Controls (cont)<br />
the minimum position. After the room thermostat is satisfied,<br />
the damper will spring return to the fully-closed<br />
position.<br />
When the outdoor air is below the (EC) setting and the<br />
thermostat calls for cooling, the economizer outdoor-air<br />
damper is opened proportionally to maintain between 50<br />
and 56 F at the mixed-air sensor. If outdoor air alone cannot<br />
satisfy the cooling requirements, economizer cooling<br />
is integrated with mechanical cooling. When the room thermostat<br />
is satisfied, the damper will spring return to the fullyclosed<br />
position.<br />
Cooling, units with Parablade economizer (48TJ008-<br />
014) — When the outdoor air is above the enthalpy control<br />
(EC) setting, and the room thermostat calls for cooling,<br />
and compressor contactor no. 1 is energized to start compressor<br />
no. 1 and the condenser-fan motor. The evaporatorfan<br />
motor is energized and the economizer damper moves<br />
to the minimum position. Upon a further call for cooling,<br />
compressor contactor no. 2 is energized, starting compressor<br />
no. 2. After the room thermostat is satisfied, the damper<br />
will spring return to the fully-closed position.<br />
When the outdoor-air temperature is below the EC setting<br />
and the thermostat calls for cooling, the economizer<br />
outdoor-air damper is opened proportionally to maintain<br />
between 50 and 56 F at the mixed-air sensor. If outdoor-air<br />
alone cannot satisfy the cooling requirements, economizer<br />
cooling is integrated with mechanical cooling, and the second<br />
compressor is locked out. When the room thermostat<br />
is satisfied, the damper will spring return to the fully-closed<br />
position.<br />
Cooling, units with economizer (48TJ016-028) —<br />
Upon a call for cooling, when outdoor ambient is above the<br />
temperature control setting, the economizer damper moves<br />
to VENT position. The compressors and evaporator and<br />
condenser fans energize.<br />
Upon a first call for cooling, when outdoor ambient is<br />
below the temperature control setting, the evaporator fan<br />
60<br />
starts and the economizer opens to maintain 53 F leavingair<br />
temperature. The compressors remain off.<br />
Upon a second-stage call for cooling, compressor no. 1<br />
is energized and mechanical cooling is integrated with economizer<br />
cooling. If the outdoor-air temperature drops below<br />
50 F, a cooling lockout switch prevents the compressors<br />
from running.<br />
When supply-air temperature drops below a fixed set point,<br />
the economizer damper modulates to maintain the temperature<br />
at the fixed set point.<br />
A freeze protection thermostat (FPT) is located on the<br />
evaporator coil. It detects frost build-up and turns off the<br />
compressors, allowing the coil to clear. Once frost has melted,<br />
the compressors can be reenergized.<br />
Heating, units with economizer (48TJ004-014) —<br />
When the thermostat calls for heating, terminal W1 is energized.<br />
In order to prevent thermostat short-cycling, the<br />
unit is locked into the Heating mode for at least 1 minute<br />
when W1 is energized. The induced-draft motor is then energized<br />
and the burner ignition sequence begins. The indoor<br />
(evaporator) fan motor (IFM) is energized 45 seconds<br />
after a flame is ignited and the damper moves to the minimum<br />
position. On units equipped for two stages of heat,<br />
when additional heat is needed, W2 is energized and the<br />
high-fire solenoid on the main gas valve (MGV) is energized.<br />
When the thermostat is satisfied and W1 is deenergized, the<br />
IFM stops after a 45 second time-off delay. The economizer<br />
damper then moves to the fully closed position. When using<br />
continuous fan, the damper will remain in the minimum<br />
position.<br />
Heating, units with economizer (48TJ016-028) —<br />
Outdoor-air damper stays at VENT position while evaporator<br />
fan is operating. Refer to Heating, units without economizer<br />
section on page 59 for remainder of operating<br />
sequence.