Design Data - <strong>Air</strong> & Water Cooled Models<br />
REFRIGERANT PIPE<br />
SIZING GUIDE -<br />
X TYPE MODELS<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
Pipe lengths calculated for Indoor unit with standard Outdoor CE Condenser match. For<br />
Condenser unit connections sizes, please refer to Condenser Installation <strong>Manual</strong>.<br />
Indoor Outdoor Indoor Unit<br />
Equivalent Pipe Lengths with R407C<br />
Connection Size<br />
0-15m 15-40m<br />
Liquid Discharge Liquid<br />
Discharge<br />
Horizontal<br />
Liquid<br />
Discharge<br />
(1) Vertical (2) Horizontal (1) Vertical (2)<br />
DF6X C11 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />
DF8X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />
DF10X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />
DF13X C20 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />
DF15X C25 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />
DF17X C35 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />
DF22X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 7/8” 7/8”<br />
DF25X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 1 1/8” 7/8”<br />
DF26X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />
DF28X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />
DF31X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />
DF35X CS50 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 3/8” 1 1/8”<br />
DF40X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 3/4” 1 3/8” 1 3/8”<br />
DF45X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 3/8” 1 3/8”<br />
DF50X2 CS65 7/8” 1 3/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 5/8” 1 3/8”<br />
DF55X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 3/8” 7/8” 1 5/8” 1 5/8”<br />
DF60X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 5/8” 1 1/8” 1 5/8” 1 5/8”<br />
(1) For interconnecting pipework with a predominantly horizontal layout.<br />
(2) For interconnecting pipework with a predominantly vertical layout.<br />
REFRIGERANT<br />
CHARGING GUIDE -<br />
X TYPE MODELS<br />
Unit Refrigerant Charge<br />
(kg/Circuit)<br />
The following information can be used to estimate the refrigerant quantity required in a<br />
typical split system installation.<br />
The following table shows the refrigerant charge / circuit for the indoor and outdoor units.<br />
Indoor Unit Standard Condenser Upgraded Condenser<br />
(IR) kg/Circuit (OR) kg/Circuit (OR) kg/Circuit<br />
DF6X-EZ 2.0 C11 2.1 C15 2.1<br />
DF8X-EZ 2.0 C15 2.1 C20 2.3<br />
DF10X-EZ 2.0 C15 2.1 C20 2.3<br />
DF13X-EZ 3.2 C20 2.3 C25 3.1<br />
DF15X-EZ 3.2 C25 3.1 C35 6.1<br />
DF17X-EZ 3.2 C35 6.1 C45 6.1<br />
DF22X2-EZ 4.1 C45 6.1 CS50 4.3<br />
DF25X2-EZ 4.1 C45 6.1 CS50 4.3<br />
DF26X-EZ 4.9 C45 6.1 CS50 4.3<br />
DF28X-EZ 4.9 C45 6.1 CS50 4.3<br />
DF31X-EZ 4.9 C45 6.1 CS50 4.3<br />
DF35X-EZ 6.5 CS50 4.3 CS65 8.5<br />
DF40X-EZ 6.5 CS50 4.3 CS65 8.5<br />
DF45X2-EZ 7.9 CS50 4.3 CS65 8.5<br />
DF50X2-EZ 7.7 CS65 8.5 CS80 7.3<br />
DF55X2-EZ 9.4 CS80 7.3 CS105 14.6<br />
DF60X2-EZ 9.4 CS80 7.3 CS105 14.6