ings codes for wood structural panels used to resist seismic forces without<br />

further reduction in design values. Two walls of each sheathing material<br />

were tested under both monotonic and cyclic loading. All walls in this<br />

study incorporated the use of overturning anchors in the form of mechanical<br />

hold-downs. The monotonic tests were conducted according to ASTM<br />

E564, while the cyclic tests were conducted to the recently adopted ASTM<br />

standard E2126. A comparison of the monotonic and cyclic tests leads to<br />

several key dissimilarities. In general, the performance of the shear walls<br />

when tested cyclically decreased, although the degree of reduction depends<br />

on the sheathing material. Hardboard panels tested under cyclic<br />

loading performed similar to the monotonic tests. The peak load during<br />

cyclic tests was actually larger than its corresponding monotonic test. Fiberboard<br />

panels also performed in a similar manner when tested under cyclic<br />

and monotonic loading. OSB panels did not perform as well when<br />

subjected to cyclic loading. The peak load was reduced by 12%, and the<br />

energy dissipation was 27% lower when tested under cyclic loading. Gypsum<br />

panels performed poorly under cyclic loading. Peak load reduction<br />

was 16%, failure displacement decreased by 38mm (1.5 in.), and the<br />

amount of energy dissipation was nearly reduced by one-half when subjected<br />

to cyclic loading.<br />

Conclusions<br />

A total of 31 walls were tested during this study to determine and compare<br />

the effects of monotonic and cyclic loading on shear walls with various<br />

sheathing materials. The sheathing materials investigated are oriented<br />

strand board (OSB), hardboard, fiberboard, and gypsum wallboard. All of<br />

the walls were 1.2 x 2.4 m (4 x 8 ft), and to be conservative there were no<br />

gravity loads applied to the walls. All of the tests were performed with<br />

hold-downs. Monotonic tests were performed according to ASTM E564,<br />

while the cyclic tests were performed according to ASTM E2126. The<br />

conclusions drawn from the cyclic tests are:<br />

(1) In general, the performance parameters decreased when the cyclic<br />

tests were compared to the monotonic tests. The most drastic reduction<br />

was observed during the gypsum-sheathed tests, followed by the<br />

OSB-sheathed tests.<br />

(2) Hardboard panels tested under cyclic loading performed similar to the<br />

monotonic tests. The peak load during cyclic tests was actually larger<br />

than its corresponding monotonic test (8%). The displacement at fail-<br />

ure decreased by 9%, and the energy dissipation was reduced by only<br />

4% when subjected to cyclic loading.<br />

(3) Fiberboard panels also performed in a similar manner when tested under<br />

cyclic and monotonic loading. The peak load only decreased by<br />

0.27 kN (0.06 kips), which was a reduction of 4%. The displacement<br />

at failure decreased by 7%, and the energy dissipation was reduced by<br />

5% when subjected to cyclic loading.<br />

(4) OSB panels tested cyclically did not perform as well as when tested<br />

monotonically. The peak load reduction was 1.33 kN (0.3 kips), or<br />

12%, and the energy dissipation was 27% lower when tested under<br />

cyclic loading.<br />

(5) Gypsum panels performed poorly under cyclic loading. The peak load<br />

reduction was 16%, the failure displacement decreased by 38mm (1.5<br />

in.), and the amount of energy dissipation was nearly reduced by onehalf<br />

when subjected to cyclic loading.<br />

37-15-1 M Yasumura, M Uesugi, L Davenne<br />

Estimating 3D behavior of conventional timber structures with shear<br />

walls by pseudodynamic tests<br />

Abstract<br />

One of the most important causes of the seismic damage of timber buildings<br />

is the unbalance of the lateral resistance of shear walls and the lack<br />

of the shear stiffness of the horizontal diaphragm. These damages were often<br />

observed during the 1995 Hyogoken-Nanbu Earthquake on conventional<br />

commercial buildings that had large openings in front of the building.<br />

The objective of this research is to analyse the influence of the unbalance<br />

of the lateral resistance of shear walls and the shear stiffness of the<br />

horizontal diaphragm on 3D dynamic behaviour of the structures by pseudo-dynamic<br />

tests. The specimens were conventional post and beam timber<br />

structures with shear walls of 3m width, 3 m depth and 3m height. Specimens<br />

had 7.5 mm plywood sheathed shear walls and a horizontal diaphragm<br />

sheathed with 24mm thick plywood. There were two types of horizontal<br />

diaphragms, i.e., the rigid diaphragm in which all the perimeters of<br />

plywood sheathings were nailed and the semi-rigid one that were only<br />

nailed in transversal direction. Four specimens with different combination<br />

of shear walls and diaphragms were prepared. Specimens WW-R and<br />

WW-S had shear walls with window opening in both loading direction and<br />

<strong>CIB</strong>-<strong>W18</strong> Timber Structures – A review of meeting 1-43 5 SPECIAL ACTIONS page 5.22

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!