MINEX - Driescher • Wegberg
MINEX - Driescher • Wegberg
MINEX - Driescher • Wegberg
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
L1 L2 L3<br />
■ Individual cubicle design<br />
■ High short circuit capacity<br />
■ Maximum possible active and passive<br />
safety due to<br />
■ Connection of the cubicles via solid<br />
matter insulated coupling parts<br />
■ Switchgear extension possible at site<br />
■ Modular system allows unlimited<br />
assembly possibilities<br />
■ Rated current 630 A<br />
<strong>MINEX</strong> ® -E and <strong>MINEX</strong> ® -F.<br />
The slim-line modular system.<br />
Unlimited assembling.<br />
DRIESCHER SF6-insulated<br />
medium voltage switchgear<br />
in individual cubicle design,<br />
Rated voltage 12 - 36 kV.
<strong>MINEX</strong> ® -F with solid insulated<br />
bus bar system.<br />
1876<br />
1700 176<br />
Dimension sample of a <strong>MINEX</strong> ® -F assembly<br />
1380 plus 2 x 10 mm covering of the ABS ® 10 -coupling 10<br />
440 440<br />
cable<br />
cubicle<br />
transformer<br />
cubicle<br />
500<br />
circuit breaker<br />
cubicle<br />
Modular cubicle by cubicle.<br />
Possible due to coupling<br />
system.<br />
End-adapter<br />
bus bar<br />
cross-adapter<br />
The cones for the cable connection or switchgear extension<br />
are made of reinforced cycloalyphatic exposy<br />
resin. An electrode for capacitive coupling is embedded<br />
in the epoxy resin, arranged<br />
in parallel to the live part of the<br />
bushing. By using high-quality<br />
exposy resins and latest castiron<br />
technology, a maximum<br />
possible safety is guaranteed regarding<br />
the insulation strength of<br />
the dielectric and the protection<br />
against accidental contacts.
<strong>MINEX</strong> ® -E with shielded internal<br />
cone clutch.<br />
Maximum power on<br />
minimum space.<br />
The <strong>MINEX</strong> ® -E and <strong>MINEX</strong> ® -F switchgear<br />
in individual cubicle design are particularly<br />
suitable in confined space conditions,<br />
such as wind turbines. They fit in normal<br />
door widths and they are easily moveable<br />
in extremely transport situations.<br />
Print resource: Wucher Helicopter/Huber-Images<br />
1900<br />
Easy assembly<br />
and compact.<br />
The flexible modular system was<br />
designed for all requirements<br />
in the industry and the electrical<br />
power supply. Any required<br />
arrangement of cable-, transformer-<br />
and circuit breaker cubicles<br />
is possible.<br />
406 406 466<br />
cable<br />
cubicle<br />
transformer<br />
cubicle<br />
circuit breaker<br />
cubicle
The technology of the first inventor of the<br />
SF6-medium voltage switchgear.<br />
<strong>MINEX</strong> ® 1978 <strong>MINEX</strong> ® today<br />
There can be only one original:<br />
DRIESCHER SF 6-technology since 1978.<br />
In the matter of<br />
SF 6-medium voltage<br />
technology trust in<br />
the qualification of<br />
the inventor. Since<br />
1978 DRIESCHER<br />
constantly develops<br />
further in SF6-<br />
technology.<br />
SF6 as insulating and<br />
quenching medium<br />
The quenching arc takes place in<br />
separate, hermetically sealed arcing<br />
chambers. That means the quenching<br />
medium and the insulating<br />
medium are arranged in separate<br />
sections, independent from each<br />
other. The full switching capacity is<br />
always guaranteed.
Unlimited fields of application by<br />
IAC-classified metering cubicles (20 kA / 1 s).<br />
12 kV-metering cubicle<br />
Metering cubicle with secondary protection<br />
According to drawing no.<br />
K61644<br />
W 742 mm x D 745 mm x H 1700 mm<br />
742 745 742 745<br />
12 kV-metering cubicle<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
K61669<br />
W 742 mm x D 730 mm x H 1700 mm<br />
742 730<br />
12 kV-metering cubicle<br />
Metering cubicle with relay box<br />
According to drawing no.<br />
K61444<br />
W 742 mm x D 730 mm x H 1700 mm<br />
742 730<br />
12 kV-metering cubicle<br />
Metering cubicle with secondary protection<br />
According to drawing no.<br />
K61649<br />
W 742 mm x D 745 mm x H 1300 mm<br />
12 kV-metering cubicle<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
K61667<br />
W 742 mm x D 730 mm x H 1300 mm<br />
742 730<br />
12 kV-metering cubicle<br />
Metering cubicle with relay box<br />
According to drawing no.<br />
K61665<br />
W 742 mm x D 730 mm x H 1300 mm<br />
742 730<br />
Arrangement of current transformers individual possible.<br />
24 kV-metering cubicle<br />
Metering cubicle with secondary protection<br />
According to drawing no.<br />
K61654<br />
W 942 mm x D 745 mm x H 1700 mm<br />
942<br />
942 745<br />
24 kV-metering cubicle<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
K61666<br />
W 942 mm x D 730 mm x H 1700 mm<br />
942 730<br />
36 kV-metering cubicle<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
K62167<br />
W 942 mm x D 1230 mm x H 1700 mm<br />
Front view without door<br />
24 kV-metering cubicle<br />
Metering cubicle with secondary protection<br />
According to drawing no.<br />
K61648<br />
W 942 mm x D 745 mm x H 1300 mm<br />
942 745<br />
24 kV-metering cubicle<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
K61668<br />
W 942 mm x D 730 mm x H 1300 mm<br />
942<br />
650<br />
730<br />
12 metering cubicle (K1824)<br />
Metering cubicle without secondary protection<br />
According to drawing no.<br />
HK56081–002<br />
W 650 mm x D 857 mm x H 1180 mm<br />
Front view without door
Combination possibilities with solid insulated<br />
bus bar system make nkt.<br />
1876<br />
1700 176<br />
1876<br />
176<br />
1700<br />
1876<br />
1700 176<br />
Side view cable cubicle Cable cubicle-cable cubicle<br />
Cable cubicle-transformer cubicle<br />
bus bar length 426 mm<br />
bus bar length 426 mm<br />
570<br />
855<br />
880<br />
300 a = 440<br />
440 440 440 440<br />
Side view transformer cubicle Transformer cubicle-cable cubicle<br />
Transformer cubicle-transformer cubicle<br />
bus bar length 426 mm<br />
bus bar length 426 mm<br />
36 kV = 870<br />
24 kV = 575<br />
880<br />
300 a = 440<br />
440 440<br />
140 300<br />
880<br />
a = 440<br />
140<br />
880<br />
300 a = 440<br />
440 440<br />
Cable cubicle-circuit breaker cubicle<br />
bus bar length 506 mm<br />
140 300<br />
940<br />
a = 520<br />
440 500<br />
Transformer cubicle-circuit breaker cubicle<br />
bus bar length 506 mm<br />
940<br />
300 a = 520 120<br />
440 500<br />
Side view circuit breaker cubicle Circuit breaker cubicle-cable cubicle<br />
Circuit breaker cubicle-transformer cubicle Circuit breaker cubicle-circuit breaker cubicle<br />
bus bar length 406 mm<br />
bus bar length 406 mm<br />
bus bar length 486 mm<br />
940<br />
940<br />
1000<br />
380 a = 420 140 380 a = 420 140 380 a = 500 120<br />
952<br />
570<br />
495<br />
a = actual dimension of the external cone connections<br />
s = bus bar length = a - 14 mm<br />
500 440 500 440 500 500<br />
140<br />
120
Switchgear Data<br />
Cubicle type cubicle width<br />
(mm)<br />
cable cubicle<br />
≤ 36 kV<br />
cable cubicle<br />
≤ 36 kV<br />
transformer cubicle<br />
≤ 24 kV<br />
transformer cubicle<br />
≤ 36 kV<br />
transformer cubicle<br />
≤ 36 kV<br />
circuit breaker cubicle<br />
≤ 36 kV<br />
circuit breaker cubicle<br />
≤ 36 kV<br />
vacuum safety switch cubicle<br />
≤ 24 kV<br />
Technical Data<br />
cubicle depth<br />
(mm)<br />
cubicle height<br />
(mm)<br />
weight<br />
(kg)<br />
Connection via<br />
straight connector | elbow connector | inside cone<br />
<strong>MINEX</strong> ® -F 440 570 1876 ca. 130 <strong>•</strong><br />
<strong>MINEX</strong> ® -E 406 720 1900 ca. 160 <strong>•</strong><br />
<strong>MINEX</strong> ® -F 440 575 1876 ca. 200 <strong>•</strong><br />
<strong>MINEX</strong> ® -F 440 870 1876 ca. 210 <strong>•</strong><br />
<strong>MINEX</strong> ® -E 406 870 1900 ca. 240 <strong>•</strong><br />
<strong>MINEX</strong> ® -F 500 952 1876 ca. 280 <strong>•</strong><br />
<strong>MINEX</strong> ® -E 466 952 1900 ca. 280 <strong>•</strong><br />
<strong>MINEX</strong> ® -F 440 777 1876 ca. 150 <strong>•</strong> <strong>•</strong><br />
Cable cubicle / transformer cubicle Circuit breaker cubicle VSS<br />
Rated voltage ≤ 12 kV ≤ 24 kV ≤ 36 kV ≤ 12 kV ≤ 24 kV ≤ 36 kV ≤ 12 kV ≤ 24 kV<br />
Rated power frequency withstand voltage 28 kV 50 kV 70 kV 28 kV 50 kV 70 kV 28 kV 50 kV<br />
Rated lightning impulse withstand voltage 75 kV 125 kV 170 kV 75 kV 125 kV 170 kV 75 kV 125 kV<br />
Rated frequency 50 / 60 Hz<br />
Rated operating current of bus bar 630 A<br />
Rated operating current 630 / 200 A 630 / 200 A 630 / 200 A 630 A 630 A 630 A 630 A 630 A<br />
Rated short time current 20 kA (25 kA option)<br />
Rated peak current 50 kA (63 kA option)<br />
Rated short-circuit duration 1 s (3 s option)<br />
Rated short-circuit making current 50 kA (63 kA) 50 kA 50 kA 50 kA (63 kA) 50 kA 50 kA 63 kA 50 kA<br />
Rated short-circuit breaking current 20 kA (25 kA) 20 kA 20 kA 25 kA 20 kA<br />
Rated mainly active load breaking current 630 A 630 A 630 A<br />
Rated closed loop breaking current 630 A 630 A 630 A<br />
Rated cable charging breaking current 25 A 25 A 20 A 50 A 50 A 50 A 50 A 50 A<br />
Rated overhead line breaking current 10 A 10 A 6 A 10 A 10 A 10 A 10 A 10 A<br />
Rated overhead line breaking current<br />
under earth-fault conditions<br />
300 A 300 A 300 A<br />
Rated operation sequence O-0,3 s-CO-15 s-CO<br />
Internal Arc Classification IAC AFLR 20 kA 1 s (IAC AFLR 25 kA / 1 s option)<br />
Ambient temperature -25 °C bis +60 °C
Often imitated but never equalled!<br />
The optimum of safety.<br />
Duration of internal fault<br />
1000ms<br />
With conventional<br />
burst disc<br />
In spite of passed internal<br />
arc test according to<br />
IEC 62271-200<br />
Risk for persons nearby<br />
the installation by toxic<br />
flue gas<br />
Material damages, reconstruction<br />
of building trough<br />
High pressure increase<br />
We reserve the right to alter the dimensions<br />
and technical information.<br />
Please contact us for more details.<br />
© <strong>Driescher</strong>-<strong>Wegberg</strong><br />
With<br />
Duration of internal fault<br />
30ms<br />
considerably better as<br />
the standard requires<br />
No injury to persons<br />
No material damages<br />
No pressure increase to<br />
the station walls in case<br />
of an arc fault inside the<br />
gas compartment<br />
The reaction time<br />
makes the<br />
difference!<br />
The advantages of switchgear with<br />
ABS ® -system are the quick transformation<br />
of the arc fault into a galvanical<br />
short circuit.<br />
The reaction time is making the difference,<br />
because only few milliseconds<br />
decide on the effects of an internal<br />
arc in the installation.<br />
The DRIESCHER-ABS ® technique<br />
has been proved for more than 25<br />
years regarding safety and reliability.<br />
In case of an<br />
internal arc the<br />
preloaded<br />
earthing switch<br />
will be switched<br />
on via an<br />
integrated<br />
pressure sensor<br />
in the wall of the<br />
tank, in a time<br />
of 30 ms up to<br />
100 ms due to<br />
the current level.<br />
Fritz <strong>Driescher</strong> KG Spezialfabrik für Elektrizitätswerksbedarf GmbH & Co.<br />
Postfach 1193 · D-41837 <strong>Wegberg</strong> · Industriestr. 2 · D-41844 <strong>Wegberg</strong><br />
Telefon +49 (0) 2434/81-1 · Telefax +49 (0) 2434/81446<br />
Internet: www.driescher-wegberg.de · E-Mail: info@driescher-wegberg.de<br />
C 13 1.0 W