26<br />

Cast Iron Condensing <strong>Boiler</strong>s – Installation <strong>Manual</strong><br />

KN Series "Heat Net Control" Troubleshooting (Firing the KN <strong>Boiler</strong>)<br />

Variable Frequency<br />

Drive<br />

Operate Blower<br />

Motor @ 0%<br />

Operate Blower<br />

Motor @ 0%<br />

Operate Blower<br />

Motor @ ~55%<br />

Operate Blower<br />

Motor @ ~32%<br />

Operate Blower<br />

Motor @ Min Fire,<br />

then Modulate to<br />

maintain temp<br />

DISPLAY:<br />

STANDBY<br />

DISPLAY:<br />

HEATING:<br />

J4 Pins 4 & 8<br />

KN Control Functions<br />

Ignition Sequence<br />

If Yes, do<br />

not operate<br />

blower.<br />

J4 Pins 4 & 8<br />

DISPLAY:<br />

PRE PURGE<br />

NO<br />

NO<br />

J4 Pins 4 & 8<br />

DISPLAY:<br />

PILOT:<br />

J4 Pins 4 & 8<br />

DISPLAY:<br />

RUN % 25<br />

CALL FOR<br />

HEAT?<br />

YES<br />

NO<br />

NO<br />

YES<br />

Start Circulator<br />

Interlocks OK?<br />

NO<br />

YES<br />

Are we below the<br />

Temp Band?<br />

Close the Last<br />

limit in the Limit<br />

String to Ignition<br />

Control<br />

INPUTS:<br />

1. MODBUS<br />

2. AA<br />

3.Heat Demand<br />

4. 4-20ma<br />

5. T1-T4<br />

J5 Pin 3<br />

Have We<br />

"BLOWER"<br />

received the<br />

"BLOWER"<br />

signal?<br />

YES<br />

NO<br />

PRE_PURGE<br />

PILOT signal?<br />

J5 Pin 2<br />

"PILOT"<br />

PILOT<br />

YES<br />

YES<br />

J13 "CIRC"<br />

YES, fire the boiler.<br />

"MAIN VALVE"<br />

greater than 7 VAC<br />

PILOT Ignition<br />

MAIN signal?<br />

1. Minimum fire rate<br />

2. Hold for (x) secs.<br />

3. Modulate to temp<br />

J5, J11A,J11B<br />

Setpoint - 1/2<br />

Heat Band<br />

J5 Pin 10<br />

"LIMITS"<br />

J5 Pin 1<br />

"MAIN"<br />

Hand Shake<br />

LIMITS<br />

BLOWER<br />

MAIN<br />

Ignition Contrrol<br />

(Honeywell S7800)<br />

TERM 6<br />

"LIMITS"<br />

Send 120 VAC<br />

BLOWER signal<br />

TERM 4<br />

"MOTOR"<br />

TERM 8<br />

"PILOT"<br />

After 10 Seconds<br />

send PILOT signal<br />

TERM 9<br />

"MAIN"<br />

NO<br />

Limits OK?<br />

YES<br />

FLAME?<br />

YES<br />

After 10 Seconds<br />

send MAIN<br />

VALVE signal