Performance data<br />
48TJ004 (3 TONS)<br />
Temp (F)<br />
Air Entering<br />
Condenser<br />
(Edb)<br />
75<br />
85<br />
95<br />
105<br />
115<br />
Air Entering Evaporator — Cfm/BF<br />
900/0.11 1200/0.14 1500/0.17<br />
Air Entering Evaporator — Ewb (F)<br />
72 67 62 72 67 62 72 67 62<br />
TC 42.8 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2<br />
SHC 20.0 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0<br />
kW 2.91 2.81 2.70 2.99 2.88 2.78 3.02 2.92 2.82<br />
TC 40.8 36.9 33.3 42.5 38.7 35.0 43.6 39.9 36.1<br />
SHC 19.4 23.7 27.9 21.0 26.8 31.8 22.6 29.7 35.1<br />
kW 3.14 3.01 2.90 3.20 3.08 2.97 3.24 3.14 3.02<br />
TC 38.7 34.9 31.4 40.4 36.6 33.0 41.4 37.6 34.1<br />
SHC 18.6 22.9 27.0 20.3 26.0 30.9 22.0 28.8 34.0<br />
kW 3.35 3.21 3.09 3.42 3.29 3.16 3.47 3.35 3.22<br />
TC 36.5 32.8 29.2 38.1 34.3 30.9 39.0 35.2 32.4<br />
SHC 17.8 22.1 25.9 19.6 25.2 29.8 21.2 28.0 32.3<br />
kW 3.55 3.41 3.27 3.63 3.49 3.35 3.68 3.54 3.43<br />
TC 34.3 30.7 26.9 35.7 32.1 28.8 36.5 32.9 30.6<br />
SHC 17.0 21.3 24.8 19.0 24.4 28.8 20.5 27.1 30.6<br />
kW 3.76 3.60 3.45 3.84 3.68 3.54 3.88 3.74 3.64<br />
48TJ005 (4 TONS)<br />
Temp (F)<br />
Air Entering<br />
Condenser<br />
(Edb)<br />
75<br />
85<br />
95<br />
105<br />
115<br />
Air Entering Evaporator — Cfm/BF<br />
1200/0.12 1600/0.15 2000/0.18<br />
Air Entering Evaporator — Ewb (F)<br />
72 67 62 72 67 62 72 67 62<br />
TC 57.9 53.1 48.3 60.4 55.9 51.3 62.2 57.3 52.9<br />
SHC 27.2 33.3 39.2 29.4 37.2 44.8 31.4 40.3 49.1<br />
kW 4.07 3.93 3.79 4.17 4.03 3.90 4.24 4.08 3.96<br />
TC 55.7 50.8 45.3 57.7 53.4 48.5 59.4 55.0 50.2<br />
SHC 26.4 32.5 37.8 28.4 36.7 43.6 30.5 40.3 47.9<br />
kW 4.40 4.24 4.08 4.47 4.35 4.20 4.54 4.42 4.25<br />
TC 52.9 48.1 42.5 55.2 50.5 45.7 56.7 52.0 47.4<br />
SHC 25.5 31.5 36.4 27.6 35.6 42.2 29.7 39.2 46.7<br />
kW 4.70 4.54 4.36 4.78 4.63 4.47 4.87 4.70 4.56<br />
TC 50.1 45.3 39.8 52.3 47.6 42.8 53.6 48.9 44.9<br />
SHC 24.4 30.3 35.1 26.7 34.5 40.7 28.8 38.1 44.6<br />
kW 5.00 4.81 4.62 5.10 4.91 4.73 5.17 4.99 4.84<br />
TC 47.3 42.6 37.2 49.3 44.6 40.0 50.5 45.9 42.4<br />
SHC 23.4 29.2 33.7 25.9 33.3 39.3 27.8 37.1 42.4<br />
kW 5.30 5.07 4.88 5.42 5.19 4.99 5.48 5.28 5.12<br />
48TJ007 (6 TONS)<br />
Temp (F)<br />
Air Entering<br />
Condenser<br />
(Edb)<br />
75<br />
85<br />
95<br />
105<br />
115<br />
COOLING CAPACITIES<br />
48TJ006 (5 TONS)<br />
Temp (F)<br />
Air Entering<br />
Condenser<br />
(Edb)<br />
75<br />
85<br />
95<br />
105<br />
115<br />
Air Entering Evaporator — Cfm/BF<br />
1500/0.07 2000/0.09 2500/0.12<br />
Air Entering Evaporator — Ewb (F)<br />
72 67 62 72 67 62 72 67 62<br />
TC 71.0 63.8 55.4 74.5 67.2 59.2 76.5 69.7 62.1<br />
SHC 33.9 41.5 47.9 37.4 47.4 55.8 40.6 52.8 61.8<br />
kW 5.04 4.82 4.62 5.20 4.97 4.76 5.29 5.06 4.87<br />
TC 69.2 61.0 54.2 72.9 65.6 57.2 75.2 68.1 61.5<br />
SHC 33.4 40.5 47.3 37.0 46.9 54.9 40.1 52.3 61.3<br />
kW 5.50 5.27 5.02 5.66 5.41 5.18 5.75 5.50 5.29<br />
TC 65.5 56.6 50.4 69.4 60.9 53.1 71.2 63.3 57.8<br />
SHC 32.1 38.8 45.6 35.8 45.3 52.6 39.1 50.9 57.8<br />
kW 5.88 5.62 5.37 6.01 5.76 5.53 6.12 5.87 5.67<br />
TC 61.9 53.1 47.1 65.4 56.6 50.5 67.1 58.8 54.5<br />
SHC 30.8 37.5 44.1 34.5 43.7 50.2 37.9 49.3 54.5<br />
kW 6.25 5.99 5.72 6.38 6.13 5.91 6.50 6.23 6.06<br />
TC 58.2 49.7 43.7 61.4 52.3 47.8 63.0 54.3 51.2<br />
SHC 29.5 36.1 42.5 33.2 42.1 47.8 36.7 47.6 51.2<br />
kW 6.63 6.35 6.08 6.75 6.49 6.29 6.88 6.59 6.46<br />
Standard Ratings<br />
BF<br />
Edb<br />
Ewb<br />
kW<br />
Ldb<br />
Lwb<br />
SHC<br />
TC<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
LEGEND<br />
Bypass Factor<br />
Entering Dry-Bulb<br />
Entering Wet-Bulb<br />
Compressor Motor Power Input<br />
Leaving Dry-Bulb<br />
Leaving Wet-Bulb<br />
Sensible Heat Capacity (1000 Btuh) Gross<br />
Total Capacity (1000 Btuh) Gross<br />
NOTES:<br />
1. Direct interpolation is permissible. Do not extrapolate.<br />
2. The following formulas may be used:<br />
t ldb = tedb −<br />
sensible capacity (Btuh)<br />
1.10 x cfm<br />
t = Wet-bulb temperature corresponding to enthalpy of air leaving<br />
lwb<br />
h = h −<br />
lwb ewb<br />
Air Entering Evaporator — Cfm/BF<br />
1800/0.06 2100/0.08 2400/0.09 3000/0.11<br />
Air Entering Evaporator — Ewb (F)<br />
72 67 62 72 67 62 72 67 62 72 67 62<br />
TC 86.6 80.0 73.6 87.8 80.3 87.8 90.8 84.1 77.2 93.2 86.6 79.7<br />
SHC 42.2 52.3 62.2 43.0 53.9 43.0 46.5 59.6 71.6 50.1 66.4 78.7<br />
kW 5.48 5.33 5.21 5.69 5.50 5.69 5.59 5.44 5.29 5.66 5.51 5.35<br />
TC 84.1 77.4 71.0 84.0 77.2 84.0 87.8 81.2 74.5 90.1 83.5 77.3<br />
SHC 41.4 51.3 61.1 41.7 53.1 41.7 45.5 58.6 70.3 49.4 65.4 76.7<br />
kW 6.17 6.00 5.85 6.21 6.04 6.21 6.27 6.11 5.94 6.35 6.19 6.02<br />
TC 81.6 74.7 68.5 81.0 73.5 81.0 84.8 78.2 71.8 87.0 80.4 74.8<br />
SHC 40.6 50.3 60.0 40.8 51.8 40.8 44.6 57.6 69.1 48.7 64.5 74.7<br />
kW 6.86 6.67 6.49 6.78 6.54 6.78 6.95 6.77 6.59 7.03 6.86 6.69<br />
TC 78.4 71.8 65.6 76.8 69.7 76.8 81.6 74.9 68.9 83.3 76.9 72.1<br />
SHC 39.4 49.2 58.7 39.4 50.3 39.4 43.5 56.4 67.4 47.4 63.1 72.0<br />
kW 7.60 7.39 7.20 7.30 7.05 7.30 7.72 7.50 7.31 7.77 7.59 7.41<br />
TC 75.1 68.7 62.5 72.5 65.5 72.5 78.0 71.5 66.1 79.5 73.3 69.3<br />
SHC 38.1 47.9 57.2 37.9 48.7 37.9 42.3 55.1 65.5 46.3 61.6 69.2<br />
kW 8.36 8.14 7.93 7.81 7.53 7.81 8.49 8.25 8.06 8.55 8.33 8.18<br />
evaporator coil (h )<br />
lwb<br />
total capacity (Btuh)<br />
4.5 x cfm<br />
Where: h = Enthalpy of air entering evaporator coil<br />
ewb<br />
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.<br />
Below 80 F edb, subtract (corr factor x cfm) from SHC.<br />
Above 80 F edb, add (corr factor x cfm) to SHC.<br />
Correction Factor = 1.10 x (1 − BF) x (edb − 80).<br />