Quick Guide to - Festo

Quick Guide to - Festo Quick Guide to - Festo

02.04.2013 Views

Tip Tip Input data order “polled, COS or cyclic” I/O Diagnostic Bits (Deactivated by default) Analogue modules, each channel 16 Bit Technologies modules (e.g. CPI Interface, CPX-FEC) Digital and valve modules (I/O, MPA, Pneu. Interface) Input data “Strobed” 1 Byte Status (optional) Tip CPX-FB11 I/O mapping Using the “Status Bits” of the “Strobed Connection” 1 2 3 4 Output data order “polled, COS or cyclic” ADR – Auto Address Recovery IDLE and Fault Mode I/O Diagnostic Bits (Deactivated by default) Analogue modules, each channel 16 Bit Technologies modules (e.g. CPI Interface, CPX-FEC) Digital and valve modules (I/O, MPA, Pneu. Interface) By using the ADR function field device parameters are directly stored inside the PLC DeviceNet scanner. The scanner must support this function. An automatic recovery of parameters during a device exchange is possible Activating ADR: Go to scanner Properties -> ADR 1. “Enable ADR” 2. “Load Device Config” 3. “Configuration Recovery” Tip Tip Tip IDLE mode: Defines the status of output signals during the connection to a PLC which is actually stopped or in programming mode FAULT mode: Defines the status of output signals during a network failure when connected to a running PLC The default setup defines all output signals to the OFF state during one of the modes An optional channel based setup can be made: Value to OFF (default) Value to ON Hold Last State ! The internal CPX mapping cannot be changed by the configuration tools. PROG PROG PROG RUN RUN RUN The “Status Bits” are 8 major signals which can be considered inside the PLC program. They are accessed via the optional “Strobed connection” Bit Diagnostic information Description ---------------------------------------------------------------------------------------------- 0 Fault at valve Module type on which 1 Fault at output a fault has occurred 2 Fault at input 3 Fault on analogue/function module ---------------------------------------------------------------------------------------------- 4 Under voltage Type of fault 5 Short circuit/overload 6 Wire fracture/open load 7 Other faults ---------------------------------------------------------------------------------------------- Additional and advanced diagnostics can be read out with: - Online mode of RSNetWorx - Handheld unit CPX-MMI Modular EDS makes an easier parameterisation possible. Just existing parameters are visible. Parameters of complex modules and technology modules are just listed in modular EDS. The I/O size is visible. 1. Install all EDS files from the CPX modular EDS file library 2. Change the DIP switches Operating mode: Remote I/O Modular EDS Attention: - In combination with RSNetWorx v.5 only - The internal I/O mapping is still the standard mapping (see Step 4) Modular EDS for CPX-FB11 (from R14, SW 25.04.05) Additional diagnostics and system data access 1. Explicit Messaging via DeviceNet A library with objects for data access via DeviceNet is available. The library includes objects (data groups), instances (module no) and attributes (parameters) for almost all system data. More details: Manual CPX-FB11 Attachments 2. Activating Status Interface or diagnostic Bits into the process data Diagnostic Bits: Instead of using the status bits via “Strobed connection”, an alternative mapping into the process data is possible (2 Byte IN) Status Interface: Allows an access to advanced CPX data via a 2 Byte IN/OUT interface inside the process data. 3. Using alternative tools - RSNetWorx in online mode - CPX-MMI - Handheld-tool which is optimised for use of CPX-Terminals Festo AG & Co KG Quick Guide to CPX-FB11/Rockwell Automation PLC Version A3

Tip Tip<br />

Input data order<br />

“polled, COS or cyclic”<br />

I/O Diagnostic Bits<br />

(Deactivated by default)<br />

Analogue modules,<br />

each channel 16 Bit<br />

Technologies modules<br />

(e.g. CPI Interface, CPX-FEC)<br />

Digital and valve modules<br />

(I/O, MPA, Pneu. Interface)<br />

Input data “Strobed”<br />

1 Byte Status (optional)<br />

Tip<br />

CPX-FB11 I/O mapping Using the “Status Bits” of the<br />

“Strobed Connection”<br />

1<br />

2<br />

3<br />

4<br />

Output data order<br />

“polled, COS or cyclic”<br />

ADR – Au<strong>to</strong> Address<br />

Recovery<br />

IDLE and Fault Mode<br />

I/O Diagnostic Bits<br />

(Deactivated by default)<br />

Analogue modules,<br />

each channel 16 Bit<br />

Technologies modules<br />

(e.g. CPI Interface, CPX-FEC)<br />

Digital and valve modules<br />

(I/O, MPA, Pneu. Interface)<br />

By using the ADR function field device parameters are directly s<strong>to</strong>red<br />

inside the PLC DeviceNet scanner. The scanner must support this function.<br />

An au<strong>to</strong>matic recovery of<br />

parameters during a device<br />

exchange is possible<br />

Activating ADR:<br />

Go <strong>to</strong> scanner<br />

Properties -> ADR<br />

1. “Enable ADR”<br />

2. “Load Device Config”<br />

3. “Configuration<br />

Recovery”<br />

Tip<br />

Tip Tip<br />

IDLE mode:<br />

Defines the status of output<br />

signals during the connection<br />

<strong>to</strong> a PLC which is<br />

actually s<strong>to</strong>pped or in<br />

programming mode<br />

FAULT mode:<br />

Defines the status of output<br />

signals during a network failure<br />

when connected <strong>to</strong> a running PLC<br />

The default setup defines all<br />

output signals <strong>to</strong> the OFF<br />

state during one of the modes<br />

An optional channel based setup<br />

can be made:<br />

Value <strong>to</strong> OFF (default)<br />

Value <strong>to</strong> ON<br />

Hold Last State<br />

! The internal CPX mapping<br />

cannot be changed by the<br />

configuration <strong>to</strong>ols.<br />

PROG<br />

PROG<br />

PROG<br />

RUN<br />

RUN<br />

RUN<br />

The “Status Bits” are 8 major signals which can be considered inside the<br />

PLC program. They are accessed via the optional “Strobed connection”<br />

Bit Diagnostic information Description<br />

----------------------------------------------------------------------------------------------<br />

0 Fault at valve Module type on which<br />

1 Fault at output a fault has occurred<br />

2 Fault at input<br />

3 Fault on analogue/function module<br />

----------------------------------------------------------------------------------------------<br />

4 Under voltage Type of fault<br />

5 Short circuit/overload<br />

6 Wire fracture/open load<br />

7 Other faults<br />

----------------------------------------------------------------------------------------------<br />

Additional and advanced diagnostics can be read out with:<br />

- Online mode of RSNetWorx<br />

- Handheld unit CPX-MMI<br />

Modular EDS makes an easier parameterisation possible. Just existing<br />

parameters are visible. Parameters of complex modules and technology<br />

modules are just listed in modular EDS. The I/O size is visible.<br />

1. Install all EDS files from<br />

the CPX modular EDS file<br />

library<br />

2. Change the DIP switches<br />

Operating mode:<br />

Remote I/O<br />

Modular EDS<br />

Attention:<br />

- In combination with<br />

RSNetWorx v.5 only<br />

- The internal I/O mapping is<br />

still the standard mapping<br />

(see Step 4)<br />

Modular EDS for CPX-FB11<br />

(from R14, SW 25.04.05)<br />

Additional diagnostics<br />

and system data access<br />

1. Explicit Messaging via DeviceNet<br />

A library with objects for data access via DeviceNet is available.<br />

The library includes objects (data groups), instances (module no)<br />

and attributes (parameters) for almost all system data.<br />

More details: Manual CPX-FB11 Attachments<br />

2. Activating Status Interface or diagnostic Bits in<strong>to</strong> the process data<br />

Diagnostic Bits: Instead of using the status bits via<br />

“Strobed connection”, an alternative mapping in<strong>to</strong><br />

the process data is possible (2 Byte IN)<br />

Status Interface: Allows an access <strong>to</strong> advanced CPX<br />

data via a 2 Byte IN/OUT interface inside<br />

the process data.<br />

3. Using alternative <strong>to</strong>ols<br />

- RSNetWorx in online mode<br />

- CPX-MMI - Handheld-<strong>to</strong>ol which is optimised for use of CPX-Terminals<br />

Fes<strong>to</strong> AG & Co KG <strong>Quick</strong> <strong>Guide</strong> <strong>to</strong> CPX-FB11/Rockwell Au<strong>to</strong>mation PLC Version A3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!