Fittings / Accessories<br />

Volumeter<br />

p in<br />

p in<br />

2<br />

qV = K × —<br />

<br />

× pDü Direct <strong>driven</strong> centrifugal fans / RZA / Accessories<br />

With the flow measuring device it is possible to easilymeasure / monitor the flow rate<br />

after the fan is installed. A pressure tapping at a predetermined position on the inlet<br />

cone is provided whereby the differential pressure in relation to the static pressure is<br />

measured in front ofthe inlet cone in a static atmosphere.<br />

• volume flow qV<br />

[m³/h]<br />

• calibration factor K [m²s/h]<br />

• density of media r [kg/m³]<br />

• pressure difference at cone DpDü [Pa]<br />

In order to calculate the flow rate, a calibrating factor "K" is required. This factor is<br />

determined by comparativemeasurement on a standard test rig.<br />

•<br />

•<br />

•<br />

Measuring connector in inlet cone<br />

Hose pipe to connecting piece in the side wall<br />

Connecting piece (external diameter of 6mm) for the pressure measurement<br />

Standard-calibration faktor K10