06.03.2013 Views

buletinul institutului politehnic din iaşi - Universitatea Tehnică ...

buletinul institutului politehnic din iaşi - Universitatea Tehnică ...

buletinul institutului politehnic din iaşi - Universitatea Tehnică ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

BULETINUL INSTITUTULUI POLITEHNIC DIN IAŞI<br />

Publicat de<br />

<strong>Universitatea</strong> <strong>Tehnică</strong> „Gheorghe Asachi“ <strong>din</strong> Iaşi,<br />

Tomul LVIII (LXII), Fasc. 4, 2012<br />

Secţia<br />

CONSTRUCŢII DE MAŞINI<br />

EXPERIMENTAL RESULTS ON A VAPOUR INJECTION<br />

SCROLL COMPRESSOR<br />

BY<br />

ION ZABET 1 and GRAŢIELA-MARIA ŢÂRLEA ∗2<br />

1 Romanian General Association of Refrigeration of Bucharest,<br />

2 Technical University of Civil Engineering of Bucharest<br />

Received: September 12, 2012<br />

Accepted for publication: November 20, 2012<br />

Abstract. This paper presents experimental results from a vapour injection<br />

scroll compressor system. The purpose of this paper is to test a vapour injection<br />

scroll compressor for a heat pump. For the measurements, the inputs were given<br />

by different pressure values (evaporation and condensation process). On this test<br />

rig we mount a pressure sensor on the evaporator supply and a new system of<br />

expansion valves. This new system of the expansion valves allow us to extend<br />

the tests matrix to a wide range of capacities and a higher control over the<br />

system. The expansion valves are mounted three on the evaporator and two on<br />

the injection evaporator. The work is conducted in two phases: the first phase of<br />

the rig consists in the set-up of a test rig, its instrumentation, the calibration of<br />

the measurements devices, the set-up of the data acquisition system and a few<br />

verification tests and the second phase consists in the achievement of the 100<br />

tests. The last part of the paper presents the results obtained by the experimental<br />

model. These results are: performance coefficient, power consumption,<br />

exhausted compressor temperature and refrigerant charge of the refrigerant<br />

R404A in different working conditions.<br />

Key words: vapour injection scroll compressor, exhausted compressor<br />

temperature, refrigerant charge and heat exchanger.<br />

1. Introduction<br />

The purpose of this study is to test a vapour injection scroll compressor<br />

and find a simplify model for a heat pump (Lemort, 2008), (Winandy & Lebrun,<br />

∗ Correspon<strong>din</strong>g author: e-mail: gratiela.tarlea@gmail.com