Product Data - Carrier
Product Data - Carrier
Product Data - Carrier
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Accessory dimensions (cont)<br />
Selection procedure (with 48TJE016 example)<br />
I Determine cooling and heating requirements at<br />
design conditions.<br />
Given:<br />
Required Cooling Capacity ......... 170,000 Btuh<br />
Sensible Heat Capacity ............ 114,000 Btuh<br />
Required Heating Capacity ......... 200,000 Btuh<br />
Condenser Entering Air Temp ..... 95 F (Summer)<br />
Evaporator Entering Air Temp .......... 80 F edb,<br />
67 F ewb<br />
Evaporator Air Quantity .............. 4,500 cfm<br />
External Static Pressure ............... 0.6 in. wg<br />
Electrical Characteristics (V-Ph-Hz) ...... 460-3-60<br />
Vertical discharge unit with optional economizer<br />
required.<br />
edb — Entering dry-bulb<br />
ewb — Entering wet-bulb<br />
II Select unit based on required cooling capacity.<br />
Enter Cooling Capacities table for 48TJ016 (page 27)<br />
at condenser entering temperature 95 F, evaporator<br />
air entering at 4,500 cfm and 67 F wb. The 48TJE016<br />
unit will provide a total cooling capacity of 180,000<br />
Btuh and a sensible heating capacity of 120,000 Btuh.<br />
For air entering evaporator at temperatures other than<br />
80 F edb, calculate sensible heat capacity correction<br />
as required using the formula in the notes following the<br />
Cooling Capacities tables.<br />
NOTE: Unit ratings are gross capacities and do not include<br />
the effect of evaporator-fan motor heat. To calculate<br />
net capacities, see Step V.<br />
III Select heating capacity of unit to provide design<br />
condition requirements.<br />
In the Heating Capacities and Efficiencies table (page 6)<br />
note that the 48TJE016 will provide an output capacity<br />
of 216,000 Btuh, which is adequate for the given<br />
application.<br />
24<br />
HORIZONTAL SUPPLY/RETURN ADAPTER INSTALLATION<br />
48TJ016-028<br />
NOTE: 50DP900211 and 48DP900071 are fully factory preassembled<br />
horizontal adapters and include an insulated high<br />
static regain transition duct which substantially improves fan<br />
static performance.<br />
IV Determine fan speed and power requirements<br />
at design conditions.<br />
Before entering the Fan Performance tables, calculate<br />
the total static pressure required based on unit<br />
components. From the given and the Accessory/FIOP<br />
Economizer Static Pressure table on page 49 find:<br />
External static pressure 0.60 in. wg<br />
Economizer static pressure 0.04 in. wg<br />
Total static pressure 0.64 in. wg<br />
Enter the Fan Performance table 48TJ016 (page 45)<br />
at 4,500 cfm and 0.64 in. wg external static pressure.<br />
By interpolation, find that the rpm is 988 and the watts<br />
are 1334.<br />
V Determine net cooling capacity.<br />
Cooling capacities are gross capacities and do not include<br />
indoor (evaporator) fan motor (IFM) heat. Use<br />
the watts input power to the motor calculated in Section<br />
IV above.<br />
IFM Watts = 1334<br />
Determine net cooling capacity using the following<br />
formula:<br />
Net capacity = Gross capacity – IFM heat<br />
= 180,000 Btuh – 1334 Watts<br />
(3.412 Btuh )<br />
Watts<br />
= 180,000 Btuh – 4552 Btuh<br />
= 175,448 Btuh<br />
Net sensible capacity = 120,000 Btuh – 4552 Btuh<br />
= 115,448 Btuh<br />
The calculations show that a 48TJE016 unit with the<br />
standard motor and a field-supplied drive is the correct<br />
selection for the given conditions.