E47076<br />

Electrical diagrams<br />

Remote-operated<br />

source-<strong>changeover</strong> <strong>systems</strong><br />

3 Masterpact NW devices<br />

Diagram no. 51156910<br />

3 sources with only 1 device closed: electrical interlocking without lockout after a fault<br />

SOURCE 1<br />

SOURCE 2<br />

SOURCE 3 Auxiliary<br />

power supply<br />

QS1<br />

QS2<br />

QS3<br />

B3<br />

B2<br />

CH<br />

MCH<br />

B1<br />

MX<br />

C2<br />

C1<br />

XF<br />

12<br />

14<br />

22<br />

24<br />

32<br />

34<br />

42<br />

44<br />

312<br />

314<br />

322<br />

324<br />

Legends<br />

QS... “<strong>Source</strong>” Masterpact NW<br />

MCH spring-charging motor<br />

MX standard opening voltage release<br />

XF standard closing voltage release<br />

OF... breaker ON/OFF indication contact<br />

PF “ready-to-close” contact<br />

CE... “connected-position” indication contact (carriage switch)<br />

CH “springs charged” indication contact<br />

F1 auxiliary power supply <strong>circuit</strong> breaker<br />

t1 order <strong>for</strong> transfer to “<strong>Source</strong> 1”<br />

(QS1 closing time delay = 0.25 sec. minimum)<br />

t2 order <strong>for</strong> transfer to “<strong>Source</strong> 2”<br />

(QS2 closing time delay = 0.25 sec. minimum)<br />

t3 order <strong>for</strong> transfer to “<strong>Source</strong> 3”<br />

(QS3 closing time delay = 0.25 sec. minimum)<br />

t1<br />

A2<br />

A1<br />

252<br />

254<br />

PF<br />

251<br />

OF1<br />

11<br />

OF2<br />

21<br />

OF3<br />

31<br />

OF4<br />

F1<br />

CE1 CE2<br />

41<br />

311<br />

321<br />

CN1 . CN1 +<br />

CN2 . CN2<br />

B3<br />

B2<br />

CH<br />

MCH<br />

B1<br />

MX<br />

C2<br />

C1<br />

XF<br />

t2<br />

A2<br />

A1<br />

252<br />

254<br />

PF<br />

251<br />

12<br />

14<br />

22<br />

24<br />

32<br />

34<br />

42<br />

44<br />

312<br />

OF1 OF2 OF3 OF4<br />

States permitted by mechanical interlocking system<br />

<strong>Source</strong> 1 <strong>Source</strong> 2 <strong>Source</strong> 3<br />

0 0 0<br />

1 0 0<br />

0 1 0<br />

0 0 1<br />

82<br />

Schneider Electric<br />

see your best prices of Merlin Gerin Circuit Breakers, Automatic Transfer Switches and other products at www.cyberallgroup.com/SchneiderElectric<br />

11<br />

21<br />

31<br />

41<br />

CE1<br />

314<br />

311<br />

322<br />

324<br />

CE2<br />

321<br />

B3<br />

B2<br />

CH<br />

MCH<br />

B1<br />

MX<br />

C2<br />

C1<br />

XF<br />

A2<br />

A1<br />

t3<br />

252<br />

254<br />

PF<br />

251<br />

12<br />

14<br />

22<br />

24<br />

32<br />

34<br />

42<br />

44<br />

312<br />

OF1 OF2 OF3 OF4<br />

11<br />

21<br />

31<br />

314<br />

322<br />

324<br />

CE1 CE2<br />

Note:<br />

Diagram shown with <strong>circuit</strong> <strong>breakers</strong> in connected position,<br />

open, charge.<br />

Auxiliary power supply = supply voltage of auxiliary relays<br />

(KA...) = supply voltage of electrical auxiliaries (MCH, MX,<br />

MN...)<br />

41<br />

311<br />

321