staircase. Signs may have <strong>to</strong> be illum<strong>in</strong>ated (this is not required where they are<br />

adequately lit by emergency light<strong>in</strong>g).<br />

Signs must comply with BS 5499 and the Health and Safety (Safety Signs & Signals)<br />

Regulations 1996.<br />

Fire Fight<strong>in</strong>g Equipment<br />

The provision of emergency fire fight<strong>in</strong>g equipment forms part of the Fire Risk Assessment<br />

for the common areas of the house, where it provides a measure <strong>to</strong> control small fires and<br />

<strong>to</strong> prevent them develop<strong>in</strong>g. Multi-purpose fire ext<strong>in</strong>guishers hav<strong>in</strong>g a rat<strong>in</strong>g of 2A10B:C<br />

should be provided with<strong>in</strong> the common areas, normally 1 per land<strong>in</strong>g. Fire fight<strong>in</strong>g<br />

equipment must be selected, <strong>in</strong>stalled, and ma<strong>in</strong>ta<strong>in</strong>ed <strong>in</strong> accordance with BS 5306.<br />

Dwell<strong>in</strong>g Fire Safety<br />

Dwell<strong>in</strong>g Layout and Design<br />

The layout and design of the flat must provide a protected escape route from the<br />

bedrooms <strong>to</strong> the flat exit door. In most cases this is by means of a protected entrance<br />

hallway compris<strong>in</strong>g fire resist<strong>in</strong>g partitions and <strong>in</strong>ternal fire doors. Internal fire doors must<br />

provide at least 20 m<strong>in</strong>utes fire resistance. Ideally the layout should be such that the<br />

bedroom doors are positioned closer <strong>to</strong> the exit door than the doors <strong>to</strong> the risk rooms<br />

(kitchen & liv<strong>in</strong>g room). In no case should an <strong>in</strong>ner room [one entered only via another<br />

room] be used for sleep<strong>in</strong>g purposes unless provided with an alternative means of escape.<br />

Au<strong>to</strong>matic Fire Detection (AFD) System<br />

The l<strong>in</strong>ked Grade A heat detec<strong>to</strong>r provided as part of the common areas system will<br />

provide no protection aga<strong>in</strong>st a fire orig<strong>in</strong>at<strong>in</strong>g with<strong>in</strong> the flat dwell<strong>in</strong>g. For this reason a<br />

separate Grade D ma<strong>in</strong>s powered [with battery backup] AFD system must be provided <strong>in</strong><br />

each flat. The system should provide Category LD2 coverage, with smoke alarms <strong>to</strong> the<br />

entrance hallway and any <strong>in</strong>ternal stairway, <strong>to</strong>gether with a heat alarm <strong>to</strong> the kitchen. All<br />

alarms with<strong>in</strong> each flat must be <strong>in</strong>terl<strong>in</strong>ked. Fitt<strong>in</strong>g of an optical type smoke alarm <strong>in</strong> the<br />

entrance hallway and any <strong>in</strong>ternal stairway is advised.<br />

If the flat <strong>in</strong>ternal layout is not ideal additional detection (smoke alarm) will be required <strong>to</strong><br />

the liv<strong>in</strong>g room. In addition if the structural fire separation <strong>to</strong> adjo<strong>in</strong><strong>in</strong>g flats is poor (typically<br />

lath & plaster partitions/ceil<strong>in</strong>gs) detection will be required <strong>to</strong> all rooms <strong>in</strong> the flat, except<strong>in</strong>g<br />

bathrooms & WCs.<br />

Care should be taken <strong>to</strong> ensure that the test/hush but<strong>to</strong>ns of the alarms can be safely<br />

operated from floor level-this may be a problem where the alarm is fitted on a high ceil<strong>in</strong>g.<br />

The ability <strong>to</strong> access alarm control but<strong>to</strong>ns is essential, and fitt<strong>in</strong>g of remote test/hush<br />

controls at low level may be required.<br />

Fire fight<strong>in</strong>g equipment<br />

A fire blanket, <strong>to</strong> comply with BS 6575, must be provided <strong>in</strong> the kitchen,<br />

LISTED BUILDINGS<br />

Fire protection works with<strong>in</strong> listed build<strong>in</strong>gs requires more specialist consideration and<br />

build<strong>in</strong>g techniques and you are strongly advised <strong>to</strong> contact the Listed Build<strong>in</strong>g section of<br />

the Plann<strong>in</strong>g Department before commencement of any works. Contact telephone number<br />

020 7641 2513.<br />