Cast Iron Condensing <strong>Boiler</strong>s – Installation <strong>Manual</strong><br />
CONDENSATE PIPING<br />
The condensate trap provided with the boiler must be<br />
attached to the bottom pan and piped to a suitable fl oor<br />
drain (consult local code) or condensate pump. If a<br />
condensate neutralization device is required by local<br />
code, it must be positioned prior to boiler room drain. Fill<br />
the condensate trap with water, check and maintain water<br />
level in trap during operation prior to start-up.<br />
Figure 16 - KN Series Condensate Drain<br />
GAS SUPPLY PIPING<br />
Check the boiler rating plate to make sure that<br />
the boiler is for the type of gas that<br />
will be used. If it isn’t, do not connect the<br />
boiler to the gas supply. Failure to comply with<br />
this warning can result in extensive property<br />
damage, severe personal injury or death!<br />
The KN comes from the factory ready to be piped to<br />
the gas supply. If for any reason the boiler is not for the<br />
type of gas available at the installation site, call your<br />
HydroTherm representative to resolve the problem.<br />
Table 8 should be used to ensure that the gas supply<br />
piping is sized properly. If more than one appliance is<br />
supplied by the same supply pipe, the piping must be<br />
sized based on the maximum possible demand. Do not<br />
neglect the pressure drop due to pipe fi ttings. Table 8<br />
should be used in conjunction with Table 9 to ensure<br />
that the gas supply piping has the capacity to meet the<br />
demand.<br />
Figure 17 depicts the proper way to connect the boiler<br />
to the gas supply piping. The manual shut-off valve<br />
MUST be installed in the supply piping. It should be<br />
installed 5 ft, 1 m above the fl oor where required by<br />
local codes. Provide a sediment trap at the bottom of the<br />
vertical section of the gas supply pipe upstream of the<br />
gas controls.<br />
A ground joint union should be installed between the<br />
boiler gas controls and the supply piping. Each of these<br />
items are needed to ensure long life and ease of<br />
servicing. Always use a pipe sealant that is suitable for<br />
use with with the type of gas (NG/LP) being used.<br />
Table 8 - Gas Pipe Capacity<br />
Maximum pipe capacity in ft 3 /hr based on 0.60 specifi c gravity gas<br />
at a pressure of 0.5 psig or less and a 0.3" WC pressure drop.<br />
Nominal<br />
Pipe length in feet<br />
Iron Pipe 10 20 30 40 50 60 80 100 150<br />
Size<br />
Maximum gas volume of pipe (ft3 /hr)<br />
1" 520 350 285 245 215 195 170 150 120<br />
11 /4" 1050 730 590 500 440 400 350 305 250<br />
11 /2" 1600 1100 890 760 670 610 530 460 380<br />
2" 3050 2100 1650 1450 1270 1150 990 870 710<br />
Note: Multiply the gas volume by 0.62 for propane fl ow capacity in<br />
ft3 /hr. Multiply the propane fl ow capacity by 2500 Btu/ft3 to determine<br />
the propane Btu/hr capacity for a given pipe size and length.<br />
19