Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF40X-EZ DF45X-EZ DF50X2-EZ DF55X2-EZ DF60X2-EZ<br />

DF40WX-EZ DF45WX-EZ DF50WX2-EZ DF55WX2-EZ DF60WX2-EZ<br />

Standard Matched Condensers - X CS50 CS50 CS65 CS80 CS80<br />

Unit Data - X (1)<br />

Nominal Run Amps A 72.60 75.70 90.50 91.20 97.60<br />

Maximum Start Amps A 194.70 224.70 204.80 196.70 201.50<br />

Recommended Mains Fuse Size A 80 100 100 100 125<br />

Max Mains Incoming Cable Size mm² 35 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 67 70.1 82.1 82.5 88.9<br />

Maximum Start Amps A 189.1 219.1 197.8 188 192.8<br />

Recommended Mains Fuse Size A 80 80 100 100 100<br />

Max Mains Incoming Cable Size mm² 35 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 5.5 1 x 5.5 2 x 2.2 2 x 2.2 2 x 3.0<br />

Full Load Amps A 10.9 10.9 4.7 4.7 6.3<br />

Locked Rotor Amps A 76.3 76.3 32.9 32.9 44.1<br />

Compressor - Per Compressor<br />

Quantity 1 1 2 2 2<br />

Nominal Run Amps A 22.9 26.0 14.3 14.5 16.1<br />

Locked Rotor Amps A 145.0 175.0 130.0 120.0 120.0<br />

Motor Size kW 11.9 13.2 7.8 8.5 9.7<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 2 x 0.78 2 x 0.78 3 x 0.78 3 x 0.78 3 x 0.78<br />

Full Load Amps A 3.50 3.50 3.50 3.50 3.50<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 3 3 3 3 3<br />

Number of Elements 8 8 12 12 12<br />

Rating (Total) kW 20.0 20.0 30.0 30.0 30.0<br />

Current Per Phase A 32.4 32.4 43.6 43.6 43.6<br />

Humidifier<br />

Capacity kg/hr 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00<br />

Rating kW 11.25 11.25 11.25 11.25 11.25<br />

Full Load Amps A 15.80 15.80 15.80 15.80 15.80<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW N/A N/A 2 x 3.0 2 x 3.0 2 x 4.0<br />

Full Load Amps A N/A N/A 6.3 6.3 8.2<br />

Locked Rotor Amps A N/A N/A 44.1 44.1 57.4<br />

Next Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW<br />

Motor Size kW N/A N/A 2 x 4.0 2 x 4.0 N/A<br />

Full Load Amps A N/A N/A 8.2 8.2 N/A<br />

Locked Rotor Amps A N/A N/A 57.4 57.4 N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors and<br />