Cast Iron Condensing <strong>Boiler</strong>s – Installation <strong>Manual</strong><br />

Primary/Secondary Piping<br />

Although acceptable, the system is not as cost effective<br />

as reverse return piping. Figure 12 shows a typical<br />

primary/secondary piping system. A dedicated pump is<br />

used to maintain a constant water fl ow through the<br />

boiler. Systems using multiple boilers can be installed<br />

using a primary/secondary manifold system, Figure 13.<br />

Piping For Use With Cooling Units<br />

The boiler, when used in connection with a refrigeration<br />

system, must be installed so the chilled medium is piped<br />

in parallel with the boiler. Appropriate valves must be used<br />

to prevent the chilled water from entering the boiler.<br />

Figure 10 - Typical Single <strong>Boiler</strong> Piping (RECOMMENDED)<br />

(Circulator pump must be sized for minimum water fl ow rate of boiler, including system pressure drop)<br />

HIOM-64<br />

When a boiler is connected to a heating coil that may<br />

be exposed to refrigerated air from an air handling<br />

device, the piping system must be equipped with fl owcontrol<br />

valves or some other automatic means of<br />

preventing gravity circulation of the boiler water during<br />

the cooling cycle.<br />

It is essential that following boiler shut off,<br />

the boiler pump continue to operate for<br />

approximately (5) minutes to dissipate the<br />

heat away from the heat exchanger.<br />

15