Cast Iron Condensing <strong>Boiler</strong>s – Installation <strong>Manual</strong><br />

GENERAL PIPING REQUIREMENTS<br />

Improper piping of this boiler will void the<br />

manufacturer’s warranty and can cause boiler<br />

failure resulting in flooding and extensive<br />

property damage!<br />

Shut off valves and unions should be<br />

installed at the inlet and outlet connections<br />

of the boiler to provide for isolation of the<br />

unit should servicing be necessary.<br />

Relief Valve<br />

Pipe the discharge of the pressure relief valve as shown<br />

in Figure 9. Mount on rear section or vertically on supply<br />

nipple.<br />

Never install any type of valve between the<br />

boiler and the relief valve or an explosion<br />

causing extensive property damage, severe<br />

personal injury or death may occur!<br />

Flow Switch<br />

The fl ow switch (optional on KN-6, 10, and 20; standard<br />

on KN-16, 26 and 30) is wired to prevent the boiler from<br />

fi ring unless there's adequate water fl ow through the<br />

unit.<br />

If using the optional flow switch, failure to<br />

maintain the minimum flow rates listed in<br />

Table 6 at the boiler outlet will prevent the<br />

fl ow switch from closing. If a minimum fl ow<br />

rate cannot be maintained at the boiler outlet<br />

the fl ow switch will have to be relocated in the<br />

system.<br />

Table 6<br />

Water<br />

Flow Rates<br />

(GPM)<br />

Increase flow rates approximately 30% for glycol<br />

mixtures.<br />

Figure 9 - Relief Valve Piping<br />

*ΔT Across<br />

Heat Exchanger<br />

Min. Max. Min. * Max.<br />

KN-6 10 100 20°F 100°F<br />

KN-10 15 150 20°F 100°F<br />

KN-16 24 240 20°F 100°F<br />

KN-20 30 300 20°F 100°F<br />

KN-26 38 380 20°F 100°F<br />

KN-30 45 450 20°F 100°F<br />

*Min/Max Δt corresponds to full input, for applications<br />

requiring operation above and/or below these parameters,<br />

please consult manufacturer.<br />