T06-745.2.340-300<br />
Description<br />
300<br />
257<br />
Technical Data<br />
220<br />
110<br />
146<br />
f<br />
167<br />
Nominal<br />
Ambient<br />
Nominal voltage frequency Nominal current Nominal power Output current temperature Power losses<br />
V Hz A kW A °C W<br />
T06-745.2.340-300 400 3~ 50/60 6.7 4 6.7 -10...+40 160<br />
Cable-cross section<br />
Min. cablecross section recommended cablecross section Min. cablecross section recommended fusing in panel<br />
for motor leads<br />
for hall sensor leads<br />
for mains leads<br />
for mains leads<br />
mm² mm² mm² A<br />
T06-745.2.340-300 1.5 0.75 1 10<br />
Anschlussplan<br />
1 Start enable (START-STOP)<br />
2 Reset<br />
3 Direction (Left, Right)<br />
M1 M2 M3 M4 M5 M6<br />
19 20 21 22 23 24<br />
Brushless<br />
DC-Motor<br />
Direct <strong>driven</strong> centrifugal fans / RZP / Control electronics<br />
The <strong>Nicotra</strong> <strong>Gebhardt</strong> control electronic has a painted metal housing and is suitable<br />
for mounting in control units. The Unit must only be mounted and operated in a dry,<br />
dust free area. Minimum spacings are to be maintained when mounting (see Operating<br />
Instructions). The permitted ambient temperature amounts to +40 °C.<br />
EMI filter and line choke are integrated in the controller in accordance <strong>with</strong> the requirements<br />
of the EMC Guideline 89/336/EWG.<br />
Function<br />
Speed control through an external 0...10 V input signal or through an incorporated<br />
potentiometer<br />
On/Off switching and an adjustable speed reduction facility through potential free<br />
contacts<br />
Speed reporting through an analogue 0...10 V output or a digital output<br />
Fault and operating indication through built in LEDs and a reporting relay<br />
Extensive monitoring and protection functions for motor current, phase failure and<br />
overcurrent<br />
7<br />
E +10 RF +15Reset +24V LEFT<br />
PI 40mARIGHT<br />
DD DS<br />
8 9 10 11 12 13 14 15 16 17 18<br />
1 2 3<br />
L1 L2 L3<br />
PE<br />
Line<br />
L1 L2 L3<br />
3~ / 400 V, 50/60 Hz<br />
25 26 27 28 29 30<br />
Re1 Re2<br />
on site fuses