AIR & WATER COOLED<br />

40<br />

-DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

REFRIGERANT PIPE<br />

SIZING GUIDE -<br />

X TYPE MODELS<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Pipe lengths calculated for Indoor unit with standard Outdoor CE Condenser match. For<br />

Condenser unit connections sizes, please refer to Condenser Installation <strong>Manual</strong>.<br />

Indoor Outdoor Indoor Unit<br />

Equivalent Pipe Lengths with R407C<br />

Connection Size<br />

0-15m 15-40m<br />

Liquid Discharge Liquid<br />

Discharge<br />

Horizontal<br />

Liquid<br />

Discharge<br />

(1) Vertical (2) Horizontal (1) Vertical (2)<br />

DF6X C11 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF8X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF10X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF13X C20 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF15X C25 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF17X C35 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF22X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 7/8” 7/8”<br />

DF25X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 1 1/8” 7/8”<br />

DF26X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF28X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF31X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF35X CS50 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 3/8” 1 1/8”<br />

DF40X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 3/4” 1 3/8” 1 3/8”<br />

DF45X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 3/8” 1 3/8”<br />

DF50X2 CS65 7/8” 1 3/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 5/8” 1 3/8”<br />

DF55X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 3/8” 7/8” 1 5/8” 1 5/8”<br />

DF60X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 5/8” 1 1/8” 1 5/8” 1 5/8”<br />

(1) For interconnecting pipework with a predominantly horizontal layout.<br />

(2) For interconnecting pipework with a predominantly vertical layout.<br />

REFRIGERANT<br />

CHARGING GUIDE -<br />

X TYPE MODELS<br />

Unit Refrigerant Charge<br />

(kg/Circuit)<br />

The following information can be used to estimate the refrigerant quantity required in a<br />

typical split system installation.<br />

The following table shows the refrigerant charge / circuit for the indoor and outdoor units.<br />

Indoor Unit Standard Condenser Upgraded Condenser<br />

(IR) kg/Circuit (OR) kg/Circuit (OR) kg/Circuit<br />

DF6X-EZ 2.0 C11 2.1 C15 2.1<br />

DF8X-EZ 2.0 C15 2.1 C20 2.3<br />

DF10X-EZ 2.0 C15 2.1 C20 2.3<br />

DF13X-EZ 3.2 C20 2.3 C25 3.1<br />

DF15X-EZ 3.2 C25 3.1 C35 6.1<br />

DF17X-EZ 3.2 C35 6.1 C45 6.1<br />

DF22X2-EZ 4.1 C45 6.1 CS50 4.3<br />

DF25X2-EZ 4.1 C45 6.1 CS50 4.3<br />

DF26X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF28X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF31X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF35X-EZ 6.5 CS50 4.3 CS65 8.5<br />

DF40X-EZ 6.5 CS50 4.3 CS65 8.5<br />

DF45X2-EZ 7.9 CS50 4.3 CS65 8.5<br />

DF50X2-EZ 7.7 CS65 8.5 CS80 7.3<br />

DF55X2-EZ 9.4 CS80 7.3 CS105 14.6<br />

DF60X2-EZ 9.4 CS80 7.3 CS105 14.6