Product Data - Carrier
Product Data - Carrier
Product Data - Carrier
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Performance data (cont)<br />
FAN PERFORMANCE — 48TJ004-014 HORIZONTAL DISCHARGE UNITS (cont)<br />
48TJ007 (6 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
External Static Pressure (in. wg)<br />
Airflow<br />
(Cfm)<br />
0.1 0.2 0.4 0.6 0.8 1.0<br />
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts<br />
1800 885 0.63 623 942 0.73 700 1047 0.90 835 1139 1.05 956 1193 1.14 1031 1276 1.30 1165<br />
1900 928 0.73 700 982 0.83 779 1084 1.02 932 1160 1.11 1006 1223 1.24 1114 1301 1.38 1233<br />
2000 971 0.84 787 1022 0.94 867 1121 1.12 1014 1188 1.22 1097 1254 1.36 1216 1329 1.44 1284<br />
2100 1015 0.97 891 1063 1.10 998 1140 1.18 1064 1196 1.27 1140 1272 1.45 1292 1354 1.58 1404<br />
2200 1060 1.10 998 1104 1.20 1081 1159 1.23 1106 1229 1.41 1258 1306 1.53 1361 1363 1.70 1508<br />
2300 1104 1.25 1123 1130 1.27 1140 1196 1.37 1224 1264 1.56 1387 1340 1.66 1473 1397 1.86 1648<br />
2400 1138 1.30 1165 1174 1.37 1224 1245 1.57 1396 1305 1.63 1447 1373 1.84 1630 1440 1.95 1726<br />
2500 1183 1.43 1275 1201 1.50 1335 1284 1.65 1465 1338 1.75 1552 1402 1.99 1761 1469 2.04 1805<br />
2600 1210 1.58 1404 1246 1.67 1482 1312 1.76 1560 1366 1.96 1735 1435 2.10 1858 1494 2.19 1936<br />
2700 1254 1.76 1560 1285 1.80 1595 1354 1.95 1726 1403 2.14 1892 1474 2.21 1954 1536 2.46 2171<br />
2800 1274 1.82 1613 1304 1.85 1639 1374 2.12 1875 1459 2.25 1989 1514 2.42 2136 1570 2.66 2343<br />
2900 1318 1.95 1726 1345 2.05 1814 1412 2.32 2050 1496 2.54 2240 1529 2.61 2300 1603 2.87 2521<br />
3000 1362 2.20 1945 1378 2.30 2032 1451 2.40 2119 1534 2.66 2343 1560 2.81 2470 1611 3.01 2648<br />
48TJ007 (6 TONS) — STANDARD MOTOR (BELT DRIVE)<br />
External Static Pressure (in. wg)<br />
Airflow<br />
(Cfm)<br />
1.2 1.4 1.6<br />
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts<br />
1800 1341 1.40 1250 1413 1.55 1378 1474 1.58 1404<br />
1900 1374 1.53 1361 1437 1.62 1439 1490 1.67 1482<br />
2000 1396 1.66 1473 1460 1.68 1491 1509 1.77 1569<br />
2100 1413 1.75 1552 1475 1.73 1534 1529 1.92 1700<br />
2200 1434 1.81 1604 1487 1.85 1639 1554 2.07 1831<br />
2300 1459 1.88 1665 1520 2.07 1831 1576 2.24 1980<br />
2400 1502 2.06 1823 1552 2.24 1980 1604 2.42 2136<br />
2500 1524 2.24 1980 1585 2.42 2136 1638 2.60 2292<br />
2600 1552 2.40 2119 1616 2.63 2317 1671 2.80 2462<br />
2700 1584 2.61 2300 1646 2.83 2487 1706 2.97 2653<br />
2800 1624 2.85 2504 1677 2.99 2661 — — —<br />
2900 1671 3.03 2725 — — — — — —<br />
3000 — — — — — — — — —<br />
Bhp<br />
FIOP<br />
Watts<br />
—<br />
—<br />
—<br />
LEGEND<br />
Brake Horsepower Input to Fan<br />
Factory-Installed Option<br />
Input Watts to Motor<br />
NOTES:<br />
1. Boldface indicates field-supplied drive required. (See Note 3.)<br />
2. indicates field-supplied motor and drive required.<br />
3. Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied<br />
drive.<br />
40<br />
4. Values include losses for filters, unit casing, and wet coils. See page 49 for<br />
accessory/FIOP static pressure information.<br />
5. Maximum continuous bhp is 2.4 and maximum continuous watts are 2120.<br />
Extensive motor and electrical testing on these units ensures that the full range<br />
of the motor can be utilized with confidence. Using your fan motors up to the<br />
wattage ratings shown will not result in nuisance tripping or premature motor<br />
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance<br />
table on page 52 for additional information.<br />
6. Use of a field-supplied motor may affect wire sizing. Contact your <strong>Carrier</strong> representative<br />
for details.<br />
7. Interpolation is permissible. Do not extrapolate.