10.04.2013 Views

Centrifugal Fans direct driven with scroll - Nicotra Gebhardt

Centrifugal Fans direct driven with scroll - Nicotra Gebhardt

Centrifugal Fans direct driven with scroll - Nicotra Gebhardt

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Motor protection unit<br />

Motor protection unit EUM 33<br />

424<br />

Direct <strong>driven</strong> centrifugal fans / Appendix / Accessories<br />

Motor protection unit for three-phase current motors (standard motors) <strong>with</strong>out thermal<br />

contacts.<br />

Design<br />

Plastic casing in protection class IP55, permissible ambient temperature +40°C, 40Hz<br />

up to 60Hz, frontal operation, for wall mounting. Motor protection unit for singlespeed,<br />

non-variable speed three-phase current motors <strong>with</strong>out thermal contacts.<br />

Function<br />

The motor protection units must be adjusted on site to the trigger current. If the<br />

preset trigger current is exceeded, the device disconnects the motor from the mains<br />

supply via a thermal overload release. Pressing the “on key” causes the unit to turn on<br />

again.<br />

All motor protection units EUM33 are also suitable for the protection of EExe-motors<br />

(PTB-Prüfung Gesch-Nr. 3.35/386.3060). They must however be mounted outside of<br />

explosion endangered areas, since they are not themselves designed <strong>with</strong> explosion<br />

protection.<br />

Technical Data<br />

EUM 33- Continuous current Setting range Max. nominal power<br />

A A kW<br />

0004-8D 0.4 +0.2/+0.4 0.09<br />

0006-8D 0.6 +0.4/+0.6 0.12<br />

0010-8D 1 +0.6/+1 0.25<br />

0016-8D 1.6 +1/+1.6 0.55<br />

0024-8D 2.4 +1.6/+2.4 0.8<br />

0040-8D 4 +2.4/+4 1.5<br />

0060-8D 6 +4/+6 2.5<br />

0100-8D 10 +6/+10 4<br />

0160-8D 16 +10/+16 7.5<br />

0200-8D 20 +16/+20 9<br />

0250-8D 25 +20/+25 12.5<br />

0500-8D 50 +25/+50 25<br />

0580-8D 58 +50/+58 30<br />

Dimensions in mm, subject to change.<br />

Wiring Diagram<br />

L1<br />

L2<br />

L3<br />

PE<br />

97<br />

160<br />

1 3 5<br />

2 4 6<br />

U1 V1 W1<br />

181<br />

47.5<br />

EUM33<br />

114<br />

130