Section 7 Refrigeration System<br />

Pressure Control Specifications and Diagnostics<br />

HIGH PRESSURE CUT-OUT (HPCO) CONTROL<br />

Function<br />

Stops the ice machine if subjected to excessive highside<br />

pressure.<br />

The HPCO control is normally closed, and opens on a<br />

rise in discharge pressure.<br />

Specifications<br />

Cut-out: 450 psig ±10 (3103 kPa ±69, 31 Bar ±.69)<br />

Cut-in: <strong>Manual</strong> or automatic reset<br />

Must be below 300 psig (2068 kPa, 20.68<br />

Bar ±.69) to reset<br />

Check Procedure<br />

1. Set ICE/OFF/CLEAN switch to OFF.<br />

2. Connect manifold gauges.<br />

3. Hook voltmeter in parallel across the HPCO, leaving<br />

wires attached.<br />

4. Close the water service valve to the water<br />

condenser inlet.<br />

5. Set ICE/OFF/CLEAN switch to ICE.<br />

6. No water flowing through the condenser will cause<br />

the HPCO control to open because of excessive<br />

pressure. Watch the pressure gauge and record the<br />

cut-out pressure.<br />

! Warning<br />

If discharge pressure exceeds 460 psig (2068 kPa,<br />

20.68 Bar ) and the HPCO control does not cut out,<br />

set ICE/OFF/CLEAN switch to OFF to stop ice<br />

machine operation.<br />

Replace the HPCO control if it:<br />

• Will not reset [below 300 psig (2068 kPa, 20.68 Bar )]<br />

• Does not open at the specified cut-out point<br />

Part Number 80-1634-3 7-19