Product Data - Carrier
Product Data - Carrier
Product Data - Carrier
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Performance data (cont)<br />
FAN PERFORMANCE — 48TJ016-028 UNITS (cont)<br />
48TJ020 (18 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
External Static Pressure (in. wg)<br />
Airflow<br />
(CFM)<br />
Rpm<br />
0.2<br />
Bhp Watts Rpm<br />
0.4<br />
Bhp Watts Rpm<br />
0.6<br />
Bhp Watts Rpm<br />
0.8<br />
Bhp Watts Rpm<br />
1.0<br />
Bhp Watts Rpm<br />
1.2<br />
Bhp Watts<br />
5400 707 1.34 1237 805 1.72 1526 898 2.04 1830 986 2.42 2159 1071 2.82 2594 1153 3.22 2894<br />
5500 717 1.40 1292 813 1.80 1585 905 2.10 1892 992 2.50 2223 1076 2.90 2680 1157 3.30 2962<br />
6000 767 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 1104 3.30 2967 1181 3.80 3358<br />
6500 817 2.20 1992 903 2.60 2329 985 3.00 2673 1062 3.40 3031 1136 3.80 3410 1209 4.30 3811<br />
7000 869 2.70 2427 950 3.10 2787 1028 3.50 3151 1102 3.90 3527 1172 4.40 3919 1241 4.80 4331<br />
7200 889 2.94 2624 969 3.34 2993 1046 3.74 3366 1118 4.18 3749 1187 4.64 4147 1255 5.08 4564<br />
7500 920 3.30 2919 998 3.70 3303 1073 4.10 3689 1143 4.60 4083 1210 5.00 4490 1275 5.50 4914<br />
8000 973 3.90 3476 1047 4.30 3886 1119 4.80 4294 1186 5.30 4708 1250 5.70 5131 — — —<br />
8500 1026 4.60 4102 1097 5.10 4635 1166 5.60 4967 — — — — — — — — —<br />
9000 1079 5.40 4800 — — — — — — — — — — — — — — —<br />
48TJ020 (18 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
Airflow<br />
(Cfm)<br />
External Static Pressure (in. wg)<br />
1.3 1.4 1.6 1.8<br />
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts<br />
5400 11.92 3.47 3095 1231 3.72 3296 1306 4.12 3716 1379 4.62 4153<br />
5500 1196 3.55 3164 1234 3.80 3366 1309 4.20 3789 1381 4.70 4229<br />
6000 1218 4.00 3565 1251 4.20 3772 1327 4.70 4206 1396 5.20 4658<br />
6500 1244 4.50 4022 1279 4.70 4233 1348 5.20 4677 1415 5.80 5139<br />
7000 1275 5.05 4547 1308 5.30 4762 — — — — — —<br />
7200 1288 5.33 4783 — — — — — — — — —<br />
7500 1307 5.75 5135 — — — — — — — — —<br />
8000 — — — — — — — — — — — —<br />
8500 — — — — — — — — — — — —<br />
9000 — — — — — — — — — — — —<br />
LEGEND<br />
Bhp — Brake Horsepower Input to Fan<br />
FIOP — Factory-Installed Option<br />
Watts — Input Watts to Motor<br />
NOTES:<br />
1. Boldface indicates field-supplied drive required. (See Note 2.)<br />
2. Motor drive range is 1047 to 1251 rpm. Other rpms require a field-supplied<br />
drive.<br />
3. Static pressure losses (i.e., economizer) must be added to external static pressure<br />
before entering Fan Performance table. See table on page 49 for accessory/<br />
FIOP static pressure information.<br />
4. Interpolation is permissible. Do not extrapolate.<br />
5. Maximum continuous bhp is 5.9 and the maximum continuous watts are 5180.<br />
Extensive motor and drive testing on these units ensures that the full horsepower<br />
range of the motor can be utilized with confidence. Using your fan<br />
motors up to the watts rating shown will not result in nuisance tripping or premature<br />
motor failure. Unit warranty will not be affected. See Evaporator-Fan<br />
Motor Performance table on page 52 for additional information.<br />
6. Fan performance is based on wet coils, clean filters, and casing losses.<br />
7. Use of a field-supplied motor may affect wire sizing. Contact your <strong>Carrier</strong> representative<br />
for details.<br />
48TJ024 (20 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
External Static Pressure (in. wg)<br />
Airflow<br />
(CFM)<br />
Rpm<br />
0.2<br />
Bhp Watts Rpm<br />
0.4<br />
Bhp Watts Rpm<br />
0.6<br />
Bhp Watts Rpm<br />
0.8<br />
Bhp Watts Rpm<br />
1.0<br />
Bhp Watts Rpm<br />
1.2<br />
Bhp Watts<br />
6,000 767 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 1104 3.30 2967 1181 3.80 3358<br />
6,500 817 2.20 1992 903 2.60 2329 985 3.00 2673 1062 3.40 3031 1136 3.80 3410 1209 4.30 3811<br />
7,000 869 2.70 2427 950 3.10 2787 1028 3.50 3151 1102 3.90 3527 1172 4.40 3919 1241 4.80 4331<br />
7,500 920 3.30 2919 998 3.70 3303 1073 4.10 3689 1143 4.60 4083 1210 5.00 4490 1275 5.50 4914<br />
8,000 973 3.90 3476 1047 4.30 3886 1119 4.80 4294 1186 5.30 4708 1250 5.70 5131 1313 6.20 5569<br />
8,500 1026 4.60 4102 1097 5.10 4635 1166 5.60 4967 1231 6.00 5401 1292 6.50 5843 1352 7.00 6297<br />
9,000 1079 5.40 4800 1147 5.90 5257 1214 6.40 5714 1276 6.90 6171 1336 7.40 6632 1393 7.90 7102<br />
9,500 1133 6.20 5576 1199 6.80 6058 1263 7.30 6540 1323 7.90 7018 1381 8.40 7500 1436 8.90 7988<br />
10,000 1188 7.20 6432 1250 7.80 6939 1313 8.30 7444 1371 8.90 7946 1426 9.50 8449 — — —<br />
48TJ024 (20 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
External Static Pressure (in. wg)<br />
Airflow<br />
(Cfm)<br />
Rpm<br />
1.4<br />
Bhp Watts Rpm<br />
1.6<br />
Bhp Watts Rpm<br />
1.8<br />
Bhp Watts Rpm<br />
1.9<br />
Bhp Watts Rpm<br />
2.0<br />
Bhp Watts<br />
6,000 1255 4.20 3772 1327 4.70 4206 1396 5.20 4658 1431 5.45 4884 1465 5.70 5110<br />
6,500 1279 4.70 4233 1348 5.20 4677 1415 5.80 5139 1449 6.10 5370 1482 6.40 5601<br />
7,000 1308 5.30 4762 1373 5.80 5215 1437 6.40 5686 1469 6.70 5922 1501 7.00 6157<br />
7,500 1339 6.00 5356 1401 6.50 5818 1462 7.00 6298 1493 7.25 6538 1523 7.50 6778<br />
8,000 1373 6.70 6024 1433 7.30 6495 1493 7.80 6966 1523 8.05 7202 — — —<br />
8,500 1410 7.60 6765 1467 8.10 7248 1524 8.70 7731 — — — — — —<br />
9,000 1449 8.50 7584 1503 9.00 8033 — — — — — — — — —<br />
9,500 1488 9.40 8403 — — — — — — — — — — — —<br />
10,000 — — — — — — — — — — — — — — —<br />
LEGEND<br />
Bhp — Brake Horsepower Input to Fan<br />
FIOP — Factory-Installed Option<br />
Watts — Input Watts to Motor<br />
NOTES:<br />
1. Boldface indicates field-supplied drive required. (See Note 3.)<br />
2. indicates additional capability of the 460-v motor.<br />
3. Motor drive range is 1238 to 1494 rpm. Other rpms require a field-supplied<br />
drive.<br />
4. Static pressure losses (i.e., economizer) must be added to external static pressure<br />
before entering Fan Performance table. See table on page 49 for accessory/<br />
FIOP static pressure information.<br />
46<br />
5. Interpolation is permissible. Do not extrapolate.<br />
6. Maximum continuous bhp is 8.7 for 208/230 and 575-v units and 9.5 for<br />
460-v units. The maximum continuous watts are 7915 for the 208/230 and 575-v<br />
units and 8640 for the 460-v units. Extensive motor and drive testing on these<br />
units ensures that the full horsepower range of the motor can be utilized with<br />
confidence. Using your fan motors up to the watts rating shown will not result<br />
in nuisance tripping or premature motor failure. Unit warranty will not be<br />
affected. See Evaporator-Fan Motor Performance table on page 52 for additional<br />
information.<br />
7. Fan performance is based on wet coils, clean filters, and casing losses.<br />
8. Use of a field-supplied motor may affect wire sizing. Contact your <strong>Carrier</strong> representative<br />
for details.