WwTW<br />

Haddenham<br />

Witchford<br />

Littleport<br />

Little<br />

Downham<br />

Witcham<br />

Consent<br />

parameter<br />

Stage 2 <strong>Water</strong> <strong>Cycle</strong> <strong>Study</strong>: Final Report<br />

Sept 2011<br />

Current<br />

consent<br />

standards<br />

Consent<br />

limits<br />

required for<br />

no<br />

deterioration<br />

consent<br />

P 2 20 1<br />

BOD 20A 19<br />

NH4 5 4<br />

P -<br />

No change<br />

required<br />

BOD 20A 18<br />

NH4 12 11<br />

P -<br />

No change<br />

required<br />

33<br />

Process assessment<br />

- Upgrade required?<br />

It is likely that the<br />

change to the consent<br />

could be<br />

accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

It is likely that the<br />

change to the consent<br />

could be<br />

accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

No<br />

It is likely that the<br />

change to the consent<br />

could be<br />

accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

It is likely that the<br />

change to the consent<br />

could be<br />

accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

BOD 15A 12 Yes<br />

It is likely that the<br />

change to the consent<br />

NH4 5 4<br />

could be<br />

accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

P - 1.7 Yes<br />

BOD 15A 14 It is likely that the<br />

change to the consent<br />

could be<br />

NH4 10 9 accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

P -<br />

No change<br />

required<br />

No<br />

BOD 12A 11 It is likely that the<br />

change to the consent<br />

could be<br />

NH4 6 5 accommodated within<br />

the existing process<br />

capacity of the WwTW<br />

No<br />

<strong>Cambridgeshire</strong> Horizons<br />

<strong>East</strong> <strong>Cambridgeshire</strong> – <strong>Detailed</strong> WCS<br />

Is there space<br />

to expand<br />

WwTW<br />

Yes, if adjacent<br />

land is available<br />

Yes, if adjacent<br />

land is available<br />

Yes, if adjacent<br />

land is available<br />

Yes, if adjacent<br />

land is available<br />

Yes, if adjacent<br />

land is available<br />

20 Soham WwTWs has a PE greater than 10,000 and discharges to a ‘Sensitive Areas (Eutrophic)’ as designated under the UWWTD,<br />

it is therefore required that either: a) the effluent achieves 2 mg/l of P as an annual average; or b) 80% of influent P is removed by the<br />

treatment process. Although the WwTW does not have a formal P consent value, it has been assumed for calculation purposes that<br />

a 2mg/l consent standard applies.