Product Data - Carrier
Product Data - Carrier
Product Data - Carrier
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
ARI capacity ratings (cont)<br />
UNIT 48TJ<br />
HEATING INPUT<br />
(Btuh)<br />
Stage 2/Stage 1<br />
HEATING CAPACITIES AND EFFICIENCIES<br />
OUTPUT CAPACITY<br />
(Btuh)<br />
TEMPERATURE<br />
RISE<br />
(F)<br />
AFUE<br />
(%)<br />
STEADY-STATE<br />
EFFICIENCY<br />
(%)<br />
CALIFORNIA<br />
SEASONAL<br />
EFFICIENCY<br />
(%)<br />
E004 —/ 72,000 59,200 25-55 80.0 80.0 77.2<br />
F004 115,000/ 82,000 92,000 55-85 80.0 80.0 76.7<br />
D005 —/ 72,000 59,200 25-55 80.0 80.0 77.2<br />
E005 —/115,000 92,000 35-65 80.0 80.0 77.1<br />
F005 150,000/120,000 120,000 50-80 80.0 80.0 76.9<br />
D006 —/ 72,000 59,200 25-55 80.0 80.0 77.2<br />
E006 —/115,000 92,000 35-65 80.0 80.0 77.1<br />
F006 150,000/120,000 120,000 50-80 80.0 80.0 76.9<br />
D007 —/ 72,000 59,200 25-55 80.0 80.0 77.2<br />
E007 —/115,000 92,000 35-65 80.0 80.0 77.1<br />
F007 150,000/120,000 120,000 50-80 80.0 80.0 76.9<br />
D008 —/125,000 100,000 20-50 80.0 80.0 75.8<br />
E008 180,000/120,000 144,000 35-65 80.0 80.0 77.1<br />
F008 224,000/180,000 179,200 45-75 80.0 80.0 77.1<br />
D009 —/125,000 100,000 20-50 80.0 80.0 75.8<br />
E009 180,000/120,000 144,000 35-65 80.0 80.0 77.1<br />
F009 224,000/180,000 179,200 45-75 80.0 80.0 77.1<br />
D012 180,000/120,000 144,000 35-65 80.0 80.0 77.1<br />
E012 224,000/180,000 179,200 35-65 80.0 80.0 77.1<br />
F012 250,000/200,000 200,000 40-70 80.0 80.0 76.4<br />
D014 224,000/180,000 179,200 35-65 80.0 80.0 77.1<br />
E014 250,000/200,000 200,000 40-70 80.0 80.0 76.4<br />
LEGEND<br />
AFUE — Annual Fuel Utilization Efficiency<br />
NOTE: NOx levels are 40 nanograms/joule with the accessory NOx reduction kit (004-014).<br />
UNIT 48TJ<br />
HEATING INPUT<br />
(Btuh)<br />
Stage 2/Stage 1*<br />
HEATING CAPACITIES AND EFFICIENCIES (cont)<br />
OUTPUT CAPACITY<br />
(Btuh)<br />
TEMPERATURE<br />
RISE<br />
(F)<br />
STEADY-STATE<br />
EFFICIENCY<br />
(%)<br />
MINIMUM<br />
HEATING<br />
CFM<br />
D016 231,000/115,500 185,000 25-55 80.0 3057<br />
E016 270,000/115,500 216,000 25-55 80.0 3520<br />
D020,024 270,000/115,500 216,000 15-45 80.0 4364<br />
E024 485,000/242,500 388,000 35-65 80.0 5427<br />
D028 270,000/115,500 216,000 15-45 80.0 4364<br />
E028 485,000/242,500 388,000 35-65 80.0 5427<br />
*All units are 2-stage heat.<br />
NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stge heating is 45 F. There is no<br />
minimum mixed-air temperature limitation during second-stage heating.<br />
6