1.0 SCOPE:<br />

<strong>TECHNICAL</strong> <strong>SPECIFICATION</strong> <strong>FOR</strong> <strong>METER</strong> <strong>BOARD</strong><br />

<strong>FOR</strong> <strong>Service</strong> connections<br />

1.1 This specification covers manufacture and supply of meter board with excellent<br />

weather-ability so as to offer protection against harsh weather. The box shall be<br />

anti-corrosive, dust proof, shock, vermin & waterproof, fire proof and UV<br />

stabilized. The meter board shall not deform or melt when exposed to fire.<br />

2.0 MATERIAL OF <strong>METER</strong> <strong>BOARD</strong>:<br />

2.1 The meter board shall be made out of<br />

2.1.1 Thermosetting plastic e.g. glassfibre reinforced polyester SMC (Sheet Moulding<br />

Compound) as per S1 grade of IS: 13410, or Glass Reinforced Polyester Dough<br />

Moulding Compounds as per Grade D1 of IS 13411, with flame retardant<br />

properties and mechanical & corrosion resistant properties. The overall<br />

dimensions of meter board shall be as per Annexure or as specified by the owner.<br />

OR<br />

2.1.2 Polycarbonate with UV stabilized & fire resistant properties.<br />

2.2 All accessories of MS, like nuts, bolts, washers etc., shall be galvanized.<br />

3.0 CONSTRUCTION<br />

3.1 The meter board shall be single piece moulded.<br />

3.2 Fixing arrangement:<br />

The meter meter board shall have 4 nos. 6 mm dia holes for mounting the meter<br />

board on a wall with suitable screws. The mounting arrangement shall be designed<br />

in such a way that the board is securely held on to the wall with proper guides for<br />

the screws.<br />

3.3 Inlet and Outlet:<br />

Suitable number of holes shall be provided in the meter board for cable/wire entry<br />

as required. The size of the holes shall be suitably modified depending on the size<br />

of the cable used for connections. Thickness of the meter board shall not be less<br />

than 2.5 mm.<br />

3.4 The meter board shall generally comply with the provision of IS14772 or IEC 695.<br />

The meter board shall be suitable for outdoor/indoor application. The meter board<br />

shall be with good workmanship.<br />

3.5 The color of meter board shall be off white/admiral grey or as specified by the<br />

owner.<br />

3.6 Wherever required ribs of adequate thickness shall be provided beneath the face of<br />

the board.<br />

3.7 While moulding the meter boards upto 20 %( max) resin regrind may be used with<br />

virgin material. The manufacturer shall declare the permissible regrind to be mixed


with virgin material & all type tests shall be conducted on items moulded with the<br />

maximum permissible regrind.<br />

3.8 It shall be possible to replace the switches/holders etc. without the need to remove<br />

the meter board from the wall. Wherever required metallic inserts shall be provided<br />

for fixing for fittings with screws. Screws fixing means shall be so designed that<br />

they withstand the mechanical stresses during installation and normal use. Test for<br />

this shall be carried out in line with clause 11.8 IS:14772<br />

3.9 Marking:<br />

The name of the manufacturer along with month & year of manufacture shall be<br />

engraved/moulded on the bottom half of the meter board.<br />

4.0 Sample Meter Board:<br />

4.1 The manufacturer shall submit a sample meter board before commencement of bulk<br />

production. The bulk production and supplies shall commence only after approval of<br />

sample & type test reports by the owner.<br />

5.0 Quality Control:<br />

5.1 Type test report for UV stabilization test as per ASTMG 53/26/23 on the material<br />

used for making the board shall be submitted for approval. Type test reports from<br />

NABL accredited laboratory in accordance with clause 5 of IS: 14772 for the<br />

following tests as per IS 14772 shall be submitted for approval. The type test reports<br />

shall not be older than 5 years.<br />

a) Marking<br />

b) Dimensions<br />

c) Construction - Test for screw fixing means as per clause 11.8 of IS: 14772<br />

d) Resistance to ageing & to climatic condition as per clause 12.1.1 of IS: 14772<br />

e) Resistance to humid condition as per clause 12.2 of IS: 14772<br />

f) Mechanical strength as per clause 13.2 of IS: 14772<br />

g) Resistance to heat as per clause 14.2 of IS: 14772<br />

h) Resistance to abnormal heat and fire (Glow wire test) as per clause 15 of IS:<br />

14772 at a temperature of 650 deg.C<br />

i) Drop test- The meter board shall not get damaged or deformed when dropped<br />

from a height of 2 meters on to concrete floor.<br />

5.2 The owner may witness acceptance tests as per IS 14772 or any other applicable<br />

standard. All tests shall be carried out on every batch of manufacturing. All test<br />

records shall be maintained with proper correlation. IS 13360 ‘Plastics – Methods of<br />

Testing’ shall be referred wherever required.<br />

Following Acceptance tests shall be carried out in every lot:<br />

a) Marking<br />

b) Dimensions including thickness of material<br />

c) Test for screw fixing means as per clause 11.8 of IS: 14772<br />

d) Resistance to ageing to climatic condition as per clause 12.1.1 of IS: 14772<br />

e) Resistance to humid condition as per clause 12.2 of IS: 14772


f) Mechanical strength as per clause 13.2 of IS: 14772<br />

g) Resistance to heat as per clause 14.2 of IS: 14772<br />

h) Resistance to abnormal heat and fire (Glow wire test) as per clause 15 of IS:<br />

14772 at a temperature of 650 deg.C.<br />

i) Drop test- The meter board shall not get damaged or deformed when dropped<br />

from a height of 2 meters on to concrete floor


GUARANTEED <strong>TECHNICAL</strong> PARTICULARS <strong>FOR</strong><br />

<strong>METER</strong> <strong>BOARD</strong><br />

S.No. Description<br />

1. Maker’s Name & Address<br />

2. Material<br />

3. Grade of material<br />

4. Thickness of face /sides/ribs<br />

5. Properties of material of construction<br />

a) UV resistance<br />

b) Heat deflection temperature Deg. C<br />

c) Meter board to flame as per IS:14772<br />

d) Contact with glowing hot body as per IS:14772<br />

6. Dimensions<br />

a) Length/Breadth<br />

b) Depth<br />

c) Thickness<br />

7. Colour of Meter Enclosure<br />

8. Ribs provided or not<br />

11. Metallic Inserts for screws provided or not for<br />

mounting of switches & fixtures.<br />

12. Mass/unit volume