Product Data - Carrier
Product Data - Carrier
Product Data - Carrier
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Features/Benefits (cont)<br />
<strong>Carrier</strong> Apollo controls add<br />
reliability, efficiency, and<br />
simplification<br />
The Apollo direct digital controls are<br />
ordered as a factory-installed option.<br />
Designed and manufactured<br />
exclusively by <strong>Carrier</strong>, the controls can<br />
be used to actively monitor and control<br />
all modes of operation, as well<br />
as to monitor evaporator-fan status,<br />
filter status, indoor-air quality (humidity<br />
and carbon dioxide), supply-air<br />
temperature, and outdoor-air<br />
temperature.<br />
The Apollo communicating controls<br />
are factory-installed into the rooftop<br />
unit control box, and come equipped<br />
with built-in diagnostic capabilities.<br />
Light-emitting diodes (LEDs) simplify<br />
troubleshooting by indicating thermostat<br />
commands for both stages of<br />
heating and cooling, evaporator fan<br />
operation, and economizer operation.<br />
The Apollo communicating controls<br />
are designed to work specifically with<br />
the <strong>Carrier</strong> TEMP and VVT (variable<br />
volume and temperature) thermostats.<br />
The Apollo controls, combined<br />
with <strong>Carrier</strong> thermostats, incorporate<br />
a 5-minute recycle delay timer<br />
between modes of operation to prevent<br />
short cycling.<br />
The standard rooftop control<br />
system is readily adaptable to all conventional<br />
and programmable thermostats.<br />
In addition, units are suitable<br />
for integration into building monitor<br />
control systems if required. This system<br />
gives the 48TJ units the flexibility to<br />
communicate with almost any thermostat<br />
or building control system.<br />
Model number nomenclature<br />
LEGEND<br />
Al — Aluminum<br />
Cu — Copper<br />
FIOP — Factory-Installed Option<br />
4<br />
SIZES 004-014<br />
*Refer to 48TJ Price Pages for 48TJ FIOP code table or<br />
contact your local representative for more details.<br />
†Single phase is available on 5-ton and smaller units.<br />
Indoor-air quality begins with<br />
<strong>Carrier</strong> rooftops<br />
Sloped condensate pans minimize biological<br />
growth in rooftop units in<br />
accordance with ASHRAE (American<br />
Society of Heating, Refrigeration,<br />
and Air Conditioning Engineers) Standard<br />
62. Two-in. filters with optional<br />
dirty filter indicator switch provide for<br />
greater particle reduction in the return<br />
air. The face-split evaporator<br />
coils improve the dehumidification capability<br />
of standard units, and standard<br />
enthalpy controls provided with<br />
the optional or accessory (004-014)<br />
economizers maximize building humidity<br />
control. The 48TJ004-014 units<br />
also have an accessory, 100% open,<br />
two-position damper to meet all<br />
your fresh outdoor air requirements.<br />
SIZES 016-028