 93 and 94: Description Bearings ADH / AT / RDH
- Page 95 and 96: Description Motors Attachment point
- Page 97 and 98: Description Operating limits ADH Pe
- Page 99 and 100: Description Operating limits RDH Pe
- Page 101 and 102: Description Performance p sF = p F
- Page 103: Description Sound 1 = Air permeable
- Page 107 and 108: Notes Quality management system Mac
Description<br />
Sound<br />
240<br />
L Wfc6 = L Wfc4 + L Wer<br />
Explosion protection according to <strong>AT</strong>EX<br />
Belt Driven <strong>Centrifugal</strong> <strong>Fans</strong> / Description<br />
For a free discharge situation i.e. without duct connected the sound level will be lower<br />
because of an end reflection.<br />
This is specially true for low frequencies. For this case a correction may be applied to<br />
L Wfc4 of the first 3 octave bands as follows:<br />
ADH / <strong>AT</strong> / RDH / RZR f c 63 125 250 Hz<br />
0160/-0280 L Wer -14 -9 -4 dB<br />
0315/-0800 L Wer -9 -4 -2 dB<br />
0900/-1600 L Wer -4 -1 0 dB<br />
<strong>Fans</strong> for use in explosive atmospheres must comply with EC Directive 94/9/EG<br />
(<strong>AT</strong>EX 95). Equipment in Group II (all applications except mining) is categorised in<br />
accordance with the required degree of safety for designated use in equipment categories<br />
1, 2 and 3. Depending on suitability, a distinction is in addition made between<br />
G (gas, vapours) and D (dust).<br />
Harmonised European standards and national guidelines must be observed. Equipment<br />
in class 2 and 3 is not subject to compulsory specifications nor to type testing.<br />
The manufacturer declares conformity with the EC directive.<br />
For the standard designs of our fans, the following ignition sources are essentially<br />
to be considered:<br />
A Hot surfaces, e.g. due to heat of friction or seizure of a bearing or due to blockage<br />
of an impeller<br />
A Rubbing-, grinding- or beating sparks, e.g. as a result of contact of the impeller with<br />
stationary components<br />
A Sparks resulting from discharge of electrostatically loaded, non-conducting omponents,<br />
e.g. of plasticpanels, surfaces with strong layer thickness.<br />
Preconditions for operating:<br />
A In the proximity of the motor, the temperature limits -20 °C and +40 °C must<br />
not be exceeded.<br />
A The temperature limits of -20 °C und +60 °C for the flow medium must not<br />
be exceeded. If the temperature of the flow medium should exceed +60 °C<br />
on the pressure side, then the fan must be switched off!<br />
A The fans may only be employed with a horizontal shaft.<br />
A The fans are to be protected against the falling-in or sucking-in of foreign<br />
objects. Protection guards must be ordered separately as an accessories.<br />
A On the machine plate the max. permitted fan speed is indicated.<br />
A <strong>Fans</strong> for operation in ex-hazardous areas are marked as such on the machine<br />
plate and they are accompanied by an EU conformity declaration and<br />
with operation and maintenance instructions.<br />
The operation and maintenance instructions have strictly to be observed.<br />
The conformity is always related to the fan system supplied.<br />
If the fan is completed with motor and <strong>belt</strong> drive by the customer the conformity of<br />
this fan set has to be declared at new.<br />
<strong>Fans</strong> of the series ADH / <strong>AT</strong> / RDH in <strong>AT</strong>EX-Execution on request.